Code
Warning / Aux. code
(hex)
A983
External warning 3
(Editable message text)
Programmable warning:
31.05 External event 3
source
31.06 External event 3
type
A984
External warning 4
(Editable message text)
Programmable warning:
31.07 External event 4
source
31.08 External event 4
type
A985
External warning 5
(Editable message text)
Programmable warning:
31.09 External event 5
source
31.10 External event 5
type
A991
Safe motor
temperature
AF88
Season configuration
warning
AF8C
Process PID sleep
mode
AFAA
Autoreset
AFE1
Emergency stop (off2)
AFE2
Emergency stop (off1
or off3)
AFE9
Start delay
AFEB
Run enable missing
AFEC External power signal
missing
Cause
Fault in external device 3.
Fault in external device 4.
Fault in external device 5.
You have configured a season
which starts before the
previous season.
You have configured a season
which starts before the
previous season.
The drive is entering sleep
mode.
A fault is about to be autoreset. Informative warning. See the settings in
Drive has received an
emergency stop (mode
selection off2) command.
Drive has received an
emergency stop (mode
selection off1 or off3)
command.
The start delay is active and
the drive will start the motor
after a predefined delay.
No run enable signal is
received.
95.04 Control board supply
set to
External 24V
but no
voltage is connected to the
control unit.
What to do
Check the external device.
Check setting of parameter
External event 3
source.
Check the external device.
Check setting of parameter
External event 4
source.
Check the external device.
Check setting of parameter
External event 5
source.
Configure the seasons with increasing
start dates, see parameters
Season 1 start date...34.63 Season 4
start
date.
Configure the seasons with increasing
start dates, see parameters
Season 1 start date...34.63 Season 4
start
date.
Informative warning. See section
and boost functions for process PID
control
(page 101), and parameters
40.43...40.48.
parameter group
31 Fault
Check that it is safe to continue
operation. Then return emergency stop
push button to normal position. Restart
drive.
If the emergency stop was unintentional,
check the source selected by parameter
21.05 Emergency stop
Informative warning. See parameter
21.22 Start
delay.
Check setting of parameter
enable 1
source. Switch signal on (e.g. in
the fieldbus Control Word) or check
wiring of selected source.
is
Check the external 24 V DC power
supply to the control unit, or change the
setting of parameter 95.04.
Fault tracing 387
31.05
31.07
31.09
34.60
34.60
Sleep
functions.
source.
20.12 Run