ABB ACS580 Firmware Manual page 415

General purpose drives standard control program
Hide thumbs Also See for ACS580:
Table of Contents

Advertisement

Fieldbus control through the embedded fieldbus interface (EFB) 411
Bit
Name
14
REQ_LOCAL_LO
CK
15
TORQ_LIM_PAIR
_2
16
FB_LOCAL_CTL
17
FB_LOCAL_REF
18
Reserved for
RUN_DISABLE_1
19
Reserved
20
Reserved
21
Reserved
22
USER_0
23
USER_1
24
USER_2
25
USER_3
26...
Reserved
31
Value
State/Description
1
Drive does not switch to local control mode (see
parameter
19.17 Local control
0
Drive can switch between local and remote control
modes.
1
Select torque limit set 2 (Minimum torque 2 / Maximum
torque 2) when parameter
EFB.
0
Select torque limit set 1 (Minimum torque 1 / Maximum
torque 1) when parameter
EFB.
1
Local mode for control from the fieldbus is requested.
Steal control from the active source.
0
(no op)
1
Local mode for reference from the fieldbus is requested.
Steal reference from the active source.
0
(no op)
Not yet implemented.
Writable control bits that can be combined with drive logic
for application-specific functionality.
disable).
30.18 Torq lim sel
is set to
30.18 Torq lim sel
is set to