Standard Dio, Fi, Fo - ABB ACQ80-04 Firmware Manual

Drives for water, standard control program
Table of Contents

Advertisement

82 Parameters
No.
Name/Value
10.30
RO3 source
10.31
RO3 ON delay
Status of selected
source
RO status
t
=
10.31 RO3 ON delay
On
t
=
10.32 RO3 OFF delay
Off
0.0 ... 3000.0 s
10.32
RO3 OFF delay
0.0 ... 3000.0 s
10.99
RO/DIO control
word
Bit
Name
0
RO1
1
RO2
2
RO3
3...15
Reserved
0b0000...0b1111
10.101 RO1 toggle counter
0...4294967000
10.102 RO2 toggle counter
0...4294967000
10.103 RO3 toggle counter
0...4294967000
11

11 Standard DIO, FI, FO

11.21
DI5 configuration
Digital input
Description
Selects a drive signal to be connected to relay output RO3.
For the available selections, see parameter
source.
Defines the activation delay for relay output RO3.
t
t
On
Off
Activation delay for RO3.
Defines the deactivation delay for relay output RO3. See
parameter
10.31 RO3 ON
Deactivation delay for RO3.
Storage parameter for controlling the relay outputs eg.
through the embedded fieldbus interface. To control the relay
outputs (RO) of the drive, send a control word with the bit
assignments shown below as Modbus I/O data. Set the target
selection parameter of that particular data (58.101...58.114)
to
RO/DIO control
word. In the source selection parameter of
the desired output, select the appropriate bit of this word.
Description
Source bits for relay outputs RO1...RO3. See parameters 10.24,
10.27
and 10.30.
RO/DIO control word.
Shows number of times relay output RO1 has changed
states.
State change count.
Shows number of times relay output RO2 has changed
states.
State change count.
Shows number of times relay output RO3 has changed
states.
State change count.
Configuration of the frequency input.
(Only visible with firmware ASCL2 and ASCL4)
Selects how digital input 6 is used.
DI6 is used as a digital input.
10.24 RO1
t
On
delay.
Def/FbEq16
Fault (-1)
0.0 s
1
0
1
0
Time
t
Off
10 = 1 s
0.0 s
10 = 1 s
0b0000
1 = 1
0
1 = 1
0
1 = 1
0
1 = 1
Digital input
0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents