ABB ACQ80-04 Firmware Manual page 131

Drives for water, standard control program
Hide thumbs Also See for ACQ80-04:
Table of Contents

Advertisement

No.
Name/Value
40.07
Process PID
operation mode
Off
On
On when drive
running
40.08
Set 1 feedback 1
source
Not selected
AI1 scaled
AI2 scaled
Freq in scaled
AI1 percent
AI2 percent
Feedback data
storage
Actual flow
Other
40.11
Set 1 feedback filter
time
0.000...30.000 s
40.14
Set 1 setpoint
scaling
-200000.00...
200000.00
40.15
Set 1 output scaling
-200000.00...
200000.00
40.16
Set 1 setpoint 1
source
Not selected
Internal setpoint
AI1 scaled
AI2 scaled
Description
Activates/deactivates process PID control.
Note: Process PID control is only available in external
control; see section
Local control vs. external control
29).
Process PID control inactive.
Process PID control active.
Process PID control is active when the drive is running.
Selects the primary source of process feedback.
None.
12.12 AI1 scaled value
(see page 85).
12.22 AI2 scaled value
(see page 86).
11.39 Freq in 1 scaled value
12.101 AI1 percent value
12.102 AI2 percent value
40.91 Feedback data storage
80.01 Calculated flow
(see page 159),
Source selection (see
Terms and abbreviations
Defines the filter time constant for process feedback.
Feedback filter time.
Defines, together with parameter
scaling, a general scaling factor for the external PID
control chain. The scaling can be utilized when, for
example, the process setpoint is input in Hz, and the
output of the PID controller is used as an rpm value in
speed control. In this case, this parameter might be set to
50, and parameter
40.15
Hz.
In effect, the output of the PID controller [40.15] when
deviation (setpoint - feedback) = [40.14] and [40.32] = 1.
Note: The scaling is based on the ratio between
and 40.15. For example, the values 50 and 1500 would
produce the same scaling as 1 and 3.
Process setpoint base.
See parameter
40.14 Set 1 setpoint scaling
Process PID controller output base.
Selects the primary source of process PID setpoint.
None.
Internal setpoint. See parameter
0.
12.12 AI1 scaled value
(see page 85).
12.22 AI2 scaled value
(see page 86).
(see page 83).
(see page 88)
(see page 88)
(see page 139),
on page 64).
40.15
Set 1 output
to the nominal motor speed at 50
40.14
40.24 Set 1 internal setpoint
Parameters 131
Def/FbEq16
Off
(page
0
1
2
AI2 percent
0
1
2
3
8
9
10
11
-
0.000 s
1 = 1 s
100.00
1=1
100.00
1=1
AI1 percent
0
2
3
4