No.
Name/Value
Speed or frequency Type and scaling is chosen automatically according to the
Transparent
General
Torque
Speed
Frequency
58.29
EFB act2 type
58.31
EFB act1
transparent source
Not selected
Other
58.32
EFB act2
transparent source
58.33
Addressing mode
Mode 0
Mode 1
Mode 2
58.34
Word order
HI-LO
LO-HI
Description
currently active operation mode as follows.
Motor control mode
(see par. 99.04)
Speed control
Frequency control
No scaling is applied.
Generic reference without a specific unit. Scaling: 1 = 100.
Scaling is defined by parameter
Scaling is defined by parameter
Scaling is defined by parameter
frequency.
Not applicable
Selects the source of actual value 1 when parameter
EFB act1 type is set to
Transparent.
Note: Applicable only when
disabled. If parameter MPPT reference is enabled, then the
parameter should be set to it's default value.
None.
Source selection (see
Terms and abbreviations
Not applicable
Defines the mapping between parameters and holding
registers in the 400101...465535 Modbus register range.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
Communication control (Refresh
16-bit values (groups 1...99, indexes 1...99):
Register address = 400000 + 100 × parameter group +
parameter index.
32-bit values (groups 1...99, indexes 1...99):
Register address = 420000 + 200 × parameter group +
2 × parameter index.
16-bit values (groups 1...255, indexes 1...255):
Register address = 400000 + 256 × parameter group +
parameter index.
32-bit values (groups 1...127, indexes 1...255):
Register address = 400000 + 512 × parameter group +
2 × parameter index.
Selects in which order 16-bit registers of 32-bit parameters
are transferred.
For each register, the first byte contains the high order byte
and the second byte contains the low order byte.
Changes to this parameter take effect after the control unit is
rebooted or the new settings validated by parameter
Communication control (Refresh
The first register contains the high order word, the second
contains the low order word.
The first register contains the low order word, the second
contains the high order word.
Actual 1 type
Speed
Frequency
46.03 Torque
scaling.
99.09 Motor nominal
99.08 Motor nominal
79.40 MPPT reference
is
on page 64).
settings).
settings).
Parameters 153
Def/FbEq16
0
1
2
3
speed.
4
5
58.28
Not selected
0
-
Mode 0
58.06
0
1
2
LO-HI
58.06
0
1