ABB ACQ80-04 Firmware Manual page 179

Drives for water, standard control program
Hide thumbs Also See for ACQ80-04:
Table of Contents

Advertisement

No.
Name/Value
Advanced
Adaptive
99.15
Motor polepairs
calculated
0...1000
99.16
Motor phase order
U V W
U W V
Description
Advanced
ID run.
Adaptive
ID run.
Calculated number of pole pairs in the motor.
Number of pole pairs.
Switches the rotation direction of motor. This parameter can
be used if the motor turns in the wrong direction (for example,
because of the wrong phase order in the motor cable), and
correcting the cabling is considered impractical.
Note:
• Changing this parameter does not affect speed reference
polarities, so positive speed reference will rotate the motor
forward. The phase order selection just ensures that
"forward" is in fact the correct direction.
Normal.
Reversed rotation direction.
Parameters 179
Def/FbEq16
6
7
0
1 = 1
U V W
0
1

Hide quick links:

Advertisement

Table of Contents
loading