Motor Thermal Protection - ABB ACQ80-04 Firmware Manual

Drives for water, standard control program
Hide thumbs Also See for ACQ80-04:
Table of Contents

Advertisement

120 Parameters
No.
Name/Value
32.56
Supervision 6
action
No action
Warning
Fault
Fault if running
32.57
Supervision 6
signal
32.58
Supervision 6 filter
time
0.000 ... 30.000 s
32.59
Supervision 6 low
-21474836.00...
21474836.00
32.60
Supervision 6 high
-21474836.00...
21474836.00
32.61
Supervision 6
hysteresis
0.00...100000.00
35
35 Motor thermal
protection
35.01
Motor estimated
temperature
-60...1000 °C or
-76...1832 °F
35.02
Measured
temperature 1
-60...5000 °C or
-76...9032 °F
Description
Selects whether the drive generates a fault, warning or
neither when the value monitored by signal supervision 6
exceeds its limits.
Note: This parameter does not affect the status indicated by
32.01 Supervision
status.
No warning or fault generated.
Warning
A8B5 Signal supervision 6
Drive trips on fault
80B5 Signal supervision
Drive trips on fault
80B0 Signal supervision 1
running.
Selects the signal to be monitored by signal supervision
function 6.
For the available selections, see parameter
Supervision 1
signal.
Defines a filter time constant for the signal monitored by
signal supervision 6.
Signal filter time.
Defines the lower limit for signal supervision 6.
Low limit.
Defines the upper limit for signal supervision 6.
Upper limit.
Defines the hysteresis for the signal monitored by signal
supervision 6.
Hysteresis.
Motor thermal protection settings such as temperature
measurement configuration, load curve definition and motor
fan control configuration.
See also section

Motor thermal protection

Shows motor temperature as estimated by the internal motor
thermal protection model (see parameters 35.50...35.55).
The unit is selected by parameter
This parameter is read-only.
Estimated motor temperature.
Shows temperature received through the source defined by
parameter
35.11 Temperature 1
by parameter
96.16 Unit
Note: With a PTC sensor, the value shown is not a valid
measurement. Either 0 ohm (normal temperature) or the
value of parameter
35.22 Temperature 2 fault limit
temperature) is shown.
This parameter is read-only.
Measured temperature 1.
is generated.
6.
if the motor is
32.07
(page 44).
96.16 Unit
selection.
source. The unit is selected
selection.
Def/FbEq16
No action
0
1
2
3
Zero
0.000 s
1000 = 1 s
0.00
-
0.00
-
0.00
-
0
1 = 1°C
0
(excessive
1 = 1 unit

Hide quick links: