Torque control performance figures

The drive can perform precise torque control without any speed feedback from the
motor shaft. The table below shows typical performance figures for torque control.
Torque control
Non-linearity
Torque step rise time < 10 ms with nominal
Power loss ride-through
See section
Undervoltage control (power loss ride-through)
U/f ratio
The U/f function is only available in scalar motor control mode, which uses frequency
control.
The function has two modes: linear and squared.
In linear mode, the ratio of voltage to frequency is constant below the field weakening
point. This is used in constant torque applications where it may be necessary to
produce torque at or near the rated torque of the motor throughout the frequency
range
In squared mode (default), the ratio of the voltage to frequency increases as the
square of the frequency below the field weakening point. This is typically used in
centrifugal pump or fan applications. For these applications, the torque required
follows the square relationship with frequency. Therefore, if the voltage is varied
using the square relationship, the motor operates at improved efficiency and lower
noise levels in these applications.
The U/f function cannot be used with energy optimization; if parameter
optimizer
is set to Enable, parameter
Performance
± 5% with nominal
torque
(± 20% at the most
demanding operating
point)
torque
97.20 U/F ratio
Program features 113
T
(%)
T
T
N
ref
100
T
90
10
< 5 ms
T
= rated motor torque
N
T
= torque reference
ref
T
= actual torque
act
on page 122.
is ignored.
act
t (s)
45.11 Energy