Page 1
— ABB DRIVES FOR WATER ACQ580-07 Hardware manual...
Page 3
ACQ580-07 Hardware manual Table of contents 1. Safety instructions 4. Mechanical installation 5. Guidelines for planning the electrical installation 6. Electrical installation 9. Start-up 3AXD50000045817 Rev E EFFECTIVE: 2020-09-22...
Page 5
English ADDED: Connectivity for wired remote monitoring (option +K496) This option provides a gateway to connect the drive to ABB Ability™ via a local Ethernet network. Includes NETA-21 remote monitoring tool and FMBT-21 Modbus/TCP adapter module. The NETA and FMBT-21 are installed at the factory and wired internally. An Ethernet cable for customer connection is routed from the NETA to the external control connections mounting plate (number 6 in the layout drawing for frames R6...R9, number 12 for frames...
Page 6
2 Update notice The NETA and FMBT-21 are installed at the factory and wired internally. An Ethernet cable for customer connection is routed from the NETA to the external control connections mounting plate (number 6 in the layout drawing for frames R6...R9, number 12 for frames R10 and R11).
Page 7
Update notice 3 ■ Wiring of Pt100 relays External wiring of sensor modules is shown below. Contact load capacity 250 V AC 10 A. For the actual wiring, see the circuit diagram delivered with the drive. X506 1xPt100 Sensor 1 Internal wiring for overheat indication Sensor 1...3 overtemperature = contact open Sensor 2...
Page 9
Table of contents 5 Table of contents 1 Safety instructions Contents of this chapter ..................Use of warnings and notes ................. General safety in installation, start-up and maintenance ........Electrical safety in installation, start-up and maintenance ........Electrical safety precautions ................ Additional instructions and notes ..............
6 Table of contents Cabinet layout – R10 and R11 (top entry and exit of cables, options +H351 and +H353) ....................Mounting plate – R10 and R11 ..............Cooling air flow ..................... Door switches and lights ................Main switch-disconnector Q1 ............Control panel ....................
Page 11
Availability of du/dt filter and common mode filter by drive type ..Additional requirements for explosion-safe (EX) motors ....Additional requirements for ABB motors of types other than M2_, M3_, M4_, HX_ and AM_ ..............Additional requirements for ABB high-output and IP23 motors ..
Page 12
8 Table of contents Signals that can be run in the same cable ........... Relay cable ....................Control panel to drive cable ................. PC tool cable ....................Routing the cables ....................General guidelines – IEC ................General guidelines – North America ............Continuous motor cable shield/conduit or enclosure for equipment on the motor cable ....................
Table of contents 9 Connection diagram ..................Connection procedure (frames R6…R9) ............. Connection procedure (frames R6 and R7 with options +H351 and +H353) ......................Connection procedure (frames R8 and R9 with options +H351 and +H353) ......................Connection procedure (frames R10 and R11) ..........Connection procedure (frames R10 and R11 with options +H351 and +H353) ......................
Page 14
10 Table of contents AI1 and AI2 as Pt100, Pt1000, Ni1000, KTY83 and KTY84 sensor inputs (X1) ......................Safe torque off (X4) ..................Technical data ..................... 8 Installation checklist Contents of this chapter ..................Checklist ......................9 Start-up Contents of this chapter ..................Start-up procedure ....................
Page 15
Table of contents 11 Capacitors ......................Reforming the capacitors ................Fuses ........................Replacing AC fuses (frames R6 and R7) ............. Replacing AC fuses ..................Control panel ....................... Cleaning the control panel ................Replacing the battery ................... 12 Technical data Contents of this chapter ..................Ratings ........................
Page 16
12 Table of contents Finish ......................Package ....................... Vertical package ................Horizontal package ................Package dimensions and weights for drives without empty cubicles (without options +C196 … +C201) ................... Package weights ..................Applicable standards ................... Markings ......................CE marking ......................Compliance with the European Low Voltage Directive ........
Page 17
Description ......................Compliance with the European Machinery Directive ........Wiring ........................Connection principle ..................Single ACQ580-07 drive, internal power supply ....... Single ACQ580-07 drive, external power supply ......Wiring examples ................... Single ACQ580-07 drive, internal power supply ....... Single ACQ580-07 drive, external power supply ......
Page 18
14 Table of contents Fault and warning messages ................Technical data ..................... Dimension drawing ..................... 16 CMOD-01 multifunction extension module (external 24 V AC/DC and digital I/O) Contents of this chapter ..................Product overview ....................Layout and example connections ............... Mechanical installation ..................
Page 19
Table of contents 15 18 Disconnecting EMC filter and ground-to-phase varistor When to disconnect the ground-to-phase varistor: TN-S, IT, corner-grounded delta and midpoint-grounded delta systems ............Guidelines for installing the drive to a TT system ..........Identifying the grounding system of the electrical power network ...... Disconnecting the EMC filter and ground-to-phase varistor (frames R6…R9) ..
Page 21
Safety instructions 17 Safety instructions Contents of this chapter This chapter contains the safety instructions which you must obey when you install, start up, operate and do maintenance work on the drive. If you ignore the safety instructions, injury, death or damage can occur. Use of warnings and notes Warnings tell you about conditions which can cause injury or death, or damage to the equipment.
Page 22
18 Safety instructions General safety in installation, start-up and maintenance These instructions are for all personnel who do work on the drive. WARNING! Obey these instructions. If you ignore them, injury or death, or damage to the equipment can occur. •...
Page 23
Safety instructions 19 It is heavy and its center of gravity is high. The module overturns from a sideways tilt of 5 degrees. Do not leave the module unattended on a sloping floor. • To prevent the drive module from falling, attach its top lifting lugs with chains to the cabinet (1) before you push the module into the cabinet and pull it from the cabinet.
Page 24
20 Safety instructions • Before you activate the automatic fault reset or automatic restart functions of the drive control program, make sure that no dangerous situations can occur. These functions reset the drive automatically and continue operation after a fault or supply break.
Page 25
Safety instructions 21 • Open the charging switch if present. • Open the disconnector of the supply transformer. (The main disconnecting device in the drive cabinet does not disconnect the voltage from the AC input power busbars of the drive cabinet.) •...
Page 26
22 Safety instructions Measuring points of frames R6 to R9 are shown below. L1, L2, L3...
Page 27
Safety instructions 23 Measuring points of frames R10 and R11 are shown below. You can also remove the metallic shield and measure through the holes in the clear plastic shroud behind it. L1 L2 • Make sure that the voltage between the drive output terminals (T1/U, T2/V, T3/W) and the grounding (PE) busbar is zero.
Page 28
There are electromagnetic fields present which can interfere with the function of such devices. This can cause a health hazard. • ABB recommends against attaching the cabinet by arc welding. If you have to, obey the welding instructions in the drive manuals. Note: •...
Page 29
Safety instructions 25 ■ Grounding These instructions are for all personnel who are responsible for the grounding of the drive. WARNING! Obey these instructions. If you ignore them, injury or death, or equipment malfunction can occur, and electromagnetic interference can increase. If you are not a qualified electrical professional, do not do grounding work.
Page 30
26 Safety instructions General safety in operation These instructions are for all personnel that operate the drive. WARNING! Obey these instructions. If you ignore them, injury or death, or damage to the equipment can occur. • Keep the cabinet doors closed when the drive is powered. With the doors open, a risk of a potentially fatal electric shock, arc flash or high-energy arc blast exists.
Page 31
Safety instructions 27 If you are not a qualified electrical professional, do not do installation or maintenance work. • Do not do work on the drive when a rotating permanent magnet motor is connected to it. A rotating permanent magnet motor energizes the drive including its input and output power terminals.
Page 33
Introduction to the manual 29 Introduction to the manual Contents of this chapter This chapter describes the intended audience and contents of the manual. It contains a flowchart of steps in examining the delivery, installing and commissioning the drive. The flowchart refers to chapters/sections in this manual and other manuals. Target audience This manual is intended for people who plan the installation, install, start up and do maintenance work on the drive, or create instructions for the end user of the drive...
Page 34
30 Introduction to the manual Quick installation flowchart Task Plan the electrical installation and acquire the accessories needed Guidelines for planning the (cables, fuses, etc.). electrical installa- Check the ratings, required cooling air flow, input power connection, tion (page 79) compatibility of the motor, motor connection, and other technical Technical data (page 197) data.
Page 35
Introduction to the manual 31 Task Operate the drive: start, stop, speed control etc. Start-up (page 155) firmware manual Terms and abbreviations Term/ Description Abbrevi- ation ACH-AP-H Assistant control panel with Hand-Off-Auto functionality ACH-AP-W Assistant control panel with Hand-Off-Auto functionality and Bluetooth interface CCU-24 Type of control unit CHDI-01...
Page 37
Introduction to the manual 33 You can find manuals and other product documents in PDF format on the Internet at www.abb.com/drives/documents. The code below opens an online listing of the manuals applicable to this product. ACQ580-07 manuals...
Page 39
Operation principle and hardware description 35 Operation principle and hardware description Contents of this chapter This chapter briefly describes the operation principle and construction of the drive.
Page 40
36 Operation principle and hardware description Product overview The ACQ580-07 is a drive module for controlling AC induction motors, synchronous reluctance motors and synchronous permanent magnet motors in open loop control. The single-line circuit of the drive is shown below.
Page 41
Operation principle and hardware description 37 Layout ■ General information on the cabinet layout IP21 IP42 UL Type 1 UL Type 1 Filtered (option +B054)
Page 42
38 Operation principle and hardware description ■ Cabinet layout – R6 and R7 (bottom entry and exit of cables) The cabinet layout of frame R7 with du/dt filter (option +E205) is shown below. Degree of protection IP42 (UL Type 1 Filtered [option +B054]). Frame R6 looks similar. Cabinet door closed Auxiliary voltage transformer T21 Cabinet door open...
Page 43
Operation principle and hardware description 39 Power and control cable entries ■ Cabinet layout – R6 and R7 (top entry and exit of cables, options +H351 and +H53) Cabinet door closed Power and control cable entries Cabinet door open Auxiliary voltage transformer T21 Cabinet door open and motor cable cubicle Motor cable connection terminals cover removed...
Page 44
40 Operation principle and hardware description Lifting lugs Common mode filter (option +E208) behind the mounting plate Cabinet door fan du/dt filter (option +E205) ■ Cabinet layout – R8 and R9 (bottom entry and exit of cables) The cabinet layout of frame R9 with du/dt filter (option +E205) is shown below. Degree of protection IP42 (UL Type 1 Filtered [option +B054]).
Page 45
Operation principle and hardware description 41 Gratings for cooling air out Additional I/O terminal block (option +L504) Drive control unit Mounting plate, see section Mounting plate – R6 to R9 (page 42) Lifting lugs Common mode filter (option +E208) Cabinet door fan du/dt filter (option +E205) Power and control cable entries Motor cable connection terminals...
Page 46
42 Operation principle and hardware description Drive control panel AC fuses Operating switch Main contactor (Q2, option +F250) Main switch handle Power cable connection terminals of the drive module behind the shroud Gratings for cooling air in Drive module Gratings for cooling air out Additional I/O terminal block (option +L504) Drive control unit Mounting plate, see section...
Page 47
Operation principle and hardware description 43 +G300 switch-disconnector and miniature cir- External main contactor control cuit breaker for cabinet heater (option +G300) Emergency stop relay for options X250 Indication of main contactor status5 +Q951 and +Q963 Q95, Switch-disconnector and miniature X289 Indication of the status of the molded circuit breaker for cabinet heater (op-...
Page 48
44 Operation principle and hardware description T22, 24VDC power supply and buffer with X969 Connection of external Safe torque off emergency stop options (+Q951 and button +Q963), also with line contactor option (+F250). X251, X4, X6, X56, X53, X51, X55, X18 and X19: for internal use. X250 Terminals for X250...
Page 49
Operation principle and hardware description 45 ■ Cabinet layout – R10 and R11 (bottom entry and exit of cables) Cabinet door closed Main switch-disconnector Cabinet door open AC fuses Gratings for cooling air out Line contactor (option +F250) Operating switch Lifting lugs Drive control panel Drive control unit...
Page 50
46 Operation principle and hardware description Cabinet door open, mounting plates and Input cable connection terminals cabinet shrouds removed Power and control cable entries Drive module Motor cable connection terminals Auxiliary voltage transformer T21...
Operation principle and hardware description 47 ■ Cabinet layout – R10 and R11 (top entry and exit of cables, options +H351 and +H353) Cabinet door closed Lifting lugs Cabinet door open Cubicle for motor cabling Gratings for cooling air out Drive control unit Drive control panel Mounting plate, see section...
48 Operation principle and hardware description Cabinet door open, lower shrouds and Auriliary voltage transformer T21 motor cable cubicle cover removed Input cable connection terminals behind Drive module the shroud Motor cable connection terminals ■ Mounting plate – R10 and R11 The components and terminals on the mounting plate of frames R10 and R11 are shown below.
Page 53
Operation principle and hardware description 49 Drive control unit X289 Indication of the status of the molded case circuit breaker (option +F289) Emergency stop relay for options X300 Connection terminals for cabinet +Q951 and +Q963 heater (option +G300) Q95, Switch-disconnector and miniature X951 Connection of external emergency circuit breaker for cabinet heater (op-...
50 Operation principle and hardware description T22, 24VDC power supply and buffer with K41.1 Ready pilot light control relay (option emergency stop options (+Q951 and +G327) +Q963), also with line contactor option (+F250). External main contactor control K41.2 Run pilot light control relay (op- tion+G328) X250 Indication of main contactor status...
Operation principle and hardware description 51 ■ Door switches and lights Label in English Label in local Description language READY Ready pilot light (option +G327) Run pilot light (option+G328) FAULT Fault pilot light (option +G329) MAIN CONTACT- Operating switch with option +F250 Opens the main contactor (Q2) and disables OFF ON starting of the drive...
52 Operation principle and hardware description Control by PC tools There is a USB connector on the front of the panel that can be used to connect a PC to the drive. When a PC is connected to the control panel, the control panel keypad is disabled.
Operation principle and hardware description 53 Overview of power and control connections The diagram shows the power connections and control interfaces of the drive. SLOT 1 SLOT 2 M 3 ~ Option slot 1 for optional fieldbus adapter modules Option slot 2 for optional I/O extension modules Embedded fieldbus connector Panel port...
54 Operation principle and hardware description Descriptions of options Note: All options are not available for all drive types, do not coexist with certain other options, or may require additional engineering. Check actual availability with ABB. ■ Degree of protection...
Operation principle and hardware description 55 • all components UL/CSA Listed/Recognized • maximum supply voltage 480 V • US-type main switch and fuses. ■ Plinth height (options +C164 and +C179) The standard height of the cabinet plinth is 50 mm. These options specify a plinth height of 100 mm (+C164) or 200 mm (+C179).
56 Operation principle and hardware description For North American market only. ■ Cabinet heater with external supply (option +G300) The option contains: • heating elements in the cubicles or supply/inverter modules • load switch for providing electrical isolation during service •...
Operation principle and hardware description 57 ■ Additional terminal block X504 (option +L504) The standard terminal blocks of the drive control unit are wired to the additional terminal block at the factory for customer control wiring. The terminals are spring loaded. Note: The optional modules inserted in the slots of the control unit are not wired to the additional terminal block.
Type designation key The type designation contains information on the specifications and configuration of the drive. The first digits from left express the basic configuration (eg, ACQ580-07-0640A-4). The optional selections are given thereafter, separated by plus signs, eg, +B055. The main selections are described below.
Operation principle and hardware description 59 Code Description When no options are selected: cabinet-installed drive, IP21, main switch, AC fuses, ACH-AP-H assistant control panel, for frames R6 to R9 EMC filtering for first environment TN grounded systems (category C2), for frames R10 and R11 EMC filtering for second environment TN grounded systems (category C3), input choke, common mode filter in frames R10 and R11, coated boards, ACQ580 pump control program, EIA/RS-485 fieldbus connector, Safe torque off function, bottom entry and exit of cables, multilingual...
Page 64
60 Operation principle and hardware description Code Description E208 Common mode filtering (standard with frames R10 and R11) F250 Main (line) contactor F289 MCCB circuit breaker Cabinet and module heating elements (external supply). See section Cabinet heater G300 with external supply (option +G300) (page 56).
Page 65
Operation principle and hardware description 61 Code Description M602 Trip limit setting range: 2.5 … 4 A M603 Trip limit setting range: 4 … 6.3 A M604 Trip limit setting range: 6.3 … 10 A M605 Trip limit setting range: 10…16 A P912 Seaworthy packaging P929...
Mechanical installation 63 Mechanical installation Contents of this chapter This chapter describes the mechanical installation procedure of the drive. Examining the installation site Examine the installation site. Make sure that: • The installation site is sufficiently ventilated or cooled to remove heat from the drive. See the technical data.
64 Mechanical installation Do not install the drive on an elevated platform or a recess. The module extraction/installation ramp included with the drive is only suitable for a height difference of 50 mm (2 in) maximum (ie. the standard plinth height of the drive). Necessary tools The tools required for moving the unit to its final position, fastening it to the floor and wall and tightening the connections are listed below:...
Page 70
66 Mechanical installation Vertical package (frames R10 and R11): 1088 Lifting the transport package with slings. Lifting points Lifting the transport package with forklift...
Mechanical installation 67 ■ Unpacking the transport package This drawing shows the layout of the horizontal transport package. Bracket for attaching the drive to the Timber wooden pallet Cardboard packing hood Drive cabinet Wooden pallet Plinth (delivered in a separate package for frames R6…R9) Straps Unpack the horizontal transport package as follows:...
Lift the cabinet to its position. Maximum allowed angle of the lifting slings is 20° (10° for frames R10 and R11, IP54). ° Max. 10 ° Max. 20 R10, R11 IP54 Lifting lugs Certificate of conformity The certificate is available in ABB Library at www.abb.com/drives/documents (document number 3AXD10001061361).
Page 75
Mechanical installation 71 Declaration of Conformity...
72 Mechanical installation ■ Moving the cabinet after unpacking Move drive cabinet carefully in the upright position. Avoid tilting. The center of gravity of the cabinet is high.
Mechanical installation 73 Moving the cabinet with rollers Lay the cabinet on the rollers and move it care- fully until close to its final location. Remove the rollers by lifting the unit with a crane, forklift, pallet truck or jack. Moving the cabinet to its final placement with a slate bar Move the cabinet into its final position with an iron bar.
74 Mechanical installation > 400 mm (15.75”) 120° Note 1: Any height adjustment must be done before attaching the cabinet sections to the floor or to each other. Height adjustment can be done by using metal shims between the cabinet bottom and floor. Note 2: Depending on the size of the cabinet, it has either bolt-on lifting eyes, or lifting bars with lifting holes.
Page 79
Mechanical installation 75 2. If floor mounting at the back is not possible, fasten the top of the cabinet to the wall with L-brackets (not included in the delivery) bolted to the lifting eye/bar holes, and suitable hardware. Clamping bottom to floor Attaching top to wall...
76 Mechanical installation Alternative 2 – Using the holes inside the cabinet 1. Attach the cabinet to the floor through the bottom fastening holes with M10 to M12 (3/8” to 1/2”) bolts. The recommended maximum distance between the front edge fastening points is 800 mm (31.5”).
Mechanical installation 77 Alternative 3 – Cabinets with plinth options +C164 and +C179 Frames R6…R9 1. Attach the plinth to the floor with the brackets included in the plinth package. 2. Lift the cabinet onto the plinth and attach it to the plinth with the L-brackets delivered with the plinth.
■ Arc welding ABB does not recommend attaching the cabinet by arc welding. However, if arc welding is the only option, connect the return conductor of the welding equipment to the cabinet frame at the bottom within 0.5 meters (1’6”) of the welding point.
ABB does not assume any liability whatsoever for any installation which breaches the local laws and/or other regulations. Furthermore, if the recommendations given by ABB are not followed, the drive may experience problems that the warranty does not cover.
Examining the compatibility of the motor and drive Use asynchronous AC induction motors, permanent magnet synchronous motors, AC induction servomotors or ABB synchronous reluctance motors (SynRM motors) with the drive. Select the motor size and drive type from the rating table on basis of the AC line voltage and motor load.
Page 85
Guidelines for planning the electrical installation 81 This table shows the requirements when an ABB motor is in use. Motor type Nominal AC sup- Requirement for ply voltage Motor insu- ABB du/dt and common mode filters, in- lation sys- sulated N-end motor bearings P n <...
Page 86
82 Guidelines for planning the electrical installation This table shows the requirements when a non-ABB motor is in use. Motor type Nominal AC sup- Requirement for ply voltage Motor insu- ABB du/dt and common mode filters, in- lation sys- sulated N-end motor bearings P n <...
If you will use an explosion-safe (EX) motor, follow the rules in the requirements table above. In addition, consult the motor manufacturer for any further requirements. Additional requirements for ABB motors of types other than M2_, M3_, M4_, HX_ and AM_ Use the selection criteria given for non-ABB motors.
The rated output power of high-output motors is higher than what is stated for the particular frame size in EN 50347 (2001). If you plan to use a non-ABB high-output motor or an IP23 motor, consider these additional requirements for protecting the motor insulation and bearings in drive systems: •...
Guidelines for planning the electrical installation 85 Nominal AC supply Requirement for voltage Motor insulation sys- ABB du/dt and common mode filters, insu- lated N-end motor bearings P n < 100 kW or frame 100 kW < P n < 350 kW size < IEC 315 IEC 315 <...
Page 90
86 Guidelines for planning the electrical installation Û du/dt ------------ - (1/Ps) l (m) du/dt ------------ - (1/Ps) Û l (m) Drive with du/dt filter Drive without du/dt filter Motor cable length Û LL /U N Relative peak line-to-line voltage (du/dt)/U N Relative du/dt value...
Guidelines for planning the electrical installation 87 Selecting the power cables ■ General guidelines Select the input power and motor cables according to local regulations. • Current: Select a cable capable of carrying the maximum load current. • Temperature: For an IEC installation, select a cable rated for at least 70 °C (158 °F) maximum permissible temperature of conductor in continuous use.
88 Guidelines for planning the electrical installation • use a second protective earth conductor of the same cross-sectional area as the original protective earth conductor, • use a device that automatically disconnects the supply if the protective earth conductor is damaged. If the protective earth conductor is separate (that is, it does not form part of the input power cable or the input power cable enclosure), the minimum cross-sectional area must be: 2.5 mm 2 when the conductor is mechanically protected,...
Guidelines for planning the electrical installation 89 Alternate power cable types Cable type Use as input power cabling Use as motor cabling Yes with phase conductor Yes with phase conductor smaller than 10 mm 2 (8 AWG) smaller than 10 mm 2 (8 AWG) Cu, or motors up to 30 kW (40 hp).
■ Additional guidelines, North America ABB recommends the use of conduit for power wiring to the drive and between the drive and the motor(s). Due to the variety of application needs, metallic and non-metallic conduit can be used. ABB recommends the use of metallic conduit.
Guidelines for planning the electrical installation 91 Wiring method Notes Free air Prefer symmetrical shielded VFD cable. Enclosures, air handlers, etc. Allowed internally in enclosures when in accord- ance with UL. 1) Metallic conduit may be used as an additional ground path, provided this path is a solid path capable of handling ground currents.
■ Relay cable The cable type with braided metallic shield (for example ÖLFLEX by LAPPKABEL, Germany) has been tested and approved by ABB. ■ Control panel to drive cable Use EIA-485 with male RJ-45 connector, cable type Cat 5e or better. The maximum permitted length of the cable is 100 m (328 ft).
Guidelines for planning the electrical installation 93 Routing the cables ■ General guidelines – IEC • Route the motor cable away from other cables. Motor cables of several drives can be run in parallel installed next to each other. • Install the motor cable, input power cable and control cables on separate trays.
94 Guidelines for planning the electrical installation ■ General guidelines – North America Make sure that the installation is in accordance with national and local codes. Obey these general guidelines: • Use separate conduits for the input power, motor, brake resistor (optional), and control cabling.
Guidelines for planning the electrical installation 95 ■ Continuous motor cable shield/conduit or enclosure for equipment on the motor cable To minimize the emission level when safety switches, contactors, connection boxes or similar equipment are installed on the motor cable between the drive and the motor: •...
96 Guidelines for planning the electrical installation R6, R7 R8…R11 ■ Protecting the motor and motor cable in short-circuits The drive protects the motor cable and motor in a short-circuit situation when the motor cable is sized according to the nominal current of the drive. No additional protection devices are needed.
98 Guidelines for planning the electrical installation It keeps the contactor closed in short power-loss situations. If the drive is equipped an external uninterruptible auxiliary power supply (option +G307), it keeps the main contactor closed in power-loss situations. Note that if the power loss lasts so long that the drive trips on undervoltage, a fault reset and a fresh start command is required to continue operation.
Guidelines for planning the electrical installation 99 Using a safety switch between the drive and the motor ABB recommends to install a safety switch between the permanent magnet motor and the drive output. The switch is needed to isolate the motor from the drive during maintenance work on the drive.
IEC/EN 61800-5-1, subclause 6.5.3, for example, “THIS MACHINE STARTS AUTOMATICALLY”. Bypass connection is available as a factory-installed option for some cabinet-installed drive types. Consult ABB for more information. WARNING! Never connect the drive output to the electrical power network. The connection may damage the drive.
Guidelines for planning the electrical installation 101 230 V AC 230 V AC + 24 V DC Relay output Varistor RC filter Diode Implementing a motor temperature sensor connection WARNING! IEC 60664 and IEC 61800-5-1 require double or reinforced insulation between live parts and accessible parts when: •...
102 Guidelines for planning the electrical installation Note: Extra-low voltage circuits (for example, 24 V DC) typically do not meet these requirements. As an alternative, you can connect the sensor with basic insulation to the analog/digital input(s) of the drive, if you do not connect any other external control circuits to the drive digital and analog inputs.
Guidelines for planning the electrical installation 103 Option module Temperature Temperature sensor in- sensor type sulation requirement Type Insulation/Isolation Pt100, Pt1000 CMOD-02 Reinforced insulation No special requirement between the sensor con- CPTC-02 No special requirement nector and the other con- nectors of the module (in- cluding drive control unit connector).
Electrical installation 105 Electrical installation Contents of this chapter This chapter gives instructions on the wiring the drive. Warning WARNING! If you are not a qualified electrical professional, do not do installation or maintenance work. Obey the safety instructions of the drive. If you ignore them, injury or death, or damage to the equipment can occur.
106 Electrical installation Layout of the cable entries (frames R6…R9) The layout of the input and motor cable connection terminals of frame R9 bottom entry without du/dt filter option (+E205) is shown below. The shrouds in front of the terminals are removed.
Electrical installation 107 Layout of the cable entries (frames R10 and R11) The layout of the input and motor cable connection terminals of frame R10 bottom entry is shown below. The shrouds in front of the terminals are removed. The layout is similar for frame R11.
Use a measuring voltage of 1000 V DC. The insulation resistance of an ABB motor must be more than 100 Mohm (reference value at 25 C [77°F]). For the insulation resistance of other motors, refer to the manufacturer’s instructions.
Electrical installation 109 U1-PE, V1-PE, W1-PE 1000 V DC, > 100 Mohm Grounding system compatibility check The standard drive can be installed to a symmetrically grounded TN-S system. If you install the drive to another system, you may need to disconnect the EMC filter and ground-to-phase varistor.
Page 114
110 Electrical installation 2. Prepare the ends of the cables. WARNING! Apply grease to stripped aluminum conductors before attaching them to non-coated aluminum cable lugs. Obey the grease manufacturer’s instructions. Aluminum-aluminum contact can cause oxidation in the contact surfaces. 3. If fire insulation is used, make an opening in the mineral wool sheet according to the diameter of the cable.
Electrical installation 111 ■ Connection diagram T1/ T2/ T3/ (PE) (PE) Use a separate grounding PE cable (1a) or a cable with a separate PE conductor (1b) if the conductivity of the shield does not meet the requirements for the PE conductor. 360-degree grounding is recommended if shielded cable is used.
Page 116
112 Electrical installation 360-degree grounding is required. Line contactor (option +F250) Common mode filter (option +E208 for frames R6 to R9). Standard in frames R10 and R11. du/dt filter (option +E205) Use a separate grounding cable if the shield does not meet the requirements of IEC 61439- 1 and there is no symmetrically constructed grounding conductor in the cable.
Electrical installation 113 ■ Connection procedure (frames R6…R9) This section applies to drives with bottom entry and exit of power cables. 1. Do the steps in section Electrical safety precautions (page 20) before you start the work. 2. Open the cabinet door. 3.
114 Electrical installation 5. For drives without option +E205: Knock out holes in the shroud for the motor cable conductors. 6. Connect the twisted shields of the motor cables to the ground bar and the phase conductors to the U2, V2 and W2 terminals of the drive module. For drives with du/dt filter (option +E205), connect the phase conductors to the T1/U2, T2/V2 and T3/W2 terminals of the cabinet with cable lugs.
Page 119
Electrical installation 115 4. Connect the twisted shields of the motor cables to the ground bar and the phase conductors to the U2, V2 and W2 terminals of the drive module. 5. Connect the twisted shields of the input cables and separate ground cable (if present) to the PE terminal of the cabinet and the phase conductors to the L1, L2 and L3 terminals.
116 Electrical installation 6. Tighten the power cable screws to the torque given in Terminal and entry data for the power cables (page 209). 7. Reinstall the shrouds and mounting plate. ■ Connection procedure (frames R8 and R9 with options +H351 and +H353) 1.
Page 121
Electrical installation 117 3. Remove the shrouds. 4. Connect the twisted shields of the motor cables to the ground bar and the phase conductors to the U2, V2 and W2 terminals of the drive module. 5. Connect the twisted shields of the input cables and separate ground cable (if present) to the PE terminal of the cabinet and the phase conductors to the L1, L2 and L3 terminals.
118 Electrical installation 6. Tighten the power cable screws to the torque given in Terminal and entry data for the power cables (page 209). 7. Reinstall the shrouds and mounting plate.
Electrical installation 119 ■ Connection procedure (frames R10 and R11) 1. Do the steps in section Electrical safety precautions (page 20) before you start the work. 2. Open the cabinet door. 3. Remove the shroud. 4. Remove the door fan mounting plate. See section Replacing the door fan (frames R10 and R11) (page 166) 5.
120 Electrical installation 7. Tighten the power cable screws to the torque given in Terminal and entry data for the power cables (page 209). 8. Reinstall the shrouds and mounting plate. ■ Connection procedure (frames R10 and R11 with options +H351 and +H353) 1.
Electrical installation 121 3. With top entry (option +H351) and bottom exit: Undo the mounting screws and pull the shroud out. Remove the door fan mounting plate. See section Replacing the door fan (frames R10 and R11) (page 166) 4. With top entry and top exit (options +H351 and +H353): Remove the shrouds and door fan (see Replacing the door fan (frames R10 and R11) (page 166)).
122 Electrical installation 5. Connect the twisted shields of the motor cables to the ground bar and the phase conductors to the U2, V2 and W2 terminals of the drive module. 6. Connect the twisted shields of the input cables and separate ground cable (if present) to the PE terminal of the cabinet and the phase conductors to the L1, L2 and L3 terminals.
Electrical installation 123 7. Tighten the power cable screws to the torque given in Terminal and entry data for the power cables (page 209). 8. Reinstall the shrouds and mounting plate. Connecting the control cables See chapter Control unit (page 139) for the default I/O connections of the drive control program.
124 Electrical installation ■ Overview of control cable connection procedure WARNING! Obey the instructions in chapter Safety instructions. If you ignore them, injury or death, or damage to the equipment can occur. 1. Stop the drive and do the steps in section Electrical safety precautions (page 20) before you start the work.
Page 129
Electrical installation 125 Note 1: Keep the shields continuous as close to the connection terminals as possible. Secure the cables mechanically at the entry strain relief. Note 2: If the outer surface of the shield is non-conductive: • Cut the shield at the midpoint of the bare part. Be careful not to cut the conductors or the grounding wire (if present).
Page 130
126 Electrical installation Stripped cable Conductive surface of the shield exposed Stripped part covered with copper foil Cable shield Copper foil Shielded twisted pair Grounding wire Note for top entry of cables: When each cable has its own rubber grommet, sufficient IP and EMC protection can be achieved.
Page 131
Electrical installation 127 6. If more than one cable go through a grommet, seal the grommet by applying Loctite 5221 inside the grommet.
128 Electrical installation ■ Routing the control cables inside the cabinet The route of the control cables is shown below in frame R9. The route is similar for frames R6, R7 and R8. X504 (+L504)
Electrical installation 131 ■ Connecting external wiring to the control unit or optional I/O terminal block Note: Keep any signal wire pairs twisted as close to the terminals as possible. Twisting the wire with its return wire reduces disturbances caused by inductive coupling. Note: Leave slack to the control wires to make it possible to lift the control unit mounting plate a little when the drive module is replaced.
132 Electrical installation Leave the other ends of the control cable shields unconnected or ground them indirectly via a high-frequency capacitor with a few nanofarads, eg, 3.3 nF / 630 V. The shield can also be grounded directly at both ends if they are in the same ground line with no significant voltage drop between the end points.
Electrical installation 133 Frames R10 and R11 Customer connections X951 Customer external emergency stop reset Customer external emergency stop button Remove bridges 3–4 and 5–6 if there is an external emergency stop button. The bridge connections are installed only if the cabinet door push button is in use.
134 Electrical installation Frames R6...R9 X300 1 Internal wiring of the cabinet heater: heater off/fault = contact open. 1 Internal wiring of the cabinet heater: heater Frames R10...R11 off/fault = contact open. X300 XPE95 Setting the voltage range of the auxiliary control voltage transformer (T21) Connect the power supply wires of the auxiliary control voltage transformer according to the power network voltage.
Electrical installation 135 Connecting a PC WARNING! Do not connect the PC directly to the control panel connector of the control unit as this can cause damage. A PC (with eg, the Drive composer PC tool) can be connected as follows: 1.
136 Electrical installation Installing option modules WARNING! Obey the safety instructions of the drive. If you ignore them, injury or death, or damage to the equipment can occur. 1. Stop the drive and do the steps in section Electrical safety precautions (page 20) before you start the work.
Electrical installation 137 ■ Option slot 1 (fieldbus adapter modules) 1. Put the module carefully into its position on the control unit. 2. Tighten the mounting screw (CHASSIS) to 0.8 N·m (7 lbf·in). The screw tightens the connections and grounds the module. It is necessary for fulfilling the EMC requirements and for correct operation of the module.
Control unit 139 Control unit Contents of this chapter This chapter contains the default I/O connection diagram, descriptions of the terminals and technical data for the drive control unit (CCU-24).
140 Control unit Layout The layout of the external control connection terminals on the drive module control unit is shown below. SLOT 1 SLOT 1 Option slot 1 (fieldbus adapter modules) ANALOG IN/OUT 1…3 Analog input 1 4…6 Analog input 2 1…3 7…9 Analog outputs...
Control unit 141 Default I/O connection diagram The default control connections for the Water default are shown below. Reference voltage and analog inputs and outputs Signal cable shield (screen) Output frequency/speed reference: 0…10 V 1…10 kohm AGND Analog input circuit common +10V Reference voltage 10 V DC Actual feedback: 0…10 V...
