Refer to the motor nameplate for the following nominal value settings of the motor. Enter the
values exactly as shown on the motor nameplate.
Example of a nameplate of an induction (asynchronous) motor:
ABB Motors
3
motor
M2AA 200 MLA 4
IEC 200 M/L 55
Hz
kW
V
690 Y
50
30
400 D
50
30
660 Y
50
30
380 D
30
50
415 D
50
30
440 D
35
60
Cat. no
3GAA 202 001 - ADA
6312/C3
Navigate to Main menu
Set the motor nominal current:
• Use
and
• Use
and
Press
(OK). to accept the new setting, or press
(Back) to go back to the previous view without making
changes.
Set the torque and motor Cos Φ, if needed. Motor
nominal cos Φ and nominal torque are optional.:
• Use
and
• Use
and
Press
(OK) to accept the new setting, or press
(Back) to go back to the previous view without making
changes.
Set the desired motor control mode. if Vector motor
control is selected, make sure that ID run is performed.
See
ID run
procedure.
Navigate to Options menu
direction.
No
Ins.cl. F
IP 55
IA/IN t E/s
r/min
A
cos
1475
32.5
0.83
56
1475
0.83
1470
34
0.83
1470
59
0.83
1475
54
0.83
1770
59
0.83
6210/C3
180
IEC 34-1
and select Motor data
to move the cursor left and right.
to change the value.
to move the cursor left and right.
to change the value.
and set the
.
Scalar
3A
96.06
3.0
A
0.000Nm
Cos Φ
0.00
0.000Nm
Cos Φ
0.00
Scalar
4.7A
Loc
I
13.04
Hz
2.20kW
400.0V
U V W
U V W
2.20kW
400.0V
10.13.04Hz