ABB ACQ80-04 Firmware Manual page 219

Drives for water, standard control program
Table of Contents

Advertisement

Fault / Aux. code
Code
code visible only on
(hex)
assistant control panel
and drive composer)
000E...0010 Internal error.
FF63
STO diagnostics
failure.
FF81
FB A force trip
FF8E
EFB force trip
(aux
Cause
000A (Asynchronous motors only)
Deceleration did not finish
within reasonable time.
000B (Asynchronous motors only)
Speed dropped to zero during
ID run.
000C (Permanent magnet motors
only)
First acceleration did not finish
within reasonable time.
000D (Permanent magnet motors
only)
Second acceleration did not
finish within reasonable time.
0011 (Synchronous reluctance
motors only)
Pulse test error.
0012 Motor too large for advanced
standstill ID run.
0013 (Asynchronous motors only)
Motor data error.
SW internal malfunction.
A fault trip command has been
received through fieldbus
adapter A.
A fault trip command has been
received through the
embedded fieldbus interface.
Fault tracing 219
What to do
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Check that the motor and drive sizes are
compatible.
Contact your local ABB representative.
Check that the motor nominal value
settings in the drive are the same as in
the motor nameplate.
Contact your local ABB representative.
Reboot the control unit (using parameter
96.08 Control board boot
power.
Check the fault information provided by
the PLC.
Check the fault information provided by
the PLC.
or by cycling