ABB ACQ80-04 Firmware Manual page 89

Drives for water, standard control program
Hide thumbs Also See for ACQ80-04:
Table of Contents

Advertisement

No.
Name/Value
Abs output
frequency
Abs motor torque
Abs output power
Abs motor shaft
power
AO1 data storage
AO2 data storage
Other
13.13
AO1 forced value
0.000...22.000 mA /
0.000...11.000 V
13.15
AO1 unit selection
V
mA
13.16
AO1 filter time
0.000 ... 30.000 s
Description
01.63 Abs output frequency
01.64 Abs motor torque
01.65 Abs output power
01.68 Abs motor shaft power
13.91 AO1 data storage
13.92 AO2 data storage
Source selection (see
Terms and abbreviations
Forced value that can be used instead of the selected output
signal. See parameter
13.02 AO force
Forced value for AO1.
Selects the unit for readings and settings related to analog
input AO1.
Note: In firmware ASCL2 and ASCL4), this setting must
match the corresponding hardware setting on the drive
control unit. See chapter Electrical installation, section
Switches in the Hardware manual of the drive and the default
control connections for the macro in use in chapter
macros
(page 55). Control board reboot (either by cycling the
power or through parameter
required to validate any changes in the hardware settings.
Volts.
Milliamperes.
Defines the filtering time constant for analog output AO1.
%
Unfiltered signal
100
63
Filtered signal
T
-t/T
O = I × (1 - e
I = filter input (step)
O = filter output
t = time
T = filter time constant
Filter time constant.
(page 70).
(page 70).
(page 70).
(page 70).
(page 93).
(page 93).
selection.
96.08 Control board
t
)
Parameters 89
Def/FbEq16
28
30
31
32
37
38
on page 64).
-
0.000 mA
1 = 1 unit
mA
Control
boot) is
2
10
0.100 s
1000 = 1 s