72 Parameters
No.
Name/Value
05.02
Run-time counter
0...65535 d
05.03
Pump run hours
0.0...
429496729.5 h
05.04
Fan on-time
counter
0...65535 d
05.10
Control board
temperature
-100... 300 °C
05.11
Inverter
temperature
-40.0...160.0%
05.20
Diagnostic word 1
Bit
Name
0
Any warning or fault
1
Any warning
2
Any fault
3
Reserved
4
Overcurrent flt
5
Reserved
6
DC overvoltage
7
DC undervoltage
8
Reserved
9
Device overtemp flt
10...15 Reserved
0b0000...0b1111
05.21
Diagnostic word 2
Bit
Name
0...9
Reserved
10
Motor overtemperature fault
11...15
Reserved
0b0000...0b1111
Description
Motor run-time counter. The counter runs when the inverter
modulates.
Motor run-time counter.
Shows the pump running time in hours. The pump run hours
is based on the value in parameter
and is calculated as, 24 *
day.
Hours.
Shows running time of the drive cooling fan. Can be reset
from the control panel by keeping Reset down for over 3
seconds.
Cooling fan run-time counter.
Shows measured temperature of the control board
Control board temperature in degrees Celsius or Fahrenheit.
Shows estimated drive temperature in percent of fault limit.
The fault limit varies according to the type of the drive.
0.0% = 0 °C (32 °F)
100.0% = Fault limit
Drive temperature in percent.
Diagnostic word 1. For possible causes and remedies, see
chapter
Fault
tracing.
Value
Yes = Drive has generated a warning or tripped on a fault.
Yes = Drive has generated a warning.
Yes = Drive has tripped on a fault.
Yes = Drive has tripped on fault
Yes = Drive has tripped on fault
Yes = Drive has tripped on fault
Yes = Drive has tripped on fault
Diagnostic word 1.
Diagnostic word 2. For possible causes and remedies, see
chapter
Fault
tracing.
Value
Yes = Drive has tripped on fault
temperature 1 or4982 External temperature 2
Diagnostic word 2.
05.02 Run-time counter
05.02
value + fractional part of a
2310
Overcurrent.
3210 DC link
3220 DC link
4310 Excess
Def/FbEq16
0
1 = 1 d
-
1 = 1 h
0
1 = 1 d
0
1 = unit
0
1 = 1%
0b0000
overvoltage.
undervoltage.
temperature.
1 = 1
0b0000
4981 External
1 = 1