224 Fieldbus control through the embedded fieldbus interface (EFB)
Parameter
58.33
Addressing
mode
58.34
Word order
58.101
Data I/O 1
...
...
58.114
Data I/O 14
58.06
Communication
control
The new settings will take effect when the drive is powered up the next time, or when
they are validated by parameter

Setting the drive control parameters

After the embedded fieldbus interface has been set up, check and adjust the drive
control parameters listed in the table below. The Setting for fieldbus control column
gives the value or values to use when the embedded fieldbus signal is the desired
source or destination for that particular drive control signal. The
Function/Information column gives a description of the parameter.
Parameter
CONTROL COMMAND SOURCE SELECTION
79.10 Operating
mode
OTHER SELECTIONS
EFB references can be selected as the source at virtually any signal selector parameter by
selecting Other, then either
Setting for
fieldbus control
Mode 0
(default)
[0]
LO-HI
(default) [1]
For example, the
default settings
(I/Os 1...6 contain
the control word,
the status word,
two references and
two actual values)
RO/DIO control
word
[31],
AO1
data storage
[32],
AO2 data storage
[33],
Feedback
data storage
[40],
Setpoint data
storage
[41]
Refresh settings
58.06 Communication control (Refresh
Setting for
fieldbus control
Embedded fieldbus
03.09 EFB reference 1
Function/Information
Defines the mapping between parameters
and holding registers in the 400001...465536
(100...65535) Modbus register range.
Defines the order of the data words in the
Modbus message frame.
Defines the address of the drive parameter
which the Modbus master accesses when it
reads from or writes to the register address
corresponding to Modbus In/Out parameters.
Select the parameters that you want to read
or write through the Modbus I/O words.
These settings write the incoming data into
storage parameters
10.99 RO/DIO control
word,
13.91 AO1 data
data
storage,
40.91 Feedback data storage
40.92 Setpoint data
storage.
Validates the settings of the configuration
parameters.
Function/Information
Selects fieldbus as the source for the start
and stop commands.
or
03.10 EFB reference
storage,
13.92 AO2
settings).
2.
or