Terminal sizes:
R0...R5: 0.2...2.5 mm
0.14...1.5 mm
R6...R9: 0.14...2.5 mm
Tightening torques: 0.5...0.6 N·m (0.4 lbf·ft)
Notes:
1)
See Menu - Primary settings - Start, stop, reference - Constant frequencies or parameter
group
28 Frequency reference
DI3
DI4
0
0
1
0
0
1
1
1
2)
See Menu - Primary settings - Ramps or parameter group
DI5 Ramp set
0
1
1
2
3)
Ground the outer shield of the cable 360 degrees under the grounding clamp on the
grounding shelf for the control cables.
4)
Connected with jumpers at the factory.
5)
Only frames R6...R11 have terminals 40 and 41 for external 24 V AC/DC input.
6)
All control boards do not have switches S1, S2 and S3. In that case, select voltage or current
for inputs AI1 and AI2 and output AO1 with parameters 12.15,
Input signals
•
Analog frequency reference (AI1)
•
Start/stop selection (DI1)
•
Direction selection (DI2)
•
Constant frequency selection (DI3, DI4)
•
Ramp set (1 of 2) selection (DI5)
Output signals
•
Analog output AO1: Output frequency
•
Analog output AO2: Motor current
•
Relay output 1: Ready run
•
Relay output 2: Running
•
Relay output 3: Fault (-1)
2
(terminals +24V, DGND, DCOM, B+, A-)
2
(terminals DI, AI, AO, AGND, RO, STO)
2
(all terminals)
chain.
Operation/Parameter
Set frequency through AI1
28.26 Constant frequency 1
28.27 Constant frequency 2
28.28 Constant frequency 3
Parameters
28.72 Freq acceleration time 1
28.73 Freq deceleration time 1
28.74 Freq acceleration time 2
Freq deceleration time 2
Control macros 61
28 Frequency reference
12.25
and 13.15, respectively.
chain.