142 Control unit Digital inputs DI1…DI5 also support 10 to 24 V AC Terminal sizes: 0.14…2.5 mm (all terminals) Tightening torques: 0.5…0.6 N·m (0.4 lbf·ft) Notes: Current [0(4)…20 mA, R in = 100 ohm] or voltage [0(2)…10 V, R in >200 kohm]. Change of setting requires changing the corresponding parameter.
Control unit 143 multifunction extension module. Activate the overtemperature supervision in the new digital input with these parameter settings: 1. Select the correct digital input from parameter 31.01 External event 1 source. 2. Check that parameter 31.02 External event 1 type is set to Fault = 0. For more information, see the firmware manual.
144 Control unit X50 :1 X50 1 +24V +24V DGND DGND +24 V DC DCOM DCOM 0 V DC X504:18 X504:18 WARNING! Do not connect the +24 V AC cable to the control board ground when the control board is powered using an external 24 V AC supply. PNP configurations without option +L504 Internal and external +24 V power supply connections without option +L504 for PNP configuration are shown below.
Control unit 145 +24V +24V DGND DGND +24 V DC DCOM DCOM 0 V DC WARNING! Do not connect the +24 V AC cable to the control board ground when the control board is powered using an external 24 V AC supply. ■...
146 Control unit ■ Connection examples of two-wire and three-wire sensors to analog input (AI2) Note: The maximum capability of the auxiliary voltage output (24 V DC [250 mA]) must not be exceeded. An example of a two-wire sensor/transmitter supplied by the drive auxiliary voltage output is shown below.
Control unit 147 ■ AI1 and AI2 as Pt100, Pt1000, Ni1000, KTY83 and KTY84 sensor inputs (X1) Sensors for motor temperature measurement can be connected between an analog input and output, an example connection is shown below. Leave the other end of the shield unconnected or ground it indirectly via a few nanofarads high-frequency capacitor, for example, 3.3 nF / 630 V.
148 Control unit Technical data External power supply Maximum power: 36 W, 1.50 A at 24 V AC/DC ±10% as standard Terminal size: 0.14…2.5 mm 2 Term. 40, 41 +24 V DC output Total load capacity of this outputs is 6.0 W (250 mA / 24 V) minus (Term.
Page 153
Control unit 149 Analog outputs AO1 and Current/voltage output mode for AO1 selected with a parameter, AO2 (Term. 7 and 8) Connection for obtaining 0…10 V from analog output 2 (AO2) (page 145). Current output: 0…20 mA, R load : < 500 ohm Voltage input: 0…10 V, R load : >...
Page 154
150 Control unit Isolation areas SLOT 1 1…3 4…6 7…8 10…12 24 V 13…15 16…18 34…38 EIA/R5-485 40, 41 Ext. 24 V SLOT 2 19…21 22…24 25…27 Panel port Power unit connection at the bottom of the control unit Reinforced insulation (IEC/EN 61800-5-1:2007, UL 61800-5-1 First edition) Functional insulation (IEC/EN 61800-5-1:2007, UL 61800-5-1 First edition)
Installation checklist 153 Installation checklist Contents of this chapter This chapter contains a checklist of the mechanical and electrical installation of the drive. Checklist Examine the mechanical and electrical installation of the drive before start-up. Go through the checklist together with another person. WARNING! Obey the safety instructions of the drive.
Page 158
154 Installation checklist Make sure that … The insulation resistance of the input power cable, motor cable and motor is measured according to local regulations and the manuals of the drive. The drive cabinet is attached to the floor, and if necessary due to vibration etc, also by its top to the wall or roof.
Start-up 155 Start-up Contents of this chapter This chapter contains the start-up procedure of the drive. The default device designations (if any) are given in brackets after the name, for example "main switch-disconnector (Q1)". The same device designations are also used in the circuit diagrams, typically. Start-up procedure Action Safety...
Page 160
156 Start-up Action Make sure that it is safe to connect voltage. Make sure that: • cabinet doors are closed • nobody is working on the drive or circuits that have been wired from outside into the drive cabinet • cover of the motor terminal box is on. Close the main switch-disconnector (Q1).
Fault tracing 157 Fault tracing Contents of this chapter This chapter describes the fault tracing possibilities of the drive. Warning and fault messages See the firmware manual for the descriptions, causes and remedies of the drive control program warning and fault messages.
(www.abb.com/drivesservices).For more information, consult your local ABB Service representative (www.abb.com/searchchannels). The maintenance and component replacement intervals are based on the assumption that the equipment is operated within the specified ratings and ambient conditions. ABB recommends annual drive inspections to ensure the highest reliability and optimum performance.
160 Maintenance ■ Recommended annual maintenance actions by the user Action Target IP42 air inlet and outlet meshes on the cabinet doors IP54 air filters on the cabinet doors Quality of supply voltage Spare parts Capacitor reforming, spare modules and spare capacitors Tightness of terminals Dustiness, corrosion or temperature Heat sink cleaning...
Maintenance 161 Cleaning the interior of the cabinet WARNING! Obey the safety instructions of the drive. If you ignore them, injury or death, or damage to the equipment can occur. If you are not a qualified electrical professional, do not do installation or maintenance work. WARNING! Use a vacuum cleaner with antistatic hose and nozzle, and wear a grounding wristband.
Maintenance 163 ■ Inlet (door) filters (IP54 / UL Type 12) 1. Stop the drive and do the steps in section Electrical safety precautions (page 20) before you start the work. 2. Remove the fasteners at the top of the grating. 3.
See the firmware manual for the actual signal which indicates the running time of the cooling fan. Reset the running time signal after fan replacement. Replacement fans are available from ABB. Do not use other than ABB specified spare parts. ■...
Maintenance 165 WARNING! Obey the instructions in chapter Safety instructions. If you ignore them, injury or death, or damage to the equipment can occur. 1. Stop the drive and do the steps in section Electrical safety precautions (page 20) before you start the work. 2.
