214 Fault tracing
Fault / Aux. code
Code
code visible only on
(hex)
assistant control panel
and drive composer)
64B1
Internal SSW fault
1 – Starting OS time tick failed
2 – Creating system tasks failed
3 – Initializing file system failed
4 – Checking file system failed
64B2
User set fault
64B3
Macro
parameterization error
64E1
Kernel overload
6581
Parameter system
6591
Backup/Restore
timeout
65A1
FBA A parameter
conflict
6681
EFB comm loss
Programmable fault:
Communication loss
action
6682
EFB config file
6683
EFB invalid
parameterization
(aux
Cause
A fatal error in the power-up
phase of System Software
(SSW).
Loading of user parameter set
failed because
• requested set does not exist
• set is not compatible with
control program
• drive was switched off
during loading.
Macro parameterization failed,
eg. Parameter default
value that cannot be changed
has been attempted to write.
Operating system error.
Parameter load or save failed.
During backup creating or
restoring operation a panel or
PC-tool has failed to
communicate with the drive as
part of this operation.
The drive does not have a
functionality requested by
PLC, or requested functionality
has not been activated.
Communication break in
embedded fieldbus (EFB)
58.14
communication.
Embedded fieldbus (EFB)
configuration file could not be
read.
Embedded fieldbus (EFB)
parameter settings
inconsistent or not compatible
with selected protocol.
What to do
SSW runs in partial functionality mode.
5 – Initializing WoRm volumes failed
6 – Loading FPGA configuration failed
7 – Loading application program failed
Ensure that a valid user parameter set
exists. Reload if uncertain.
Reboot the control unit (using parameter
96.08 Control board
power. If the problem persists, contact
your local ABB representative
Try forcing a save using parameter
Parameter save
Check panel or PC-tool communication
and if it is still in backup or restore state.
Check PLC programming.
Check settings of parameter groups
Fieldbus adapter (FBA)
settings.
Check the status of the fieldbus master
(online/offline/error etc.).
Check cable connections to the
EIA-485/X5 terminals 29, 30 and 31 on
the control unit.
Contact your local ABB representative.
Check the settings in parameter group
Embedded
fieldbus.
boot) or by cycling
96.07
manually. Retry.
50
and
51 FBA A
58