No.
Name/Value
20.09
Ext2 in2 source
20.10
Ext2 in3 source
20.11
Run enable stop
mode
Coast
Ramp
Torque limit
20.12
Run enable 1
source
Not selected
Selected
DI1
DI2
DI3
DI4
DI5
DI6
Reserved
Timed function 1
Timed function 2
Timed function 3
Reserved
Supervision 1
Supervision 2
Supervision 3
Reserved
FBA A MCW bit 3
EFB MCW bit 3
Other [bit]
Description
Selects source 2 for parameter
For the available selections, see parameter
source.
Selects source 3 for parameter
For the available selections, see parameter
source.
Selects the way the motor is stopped when the run enable
signal switches off.
The source of the run enable signal is selected by parameter
20.12 Run enable 1
source.
Stop by switching off the output semiconductors of the drive.
The motor coasts to a stop.
WARNING! If a mechanical brake is used, ensure it is
safe to stop the drive by coasting.
Stop along the active deceleration ramp. See parameter
group
23 Speed reference ramp
Stop according to torque limits (parameters
Selects the source of the external run enable signal. If the run
enable signal is switched off, the drive will not start. If already
running, the drive will stop according to the setting of
parameter
20.11 Run enable stop
1 = Run enable signal on.
Note: This parameter cannot be changed while the drive is
running.
See also parameter
20.19 Enable start
0.
1.
Digital input DI1
(10.02 DI delayed
Digital input DI2
(10.02 DI delayed
Digital input DI3
(10.02 DI delayed
Digital input DI4
(10.02 DI delayed
Digital input DI5
(10.02 DI delayed
Digital input DI6
(10.02 DI delayed
Bit 0 of
34.01 Timed functions status
Bit 1 of
34.01 Timed functions status
Bit 2 of
34.01 Timed functions status
Bit 0 of
32.01 Supervision status
Bit 1 of
32.01 Supervision status
Bit 2 of
32.01 Supervision status
Control word bit 3 received through fieldbus interface A.
Control word bit 3 received through the embedded fieldbus
interface.
Source selection (see
Terms and abbreviations
20.06 Ext2
commands.
20.03 Ext1 in1
20.06 Ext2
commands.
20.03 Ext1 in1
on page 212.
30.19
and 30.20). 2
mode.
command.
status, bit 0).
status, bit 1).
status, bit 2).
status, bit 3).
status, bit 4).
status, bit 5).
(see page 255).
(see page 255).
(see page 255).
(see page 248).
(see page 248).
(see page 248).
on page 144). -
Parameters 191
Def/FbEq16
Not selected
Not selected
Coast
0
1
Selected
0
1
2
3
4
5
6
7
8...17
18
19
20
21...23
24
25
26
27...29
30
31

Hide quick links: