User Load Curve - ABB ACS580 Firmware Manual

General purpose drives standard control program
Hide thumbs Also See for ACS580:
Table of Contents

Advertisement

No.
Name/Value
36.50
AL2 reset date
-
36.51
AL2 reset time
-
37

37 User load curve

37.01
ULC output status
word
Bit
Name
0
Under load limit
1
Within load range
2
Overload limit
3...15
Reserved
0000h...FFFFh
37.02
ULC supervision
signal
Not selected
Motor speed %
Motor current %
Motor torque %
Output power % of
motor nominal
Output power % of
drive nominal
Other
37.03
ULC overload
actions
Disabled
Warning
Fault
Warning/Fault
37.04
ULC underload
actions
Disabled
Description
The date on which amplitude logger 2 was last reset.
Last reset date of amplitude logger 2.
The time at which amplitude logger 2 was last reset.
Last reset time of amplitude logger 2.
Settings for user load curve.
See also section
Speed compensated stop
Displays the status of the monitored signal.
Description
1 = Signal lower than the underload curve.
1 = Signal between the underload and overload curve.
1 = Signal higher than the overload curve.
Status of the monitored signal.
Selects the signal to be supervised.
No signal selected. ULC disabled.
01.03 Motor speed %
(page 147).
01.08 Motor current % of motor nom
01.10 Motor torque
(page 147).
01.15 Output power % of motor nom
01.16 Output power % of drive nom
Source selection (see
Terms and abbreviations
Selects an action taken if the signal stays over the overload
curve for a defined time.
No warnings or fault generated.
The drive generates an
signal has been continuously over the overload curve for a
time defined by parameter
The drive generates an
has been continuously over the overload curve for a time
defined by parameter
37.41 ULC overload
The drive generates an
signal has been continuously over the overload curve for half
of the time defined by parameter
The drive generates an
has been continuously over the overload curve for a time
defined by parameter
37.41 ULC overload
Selects an action taken if the signal stays under the
underload curve for a defined time.
No warnings or fault generated.
(page 121).
(page 147).
(page 148).
(page 148).
A8C1 ULC overload warning
37.41 ULC overload
8002 ULC overload fault
timer.
A8C1 ULC overload warning
37.41 ULC overload
8002 ULC overload fault
timer.
Parameters 275
Def/FbEq16
01.01.1980
-
00:00:01
-
0000h
1 = 1
Motor
torque %
0
1
2
3
4
5
on page 144). -
Disabled
0
if the
1
timer.
if the signal
2
if the
3
timer.
if the signal
Disabled
0