ABB ACQ80-04 Firmware Manual page 68

Drives for water, standard control program
Hide thumbs Also See for ACQ80-04:
Table of Contents

Advertisement

68 Parameters
No.
Name/Value
01.14
Output power
-32768.00...
32767.00 kW
01.15
Output power % of
motor nom
-300.00... 300.00%
01.16
Output power % of
drive nom
-300.00... 300.00%
01.17
Motor shaft power
-32768.00...
32767.00 kW or hp
01.18
Inverter GWh
counter
0...65535 GWh
01.19
Inverter MWh
counter
0...1000 MWh
01.20
Inverter kWh
counter
0...1000 kWh
01.24
Flux actual %
0...200%
01.30
Nominal torque
scale
0.000...4000000
N·m or lb·ft
01.50
Current hour kWh
0.00... 1000000.00
kWh
Description
Shows drive output power. A filter time constant for this
signal can be defined by parameter
Output power.
Shows output power in percent of the nominal motor power.
Output power.
Shows output power in percent of the nominal drive power.
Output power.
Shows estimated mechanical power at motor shaft. The unit
is selected by parameter
Motor shaft power.
Shows amount of energy that has passed through the drive
(in either direction) in full gigawatt-hours. The minimum value
is zero.
Energy in GWh.
Shows amount of energy that has passed through the drive
(in either direction) in full megawatt-hours. Whenever the
counter rolls over,
01.18 Inverter GWh counter
incremented. The minimum value is zero.
Energy in MWh.
Shows amount of energy that has passed through the drive
(in either direction) in full kilowatt-hours. Whenever the
counter rolls over,
01.19 Inverter MWh counter
incremented. The minimum value is zero.
Energy in kWh.
Shows used flux reference in percent of nominal flux of motor. -
Flux reference.
Shows torque that corresponds to 100% of nominal motor
torque. The unit is selected by parameter
selection.
Note: This value is copied from parameter
nominal torque
if entered. Otherwise the value is calculated
from other motor data.
Nominal torque.
Shows current hour energy consumption. This is the energy
of the last 60 minutes (not necessarily continuous) the drive
has been running, not the energy of a calendar hour.
The value is set to the value before the power cycle when the
drive is again up and running.
Energy.
46.14 Filter time
96.16 Unit
selection.
is
is
96.16 Unit
99.12 Motor
Def/FbEq16
-
power.
1 = 1 unit
-
1 = 1%
-
1 = 1%
-
1 = 1 unit
-
1 = 1 GWh
-
1 = 1 MWh
-
10 = 1 kWh
1 = 1%
-
1 = 100 unit
-
1 = 1 kWh