ABB ACS580 Firmware Manual page 254

General purpose drives standard control program
Hide thumbs Also See for ACS580:
Table of Contents

Advertisement

250 Parameters
No.
Name/Value
Inverter
temperature
Process PID output
Process PID
feedback
Process PID
setpoint
Process PID
deviation
Other
32.08
Supervision 1 filter
time
0.000 ... 30.000 s
32.09
Supervision 1 low
-21474836.00...
21474836.00
32.10
Supervision 1 high
-21474836.00...
21474836.00
32.11
Supervision 1
hysteresis
0.00...100000.00
32.15
Supervision 2
function
Disabled
Low
High
Abs low
Abs high
Both
Abs both
32.16
Supervision 2
action
No action
Warning
Fault
Description
05.11 Inverter temperature
40.01 Process PID output actual
40.02 Process PID feedback actual
40.03 Process PID setpoint actual
40.04 Process PID deviation actual
Source selection (see
Terms and abbreviations
Defines a filter time constant for the signal monitored by
signal supervision 1.
Signal filter time.
Defines the lower limit for signal supervision 1.
Low limit.
Defines the upper limit for signal supervision 1.
Upper limit.
Defines the hysteresis for the signal monitored by signal
supervision 1.
Hysteresis.
Selects the mode of signal supervision function 2. Determines
how the monitored signal (see parameter 32.17) is compared
to its lower and upper limits
The action to be taken when the condition is fulfilled is
selected by 32.16.
Signal supervision 2 not in use.
Action is taken whenever the signal falls below its lower limit.
Action is taken whenever the signal rises above its upper
limit.
Action is taken whenever the absolute value of the signal falls
below its (absolute) lower limit.
Action is taken whenever the absolute value of the signal
rises above its (absolute) upper limit.
Action is taken whenever the signal falls below its low limit or
rises above its high limit.
Action is taken whenever the absolute value of the signal falls
below its (absolute) low limit or rises above its (absolute) high
limit.
Selects whether the drive generates a fault, warning or
neither when the value monitored by signal supervision 2
exceeds its limits.
Note: This parameter does not affect the status indicated by
32.01 Supervision
status.
No warning or fault generated.
Warning
A8B1 Signal supervision 2
Drive trips on fault
80B1 Signal supervision
(page 151).
(page 278).
(page 278).
(page 278).
(page 279).
on page 144). -
(32.19
and
32.20
respectively).
is generated.
2.
Def/FbEq16
23
24
25
26
27
0.000 s
1000 = 1 s
0.00
-
0.00
-
0.00
-
Disabled
0
1
2
3
4
5
6
No action
0
1
2