Standard Ao - ABB ACS880 Firmware Manual

Dc/dc converter control program
Hide thumbs Also See for ACS880:
Table of Contents

Advertisement

68 Parameters
No.
Name/Value
112.29
AI2 scaled at AI2
min
-32768.000
...32768.000
112.30
AI2 scaled at AI2
max
-32768.000 ...
32767.000
113

113 Standard AO

113.11
AO1 actual value
0.000 ... 22.000 mA Value of AO1.
113.12
AO1 source
Zero
DC voltage
AO1 data storage
AO2 data storage
Other
113.16
AO1 filter time
0.000 ... 30.000 s
Description
Defines the real value of parameter
that corresponds to the minimum analog input AI2 value
defined by parameter
112.27 AI2
AI
scaled
112.30
112.27
Real value corresponding to minimum AI2 value.
Defines the real value of parameter
that corresponds to the maximum analog input AI2 value
defined by parameter
112.28 AI2
parameter
112.29 AI2 scaled at AI2
Real value corresponding to maximum AI2 value.
Configuration of analog outputs.
Value of AO1 in mA.
Selects a signal to be connected to analog output AO1.
None.
101.01 DC voltage
113.91 AO1 data storage
113.92 AO2 data storage
The value is taken from another parameter.
Defines the filtering time constant for analog output AO1.
%
Unfiltered signal
100
63
Filtered signal
T
-t/T
O = I × (1 - e
)
I = filter input (step)
O = filter output
t = time
T = filter time constant
Filter time constant.
112.22 AI2 scaled value
min.
(
)
112.22
AI
(
112.28
in
112.29
112.22 AI2 scaled value
max. See the drawing at
min.
(page 70).
(page 70).
t
Def/FbEq16
0.000
)
112.21
1 = 1
1920.000
1 = 1
-
1000 = 1 mA
Zero
0
1
37
38
-
0.100 s
1000 = 1 s