Load Analyzer - ABB ACQ80-04 Firmware Manual

Drives for water, standard control program
Hide thumbs Also See for ACQ80-04:
Table of Contents

Advertisement

No.
Name/Value
36

36 Load analyzer

36.01
PVL signal source
Not selected
Motor speed used
Output frequency
Motor current
Motor torque
DC voltage
Output power
Speed ref ramp in
Speed ref ramp out
Speed ref used
Torque ref used
Freq ref used
Process PID out
Other
36.02
PVL filter time
0.00...120.00 s
36.06
AL2 signal source
36.07
AL2 signal scaling
0.00...32767.00
36.09
Reset loggers
Done
All
PVL
Description
Peak value and amplitude logger settings.
See also section
Load analyzer
Selects the signal to be monitored by the peak value logger.
The signal is filtered using the filtering time specified by
parameter
36.02 PVL filter
The peak value is stored, along with other pre-selected
signals at the time, into parameters
The peak value logger can be reset using parameter
Reset
loggers. The date and time of the last reset are stored
into parameters
36.16
and
None (peak value logger disabled).
01.01 Motor speed
used.
01.06 Output
frequency.
01.07 Motor
current.
01.10 Motor
torque.
01.11 DC
voltage.
01.14 Output
power.
23.01 Speed ref ramp
input.
23.02 Speed ref ramp
output.
24.01 Used speed
reference.
Not applicable
28.02 Frequency ref ramp
40.01 Process PID output
Source selection (see
Terms and
Peak value logger filtering time. See parameter
signal
source.
Peak value logger filtering time.
Selects the signal to be monitored by amplitude logger 2. The
signal is sampled at 200 ms intervals.
The results are displayed by parameters
Each parameter represents an amplitude range, and shows
what portion of the samples fall within that range.
The signal value corresponding to 100% is defined by
parameter
36.07 AL2 signal
Amplitude logger 2 can be reset using parameter
loggers. The date and time of the last reset are stored into
parameters
36.50
and
36.51
For the selections, see parameter
See parameter
36.01
for the selections.
Defines the monitored signal value for the amplitude logger
AL2 that corresponds to 100% sample value.
Signal value corresponding to 100%.
Resets the peak value logger and/or amplitude logger 2.
(Amplitude logger 1 cannot be reset.)
Reset completed or not requested (normal operation).
Reset both the peak value logger and amplitude logger 2.
Reset the peak value logger.
(page 49).
time.
36.10
... 36.15.
36.17
respectively.
output.
actual.
abbreviations).
36.01 PVL
36.40
... 36.49.
scaling.
36.09 Reset
respectively.
36.01 PVL signal
Parameters 127
Def/FbEq16
Output power
36.09
0
1
3
4
6
7
8
10
11
12
14
16
-
2.00 s
100 = 1 s
Motor torque
source.
100.00
1 = 1
Done
0
1
2