384 Fault tracing
Code
Warning / Aux. code
(hex)
A6E5
AI parametrization
A780
Motor stall
Programmable warning:
31.24 Stall function
A793
BR excess
temperature
A794
BR data
0000 0001 Resistance value too low.
0000 0002 Thermal time constant not
0000 0003 Maximum continuous power
A79C
BC IGBT excess
temperature
A7AB
Extension I/O
configuration failure
Cause
The current/voltage hardware
setting of an analog input does
not correspond to parameter
settings.
Motor is operating in stall
region because of e.g.
excessive load or insufficient
motor power.
Brake resistor temperature has
exceeded warning limit defined
by parameter
43.12 Brake
resistor warning
limit.
Brake resistor data has not
been given.
given.
not given.
Brake chopper IGBT
temperature has exceeded
internal warning limit.
Installed CMOD module is not
the same as configured.
What to do
Check the event log for an auxiliary code.
The code identifies the analog input
whose settings are in conflict.
Adjust either the hardware setting (on the
drive control unit) or parameter
12.15/12.25.
Note: Control board reboot (either by
cycling the power or through parameter
96.08 Control board
boot) is required to
validate any changes in the hardware
settings.
Check motor load and drive ratings.
Check fault function parameters.
Stop drive. Let resistor cool down.
Check resistor overload protection
function settings (parameter group
Brake
chopper).
Check warning limit setting, parameter
43.12 Brake resistor warning
Check that the resistor has been
dimensioned correctly.
Check that braking cycle meets allowed
limits.
One or more of the resistor data settings
(parameters 43.08...43.10) is incorrect.
The parameter is specified by the
auxiliary code.
Check value of 43.10.
Check value of 43.08.
Check value of 43.09.
Let chopper cool down.
Check for excessive ambient
temperature.
Check for cooling fan failure.
Check for obstructions in the air flow.
Check the dimensioning and cooling of
the cabinet.
Check resistor overload protection
function settings (parameters
43.06...43.10).
Check minimum allowed resistor value
for the chopper being used.
Check that braking cycle meets allowed
limits.
Check that drive supply AC voltage is not
excessive.
Check that the installed module (shown
by parameter
15.02 Detected extension
module) is the same as selected by
parameter
15.01 Extension module
43
limit.
type.