ABB ACS580 Firmware Manual page 397

General purpose drives standard control program
Hide thumbs Also See for ACS580:
Table of Contents

Advertisement

Code
Fault / Aux. code
(hex)
5691
Measurement circuit
ADC
5692
PU board powerfail
5693
Measurement circuit
DFF
5696
PU state feedback
5697
Charging feedback
6181
FPGA version
incompatible
6306
FBA A mapping file
6481
Task overload
6487
Stack overflow
64A1
Internal file load
64B2
User set fault
64E1
Kernel overload
6581
Parameter system
65A1
FBA A parameter
conflict
6681
EFB comm loss
Programmable fault:
Communication loss
action
Cause
Measurement circuit fault.
Power unit power supply
failure.
Measurement circuit fault.
State feedback from output
phases does not match control
signals.
Charging feedback signal
missing.
Firmware and FPGA versions
are incompatible.
Fieldbus adapter A mapping
file read error.
Internal fault.
Internal fault.
File read error.
Loading of user parameter set
failed because
• requested set does not exist
• set is not compatible with
control program
• drive was switched off
during loading.
Operating system error.
Parameter load or save failed.
The drive does not have a
functionality requested by
PLC, or requested functionality
has not been activated.
Communication break in
embedded fieldbus (EFB)
58.14
communication.
Fault tracing 393
What to do
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Check the feedback signal coming from
the charging system
Reboot the control unit (using parameter
96.08 Control board
boot) or by cycling
power. If the problem persists, contact
your local ABB representative
Contact your local ABB representative.
Reboot the control unit (using parameter
96.08 Control board
boot) or by cycling
power. If the problem persists, contact
your local ABB representative
Reboot the control unit (using parameter
96.08 Control board
boot) or by cycling
power. If the problem persists, contact
your local ABB representative
Reboot the control unit (using parameter
96.08 Control board
boot) or by cycling
power. If the problem persists, contact
your local ABB representative
Ensure that a valid user parameter set
exists. Reload if uncertain.
Reboot the control unit (using parameter
96.08 Control board
boot) or by cycling
power. If the problem persists, contact
your local ABB representative
Try forcing a save using parameter
Parameter save
manually. Retry.
Check PLC programming.
Check settings of parameter groups
Fieldbus adapter (FBA)
settings.
Check the status of the fieldbus master
(online/offline/error etc.).
Check cable connections to the
EIA-485/X5 terminals 29, 30 and 31 on
the control unit.
96.07
50
and
51 FBA A