104 Program features
for informing the PFC logic that a motor is not available (for example due to
maintenance or manual direct-on-line starting).
Soft pump and fan control (SPFC)
The Soft pump and fan control (SPFC) logic is a variant of the PFC logic for pump
and fan alternation applications where lower pressure peaks are desirable when a
new auxiliary motor is to be started. The SPFC logic is an easy way to implement soft
starting of direct on line (auxiliary) motors.
The main difference between traditional PFC and SPFC logic is how the SPFC logic
connects auxiliary motors on-line. When the criteria for starting a new motor is fulfilled
(see above) the SPFC logic connects the drive controlled motor to the supply network
in a flying start, that is, while the motor is still coasting. The drive then connects to the
next pump/fan unit to be started and starts controlling the speed of that one, while the
previously controlled unit now is connected directly on line through a contactor.
Further (auxiliary) motors are started in a similar manner. The motor stopping routine
is the same as for the normal PFC routine.
In some cases SPFC makes it possible to soften the start-up current while connecting
auxiliary motors on-line. Lower pressure peaks on the pipelines and pumps may be
achieved as a result.
Settings
• Parameter
96.04 Macro select
• Parameter group
• Parameter group
• Parameter groups
and monitoring

Timed functions

See parameter group
Parameter group
34 Timed functions
Motor potentiometer
The motor potentiometer is, in effect, a counter whose value can be adjusted up and
down using two digital signals selected by parameters
source
and
22.74 Motor potentiometer down
When enabled by
22.71 Motor potentiometer
assumes the value set by
mode selected in 22.71, the motor potentiometer value is either retained or reset over
a power cycle.
(macro selection)
10 Standard DI, RO
40 Process PID set 1
76 PFC configuration
(page 323).
34 Timed
functions. Settings
(page 255).
22.72 Motor potentiometer initial
(page 159)
(page 278)
(page 318) and
22.73 Motor potentiometer up
source.
function, the motor potentiometer
value. Depending on the
77 PFC maintenance