Panel Port Communication - ABB ACQ80-04 Firmware Manual

Drives for water, standard control program
Hide thumbs Also See for ACQ80-04:
Table of Contents

Advertisement

142 Parameters
No.
Name/Value
46.22
At frequency
hysteresis
0.00...1000.00 Hz
46.31
Above speed limit
0.00...30000.00
rpm
46.32
Above frequency
limit
0.00...1000.00 Hz
46.41
kWh pulse scaling
0.001...
1000.000 kWh
46.43
Power decimals
0...3
46.44
Current decimals
0...3
49
49 Panel port
communication
49.01
Node ID number
1...32
49.03
Baud rate
38.4 kbps
57.6 kbps
86.4 kbps
Description
Defines the "at setpoint" limits for frequency control of the
drive. When the absolute difference between frequency
reference and actual frequency
smaller than
46.22 At frequency
considered to be "at setpoint". This is indicated by bit 8 of
06.11 Main status
word.
Drive at setpoint
(06.11
bit 8 = 1)
Limit for "at setpoint" indication in frequency control.
Defines the trigger level for "above limit" indication in speed
control. When actual speed exceeds the limit, bit 10 of
Drive status word 2
is set.
"Above limit" indication trigger level for speed control.
Defines the trigger level for "above limit" indication in
frequency control. When actual frequency exceeds the limit,
bit 10 of
06.17 Drive status word 2
"Above limit" indication trigger level for frequency control.
Defines the trigger level for the "kWh pulse" on for 50 ms. The
output of the pulse is bit 9 of
"kWh pulse" on trigger level.
Defines the number of decimal places of power-related
parameters.
Number of decimal places of power parameters.
Defines the number of decimal places of current-related
parameters.
Number of decimal places of current parameters.
Communication settings for the control panel port on the
drive.
Defines the node ID of the drive. All devices connected to the
network must have a unique node ID.
Note: For networked drives, it is advisable to reserve ID 1 for
spare/replacement drives.
Node ID.
Defines the transfer rate of the link.
38.4 kbit/s.
57.6 kbit/s.
86.4 kbit/s.
(01.06 Output
frequency) is
hysteresis, the drive is
01.06
(Hz)
Frequency reference +
Frequency reference (Hz)
Frequency reference -
0 Hz
is set.
05.22 Diagnostic word
3.
Def/FbEq16
2.00 Hz
46.22
46.22
10 = 1
1500.00 rpm
06.17
1 = 1
50.00 Hz
10 = 1
1.000 kWh
1 = 1 kWh
2
1 = 1
1
1 = 1
1
1 = 1
115.2 kbps
1
2
3

Hide quick links: