ABB ACS580 Firmware Manual page 258

General purpose drives standard control program
Hide thumbs Also See for ACS580:
Table of Contents

Advertisement

254 Parameters
No.
Name/Value
32.50
Supervision 5 high
-21474836.00...
21474836.00
32.51
Supervision 5
hysteresis
0.00...100000.00
32.55
Supervision 6
function
Disabled
Low
High
Abs low
Abs high
Both
Abs both
32.56
Supervision 6
action
No action
Warning
Fault
Fault if running
32.57
Supervision 6
signal
32.58
Supervision 6 filter
time
0.000 ... 30.000 s
32.59
Supervision 6 low
-21474836.00...
21474836.00
32.60
Supervision 6 high
-21474836.00...
21474836.00
Description
Defines the upper limit for signal supervision 5.
Upper limit.
Defines the hysteresis for the signal monitored by signal
supervision 5.
Hysteresis.
Selects the mode of signal supervision function 6. Determines
how the monitored signal (see parameter 32.57) is compared
to its lower and upper limits
The action to be taken when the condition is fulfilled is
selected by 32.56.
Signal supervision 6 not in use.
Action is taken whenever the signal falls below its lower limit.
Action is taken whenever the signal rises above its upper
limit.
Action is taken whenever the absolute value of the signal falls
below its (absolute) lower limit.
Action is taken whenever the absolute value of the signal
rises above its (absolute) upper limit.
Action is taken whenever the signal falls below its low limit or
rises above its high limit.
Action is taken whenever the absolute value of the signal falls
below its (absolute) low limit or rises above its (absolute) high
limit.
Selects whether the drive generates a fault, warning or
neither when the value monitored by signal supervision 6
exceeds its limits.
Note: This parameter does not affect the status indicated by
32.01 Supervision
status.
No warning or fault generated.
Warning
A8B5 Signal supervision 6
Drive trips on fault
80B5 Signal supervision
Drive trips on fault
80B0 Signal supervision 1
running.
Selects the signal to be monitored by signal supervision
function 6.
For the available selections, see parameter
Supervision 1
signal.
Defines a filter time constant for the signal monitored by
signal supervision 6.
Signal filter time.
Defines the lower limit for signal supervision 6.
Low limit.
Defines the upper limit for signal supervision 6.
Upper limit.
(32.59
and
32.50
respectively).
is generated.
6.
if the motor is
32.07
Def/FbEq16
0.00
-
0.00
-
Disabled
0
1
2
3
4
5
6
No action
0
1
2
3
Zero
0.000 s
1000 = 1 s
0.00
-
0.00
-