ABB ACQ80-04 Firmware Manual page 75

Drives for water, standard control program
Table of Contents

Advertisement

No.
Name/Value
06.11
Main status word
0x0000...0xffff
06.16
Drive status word 1
Bit
Name
0
Enabled
1
Inhibited
2
DC charged
3
Ready to start
4
Following
reference
5
Started
6
Modulating
7
Limiting
8
Local control
9
Network control
10
Ext1 active
11
Ext2 active
12
Reserved
13
Start request
14
Running
15
Reserved
0b0000...0b1111
Description
Main status word of the drive.
For the bit descriptions see page 255. The related control
word and state diagram are presented on pages
respectively.
This parameter is read-only.
Bit
Name
0
Ready to switch ON
1
Ready run
2
Ready ref
3
Tripped
4
Off 2 inactive
5
Off 3 inactive
6
Switch-on inhibited
7
Warning
8
At setpoint
9
Remote
10
Above limit
11
User bit 0
12
User bit 1
13
User bit 2
14
User bit 3
15
Reserved
Main status word.
Drive status word 1.
This parameter is read-only.
Description
Not applicable.
1 = Start inhibited. To start the drive, the inhibiting signal (see par.
06.18) must be removed and the start signal cycled.
1 = DC circuit has been charged
1 = Drive is ready to receive a start command
1 = Drive is ready to follow given reference
1 = Drive has been started
1 = Drive is modulating (output stage is being controlled)
1 = Any operating limit (speed, torque, etc.) is active
1 = Drive is in local control
1 = Drive is in
network control
1 = Control location EXT1 active
1 = Control location EXT2 active
1 = Start requested. 0 = When Enable to rotate signal is 0 (rotating of
the motor is disabled).
1 = Drive is controlling speed or frequency, in PID sleep or pre-
magnetization.
Drive status word 1.
Parameters 75
253
and
256
(see page 14).
Def/FbEq16
0x0000
1 = 1
0b0000
1 = 1

Hide quick links: