Pump Cleaning - ABB ACQ80-04 Firmware Manual

Drives for water, standard control program
Hide thumbs Also See for ACQ80-04:
Table of Contents

Advertisement

No.
Name/Value
DI2
DI3
DI4
DI5
DI6
Min load current
Other [bit]
82.46
Dry run current limit
0.00...3000.00
82.47
Dry run trip monitor
time
1.0...300.0
82.48
Dry run reset time
1.0...18000.0
83

83 Pump cleaning

83.01
Pump cleaning
status
Disabled
Clean pump
No triggers
configured
Waiting for
triggering
83.02
Pump cleaning
progress
0.0...100.0%
83.03
Total cleaning count
0...1000000
83.12
Start pump cleaning
Not active
Start cleaning now
DI4
DI5
DI6
Description
Digital input DI2
(10.02 DI delayed
Digital input DI3
(10.02 DI delayed
Digital input DI4
(10.02 DI delayed
Digital input DI5
(10.02 DI delayed
Digital input DI6
(10.02 DI delayed
Enables the dry run protection when the actual load is below
the dry run current limit.
Source selection (see
Terms and abbreviations
Defines the dry run current limit. When the actual current
goes below the dry run current limit for a defined time (82.47),
the drive considers it as a dry run condition and trips on the
fault,
D4B0 Running
dry.
Current limit.
Defines the time to monitor dry run current limit. After the
defined time elapses, the drive considers it as dry run
condition and trips on the fault,
Run trip monitor time.
Defines the rest time to reset the dry run fault (D4B0). The
drive starts automatically if it receives a start command.
Dry run reset time.
Settings for the pump cleaning sequence.
See section
Pump cleaning
Displays the status of pump cleaning.
Pump cleaning is disabled.
Pump cleaning is active.
Pump cleaning is not active.
Waiting for triggering signal.
Displays the pump cleaning progress.
Percentage
Displays the cleaning count. Cleaning count increments by
one, when the sequence of cleaning cycles are completed.
For example, if
83.16 Cycles in cleaning program
the pump cleaning completes after three cycles of reverse
and forward motions of the pump and the cleaning count
changes to 1.
Total cleaning count.
Enables/disables the pump cleaning.
Pump cleaning is not active.
Starts pump cleaning immediately.
Starts pump cleaning when DI4 goes high.
Starts pump cleaning when DI5 goes high.
Starts pump cleaning when DI6 goes high.
status, bit 1).
status, bit 2).
status, bit 3).
status, bit 4).
status, bit 5).
on page 64).
D4B0 Running
dry.
(page 36).
is set as 3,
Parameters 161
Def/FbEq16
3
4
5
6
7
8
-
0.00
100 = 1
120.0
10 = 1
120.0
10 = 1
Disabled
0
1
2
3
0
10 = 1
0
1 = 1
Not active
0
1
2
3
4