62 Parameters
No.
Name/Value
110.99
RO/DIO control word
Bit
Name
0
RO1
1
RO2
2
RO3
3...7
Reserved
8
DIO1
9
DIO2
10...15 Reserved
0000h...FFFFh
111

111 Standard DIO, FI, FO

111.01
DIO status
0000h...FFFFh
111.02
DIO delayed status
0000h...FFFFh
111.05
DIO1 configuration
Output
Input
Freq
111.06
DIO1 out source
Not energized
Energized
Ready
Started
Running
Warning
Fault
-
Charging
Description
Storage parameter for controlling the relay outputs and
digital input/outputs.
To control the relay outputs (RO) and the digital
input/outputs (DIO), send a control word with the bit
assignments shown below as Modbus I/O data. Set the
target selection parameter of that particular data. In the
source selection parameter of the desired output, select the
appropriate bit of this word.
Description
Source bits for relay outputs RO1...RO3 (see parameters 110.24,
and 110.30).
Source bits for digital input/outputs DIO1...DIO3 (see parameters
and 111.06).
RO/DIO control word.
Configuration of digital input/outputs and frequency
inputs/outputs.
Status of digital input/outputs DIO8...DIO1.
Example: 0000001001 = DIO1 and DIO4 are on, the
remainder are off.
Status of digital input/outputs.
Status of digital input/outputs DIO8...DIO1 after
activation/deactivation delays.
Bit 0 reflects the delayed status of DIO1.
Delayed status of digital input/outputs.
Selects whether DIO1 is used as a digital output or input.
Note: This parameter is not effective if DIO1 has been
selected as a frequency input by parameter
HW
sel.
DIO1 is used as a digital output.
DIO1 is used as a digital input.
DIO1 is used as a frequency input or frequency output. See
also parameter
111.41 Freq in 1 HW
Selects a signal to be connected to digital input/output DIO1
when parameter
111.05 DIO1 configuration
Output is not energized.
Output is energized.
Bit 0 of
106.11 Main status word
energized when the DC/DC converter unit is ready.
Bit 4 of
106.16 Status word 1
energized when the DC/DC converter unit is started.
Bit 1 of
106.11 Main status word
energized when the DC/DC converter unit is running.
Bit 7 of
106.11 Main status word
energized when a warning is active.
Bit 3 of
106.11 Main status word
energized when a fault is active.
Reserved.
Bit 14 of
106.16 Status word 1
111.41 Freq in 1
sel.
is set to Output.
(see page 53). Output is
(see page 53). Output is
(see page 53). Output is
(see page 53). Output is
(see page 53). Output is
(see page 53).
Def/FbEq16
0000h
110.27
111.06
1 = 1
-
1 = 1
-
1 = 1
Output
0
1
2
Not energized
0
1
2
3
4
5
6
7
8