ABB ACS580 Firmware Manual page 120

General purpose drives standard control program
Hide thumbs Also See for ACS580:
Table of Contents

Advertisement

116 Program features
continues.
Motor speed
Reference
21.09 DC hold speed
Settings
Parameters
21.08 DC current control
Post-magnetization
The function keeps the motor magnetized for a certain period (parameter
magnetization
time) after stopping. This is to prevent the machinery from moving
under load, for example before a mechanical brake can be applied. Post-
magnetization is activated by parameter
current is set by parameter
Note: Post-magnetization is only available when ramp stop is selected (see
parameter
21.03 Stop
Settings
Parameters
21.03 Stop mode
heating input
source.
Pre-heating (Motor heating)
The pre-heating function keeps the motor warm and prevents condensation inside the
motor by feeding it with DC current when the drive has been stopped. The heating
can only be on when the drive is in the stopped state, and starting the drive stops the
heating.
When pre-heating is activated and the stop command is given, pre-heating starts
immediately if the drive is running below zero speed (see bit 0 in parameter
Speed control status
delayed by 60 seconds to prevent excessive current.
and
21.10 DC current
mode). Post-magnetization is only supported in vector control.
(page 197),
word). If the drive is running above zero speed, pre-heating is
DC hold
21.09 DC hold speed
21.08 DC current
control. The magnetization
reference.
21.08 DC current control
t
t
21.11 Post
and
21.11 Pre-
06.19