190 Parameters
No.
Name/Value
In1P Start; In2 Stop;
In3 Dir
In1P Start fwd; In2P
Start rev; In3 Stop
Reserved
Control panel
Fieldbus A
Reserved
Embedded fieldbus
20.07
Ext2 start trigger
type
Edge
Level
20.08
Ext2 in1 source
Description
The sources of the start and stop commands are selected by
parameters
20.08 Ext2 in1 source
The source selected by
direction. The state transitions of the source bits are
interpreted as follows:
State of
State of
source 1
source 2
(20.08)
(20.09)
0 - > 1
1
0 - > 1
1
Any
0
Notes:
• Parameter
20.07 Ext2 start trigger type
this setting.
• When source 2 is 0, the Start and Stop keys on the control
panel are disabled.
The sources of the start and stop commands are selected by
parameters
20.08 Ext2 in1
20.10 Ext2 in3
source. The source selected by
source
determines the direction. The state transitions of the
source bits are interpreted as follows:
State of
State of
source 1
source 2
(20.08)
(20.09)
0 - > 1
Any
0 - > 1
Any
Any
Any
Note: Parameter
20.07 Ext2 start trigger type
with this setting.
The start and stop commands are taken from the control
panel (or PC connected to the panel connector).
The start and stop commands are taken from fieldbus adapter
A.
Note: Set also
20.07 Ext2 start trigger type
The start and stop commands are taken from the embedded
fieldbus interface.
Note: Set also
20.07 Ext2 start trigger type
Defines whether the start signal for external control location
EXT2 is edge-triggered or level-triggered.
Note: This parameter is not effective if a pulse-type start
signal is selected. See the descriptions of the selections of
parameter
20.06 Ext2
commands.
The start signal is edge-triggered.
The start signal is level-triggered.
Selects source 1 for parameter
For the available selections, see parameter
source.
and
20.09 Ext2 in2
20.10 Ext2 in3 source
determines the
State of
source 3
(20.10)
0
Start forward
1
Start reverse
Any
has no effect with
source,
20.09 Ext2 in2 source
20.10 Ext2 in3
State of
source 3
(20.10)
1
Start forward
1
Start reverse
0
has no effect
to Level.
to Level.
20.06 Ext2
commands.
20.03 Ext1 in1
Def/FbEq16
5
source.
Command
Stop
6
and
Command
Stop
7...10
11
12
13
14
Level
0
1
Not selected