62 Control macros

ABB standard (vector) macro

The ABB standard (vector) uses vector control; otherwise it is similar to the ABB standard
macro, providing a general purpose, 2-wire I/O configuration with three constant speeds. One
signal is used to start or stop the motor and another to select the direction. To enable the macro,
select it in the Primary settings menu or set parameter
(vector).
Default control connections for the ABB standard (vector) macro
1...10 kohm
max.
500 ohm
4)
See the notes on
the next page.
S1
AI1 U/I
6)
S2
AI2 U/I
XI
Reference voltage and analog inputs and outputs
1
2
3
AGND
4
5
6
AGND
7
8
9
AGND
6)
S3
AO1 I/U
3)
X2 & X3
Aux. voltage output and programmable digital inputs
10
11
DGND
4)
12
DCOM
13
14
15
16
17
18
X6, X7, X8 Relay outputs
19
20
21
22
23
24
25
26
27
X5
EIA-485 Modbus RTU
29
30
31
DGND
S4
S5
X4
Safe torque off
34
35
4)
36
SGND
37
38
X10
24 V AC/DC
40
24 V AC/DC+ in R6...R11 only: Ext. 24V AC/DC input to power up the
5)
41
24 V AC/DC- in
96.04 Macro select
Voltage/Current selection for AI1:
Voltage/Current selection for AI2:
SCR
Signal cable shield (screen)
AI1
Output Speed reference: 0...10 V
Analog input circuit common
+10V
Reference voltage 10 V DC
AI2
Not configured
Analog input circuit common
AO1
Output frequency: 0...20 mA
AO2
Motor current: 0...20 mA
Analog output circuit common
Voltage/Current selection for AO1:
+24V
Auxiliary voltage output +24 V DC, max. 250 mA
Auxiliary voltage output common
Digital input common for all
DI1
Stop (0) / Start (1)
DI2
Forward (0) / Reverse (1)
DI3
Speed selection
DI4
Speed selection
DI5
Ramp set 1 (0) / Ramp set 2 (1)
DI6
Not configured
RO1C
Ready run
250 V AC / 30 V DC
RO1A
2 A
RO1B
RO2C
Running
RO2A
250 V AC / 30 V DC
2 A
RO2B
RO3C
Fault (-1)
250 V AC / 30 V DC
RO3A
2 A
RO3B
B+
Embedded Modbus RTU (EIA-485). See chapter
Fieldbus control through the embedded fieldbus
A-
interface (EFB)
TERM
Serial data link termination switch
BIAS
Serial data link bias resistors switch
OUT1
Safe torque off. Factory connection. Both circuits
OUT2
must be closed for the drive to start. See chapter
The Safe torque off function in the Hardware
IN1
manual of the drive.
IN2
control unit when the main supply is disconnected.
to
ABB standard
U
U
1)
I
1)
1)
2)
on page 399.
I
I
U