Start/Stop Mode - ABB ACS580 Firmware Manual

General purpose drives standard control program
Hide thumbs Also See for ACS580:
Table of Contents

Advertisement

196 Parameters
No.
Name/Value
21

21 Start/stop mode

21.01
Vector start mode
Fast
Const time
Automatic
Description
Start and stop modes; emergency stop mode and signal
source selection; DC magnetization settings.
Selects the motor start function for the vector motor control
mode, ie. when
99.04 Motor control mode
Notes:
• The start function for the scalar motor control mode is
selected by parameter
• Starting into a rotating motor is not possible when DC
magnetizing is selected
• With permanent magnet motors,
must be used.
• This parameter cannot be changed while the drive is
running.
See also section
DC magnetization
The drive pre-magnetizes the motor before start. The pre-
magnetizing time is determined automatically, being typically
200 ms to 2 s depending on motor size. This mode should be
selected if a high break-away torque is required.
The drive pre-magnetizes the motor before start. The pre-
magnetizing time is defined by parameter
Magnetization
time. This mode should be selected if constant
pre-magnetizing time is required (e.g. if the motor start must
be synchronized with the release of a mechanical brake).
This setting also guarantees the highest possible break-away
torque when the pre-magnetizing time is set long enough.
WARNING! The drive will start after the set
magnetizing time has passed even if motor
magnetization is not completed. In applications where
a full break-away torque is essential, ensure that the constant
magnetizing time is long enough to allow generation of full
magnetization and torque.
Automatic start guarantees optimal motor start in most cases.
It includes the flying start function (starting into a rotating
motor) and the automatic restart function. The drive motor
control program identifies the flux as well as the mechanical
state of the motor and starts the motor instantly under all
conditions.
Note: If parameter
99.04 Motor control mode
no flying start or automatic restart is possible unless
parameter
21.19 Scalar start mode
is set to Vector.
21.19 Scalar start
mode.
(Fast
or
Const
time).
Automatic
start mode
(page 115).
21.02
is set to Scalar,
is set to Automatic.
Def/FbEq16
Automatic
0
1
2