326 Parameters
No.
Name/Value
95.20
HW options word 1
Bit
Name
0
Supply frequency
60 Hz
1...11
Reserved
12
du/dt filter
activation
13...15 Reserved
0000h...FFFFh
96

96 System

96.01
Language
Not selected
English
Deutsch
Italiano
Español
Portugues
Nederlands
Français
Dansk
Suomi
Svenska
Russki
Polski
Türkçe
Chinese (Simplified,
PRC)
Description
Specifies hardware-related options that require differentiated
parameter defaults.
This parameter is not affected by a parameter restore.
Value
If you change the value of this bit, you have to do a complete reset to
the drive after the change. After reset you have to reselect the macro
to be used.
See section
Differences in the default values between 50 Hz and
60 Hz supply frequency settings
1 = 60 Hz.
When active, an external du/dt filter is connected to the drive/inverter
output. The setting will limit the output switching frequency, and
force the fan of the drive/inverter module to full speed.
0 = du/dt filter inactive.
1 = du/dt filter active.
Hardware options configuration word.
Language selection; access levels; macro selection;
parameter save and restore; control unit reboot; user
parameter sets; unit selection.
Selects the language of the parameter interface and other
displayed information when viewed on the control panel.
Notes:
• Not all languages listed below are necessarily supported.
• This parameter does not affect the languages visible in the
Drive composer PC tool. (Those are specified under View
– Settings – Drive default language.)
None.
English.
German.
Italian.
Spanish.
Portuguese.
Dutch.
French.
Danish.
Finnish.
Swedish.
Russian.
Polish.
Turkish.
Simplified Chinese.
Def/FbEq16
-
on page 343.0 = 50 Hz.
1 = 1
-
0
1033
1031
1040
3082
2070
1043
1036
1030
1035
1053
1049
1045
1055
2052