ABB ACS580 Firmware Manual page 165

General purpose drives standard control program
Hide thumbs Also See for ACS580:
Table of Contents

Advertisement

No.
Name/Value
10.23
RO forced data
Bit
Value
0
Force the value of this bit to RO1, if so defined in parameter
1
Force the value of this bit to RO2, if so defined in parameter
2
Force the value of this bit to RO3, if so defined in parameter
3...15
Reserved
0000h...FFFFh
10.24
RO1 source
Not energized
Energized
Ready run
Enabled
Started
Magnetized
Running
Ready ref
At setpoint
Reverse
Zero speed
Above limit
Warning
Fault
Fault (-1)
Fault/Warning
Overcurrent
Overvoltage
Drive temp
Undervoltage
Motor temp
Brake command
Ext2 active
Remote control
Reserved
Timed function 1
Timed function 2
Description
Contains the values of relay outputs that are used instead of
the connected signals if selected in parameter
force
selection. Bit 0 is the forced value for RO1.
Forced RO values.
Selects a drive signal to be connected to relay output RO1.
Output is not energized.
Output is energized.
Bit 1 of
06.11 Main status word
Bit 0 of
06.16 Drive status word 1
Bit 5 of
06.16 Drive status word 1
Bit 1 of
06.17 Drive status word 2
Bit 6 of
06.16 Drive status word 1
Bit 2 of
06.11 Main status word
Bit 8 of
06.11 Main status word
Bit 2 of
06.19 Speed control status word
Bit 0 of
06.19 Speed control status word
Bit 10 of
06.17 Drive status word 2
Bit 7 of
06.11 Main status word
Bit 3 of
06.11 Main status word
Inverted bit 3 of
06.11 Main status word
Bit 3 of
06.11 Main status word
word
(see page 154).
Fault
2310 Overcurrent
Fault
3210 DC link overvoltage
Fault
2381 IGBT overload
or
4210 IGBT overtemperature
temperature
or
4310 Excess temperature
temperature difference
has occurred.
Fault
3220 DC link undervoltage
Fault
4981 External temperature 1
temperature 2
has occurred.
Bit 0 of
44.01 Brake control status
Bit 11 of
06.16 Drive status word 1
Bit 9 of
06.11 Main status word
Bit 0 of
34.01 Timed functions status
Bit 1 of
34.01 Timed functions status
10.22 RO
(see page 154).
(see page 155).
(see page 155).
(see page 155).
(see page 155).
(see page 154).
(see page 154).
(see page 156).
(see page 156).
(see page 155).
(see page 154).
(see page 154).
(see page 154).
OR bit 7 of
06.11 Main status
has occurred.
has occurred.
or
4110 Control board temperature
or
4290 Cooling
or
or
4380 Excess
has occurred.
or
4982 External
(see page 292).
(see page 155).
(see page 154).
(see page 255).
(see page 255).
Parameters 161
Def/FbEq16
10.22 RO force
selection.
10.22 RO force
selection.
10.22 RO force
selection.
1 = 1
Ready run
0
1
2
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
42F1 IGBT
20
21
22
23
24
25...26
27
28

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents