154 Parameters
No.
Name/Value
06.11
Main status word
0000h...FFFFh
Description
Main status word of the drive.
For the bit descriptions see page 435. The related control
word and state diagram are presented on pages
respectively.
This parameter is read-only.
Bit
Name
0
Ready to switch ON
1
Ready run
2
Ready ref
3
Tripped
4
Off 2 inactive
5
Off 3 inactive
6
Switch-on inhibited
7
Warning
8
At setpoint
9
Remote
10
Above limit
11
User bit 0
12
User bit 1
13
User bit 2
14
User bit 3
15
Reserved
Main status word.
Def/FbEq16
-
433
and
436
1 = 1