286 Parameters
No.
Name/Value
DI5
DI6
Reserved
Timed function 1
Timed function 2
Timed function 3
Supervision 1
Supervision 2
Supervision 3
Other [bit]
40.43
Set 1 sleep level
0.0...32767.0
40.44
Set 1 sleep delay
0.0...3600.0 s
40.45
Set 1 sleep boost
time
0.0...3600.0 s
40.46
Set 1 sleep boost
step
0.0...32767.0 PID
customer units
40.47
Set 1 wake-up
deviation
-32768.00...
32767.00 PID
customer units
40.48
Set 1 wake-up
delay
0.00...60.00 s
Description
Digital input DI5
(10.02 DI delayed
Digital input DI6
(10.02 DI delayed
Bit 0 of
34.01 Timed functions status
Bit 1 of
34.01 Timed functions status
Bit 2 of
34.01 Timed functions status
Bit 0 of
32.01 Supervision status
Bit 1 of
32.01 Supervision status
Bit 2 of
32.01 Supervision status
Source selection (see
Terms and abbreviations
Defines the start limit for the sleep function. If the value is 0.0,
set 1 sleep mode is disabled.
The sleep function compares PID output (parameter
Process PID output
actual) to the value of this parameter. If
PID output remains below this value longer than the sleep
delay defined by
40.44 Set 1 sleep
sleep mode and stops the motor.
Sleep start level.
Defines a delay before the sleep function actually becomes
enabled, to prevent nuisance sleeping.
The delay timer starts when the sleep mode is enabled by
parameter
40.43 Set 1 sleep
mode is disabled.
Sleep start delay.
Defines a boost time for the sleep boost step. See parameter
40.46 Set 1 sleep boost
Sleep boost time.
When the drive is entering sleep mode, the process setpoint
is increased by this value for the time defined by parameter
40.45 Set 1 sleep boost
If active, sleep boost is aborted when the drive wakes up.
Sleep boost step.
Defines the wake-up level as deviation between process
setpoint and feedback.
When the deviation exceeds the value of this parameter, and
remains there for the duration of the wake-up delay
Set 1 wake-up
delay), the drive wakes up.
See also parameter
40.31 Set 1 deviation
Wake-up level (as deviation between process setpoint and
feedback).
Defines a wake-up delay for the sleep function to prevent
nuisance wake-ups. See parameter
deviation.
The delay timer starts when the deviation exceeds the wake-
up level
(40.47 Set 1 wake-up
deviation falls below the wake-up level.
Wake-up delay.
status, bit 4).
status, bit 5).
(see page 255).
(see page 255).
(see page 255).
(see page 248).
(see page 248).
(see page 248).
on page 144). -
delay, the drive enters the
level, and resets when the sleep
step.
time.
inversion.
40.47 Set 1 wake-up
deviation), and resets if the
Def/FbEq16
6
7
8...17
18
19
20
21
22
23
0.0
40.01
1 = 1
60.0 s
1 = 1 s
0.0 s
1 = 1 s
0.0 PID
customer
units
1 = 1 PID
customer unit
0.00 PID
customer
units
(40.48
1 = 1 PID
customer unit
0.50 s