166 Maintenance 3. Unplug the power supply wires. 4. Remove the shroud. 5. Undo the mounting screws and nuts of the fan. 6. Install the new fan in reverse order. ■ Replacing the door fan (frames R10 and R11) WARNING! Obey the instructions in chapter Safety instructions.
168 Maintenance ■ Replacing the cabinet fan (frames R10 and R11, IP54 / UL Type 12) WARNING! Obey the instructions in chapter Safety instructions. If you ignore them, injury or death, or damage to the equipment can occur. 1. Stop the drive and do the steps in section Electrical safety precautions (page 20) before you start the work.
Maintenance 169 ■ Replacing the drive module main fans (frames R6…R8) WARNING! Obey the instructions in chapter Safety instructions. If you ignore them, injury or death, or damage to the equipment can occur. 1. Stop the drive and do the steps in section Electrical safety precautions (page 20) before you start the work.
170 Maintenance 5. Unplug the fan power supply wires from the drive. 6. Pull the fan mounting plate down from the side edge. 7. Unplug the fan power supply wires from the drive. 8. Lift the fan mounting plate off. 9.
Maintenance 171 ■ Replacing the drive module main fans (frames R10 and R11) WARNING! Obey the instructions in chapter Safety instructions. If you ignore them, injury or death, or damage to the equipment can occur. 1. Stop the drive and do the steps in section Electrical safety precautions (page 20) before you start the work.
172 Maintenance ■ Replacing the auxiliary cooling fan of the drive module (frames R6…R9) WARNING! Obey the instructions in chapter Safety instructions. If you ignore them, injury or death, or damage to the equipment can occur. 1. Stop the drive and do the steps in section Electrical safety precautions (page 20) before you start the work.
174 Maintenance ■ Replacing the circuit board compartment cooling fans (frames R10 and R11) WARNING! Obey the instructions in chapter Safety instructions. If you ignore them, injury or death, or damage to the equipment can occur. 1. Stop the drive and do the steps in section Electrical safety precautions (page 20) before you start the work.
Page 179
Maintenance 175 Handle the drive module carefully: • Use safety shoes with a metal toe cap to avoid foot injury. • Lift the drive module only by the lifting lugs. 1. Stop the drive and do the steps in section Electrical safety precautions (page 20) before you start the work.
Page 180
176 Maintenance Tap screw M6x16 T30 (hex) Torx M6x16 Torx M6x16 Torx M6x16 4. Unplug the wires connected to the mounting plate connectors (if present). 5. Remove the mounting plate (four screws). 6. Remove the shroud (two screws). 7. Remove the shroud on the power cable connection terminals.
Page 181
Maintenance 177 8. Disconnect the option modules from the control unit. 9. For drives with additional I/O terminal block (option +L504), disconnect the upper terminals and remove any fastening. Move the wires aside before you lift the module out. Note: Mark the wires for reconnection!
Page 182
178 Maintenance 10. For drives without additional I/O terminal block (option +L504), disconnect the customer-installed wires from the control unit. Note: Mark the wires for reconnection! 1 1. For drives with line contactor (option +F250), disconnect the input power cables from the output of the contactor.
Page 183
Maintenance 179 13. Secure the drive module with chains from the lifting eyes. 14. Undo the mounting screws of the flange. 15. Slide the drive module forwards along the sliding bars. 16. Lift the module out of the cabinet with a lifting device.
182 Maintenance Replacing the drive module (frames R10 and R11) WARNING! Obey the instructions in chapter Safety instructions. If you ignore them, injury or death, or damage to the equipment can occur. This replacing procedure requires: preferably two persons, extraction/installation ramp, a set of screw drivers and a torque wrench with an extension bar of 500 mm (20 in), chains for securing the module during the installation.
Page 187
Maintenance 183 6. Remove the mounting plate.
Page 188
184 Maintenance 7. Disconnect the drive module input busbars with a torque wrench withn an extension bar of 500 mm (20 in). Combi screw M12, 70 N·m (52 lbf·ft).
Page 190
186 Maintenance 9. Remove the shroud. Undo the screws that attach the drive module to the cabinet at the top and behind the front support legs.
Page 191
Maintenance 187 10. Attach the extraction ramp to the cabinet base with two screws. 1 1. Attach the drive module lifting lugs to the cabinet lifting lug with chains. 12. Pull the drive module carefully out of the cabinet preferably with help from another person.
188 Maintenance Replacing the drive module (frames R10 and R11, IP54 / UL Type 12) WARNING! Obey the instructions in chapter Safety instructions. If you ignore them, injury or death, or damage to the equipment can occur. This replacing procedure requires: preferably two persons, extraction/installation ramp, a set of screw drivers and a torque wrench with an extension bar of 500 mm (20 in), chains for securing the module during the installation.
Page 193
Maintenance 189 6. Remove the mounting plate.
Page 194
190 Maintenance 7. Disconnect the drive module input busbars with a torque wrench withn an extension bar of 500 mm (20 in). Combi screw M12, 70 N·m (52 lbf·ft).
Page 196
192 Maintenance 9. Remove the shroud. Undo the screws that attach the drive module to the cabinet at the top and behind the front support legs.
Page 197
Maintenance 193 10. Attach the extraction ramp to the cabinet base with two screws. 1 1. Attach the drive module lifting lugs to the cabinet lifting lug with chains.
Capacitor failure is usually followed by damage to the unit and an input cable fuse failure, or a fault trip. If you think that any capacitors in the drive have failed, contact ABB. ■...
Maintenance 195 1. Stop the drive and do the steps in section Electrical safety precautions (page 20) before you start the work. 2. Open the cabinet door. 3. Remove the shrouding from in front of the switch fuse. 4. Replace the fuses with the fuse handle which is in the cabinet. 5.
196 Maintenance • Mersen (Ferraz-Shawmut): 46 N·m (34 lbf·ft) if size 33; 26 N·m (19 lbf·ft) if size • Other fuses: Refer to the fuse manufacturer's instructions. 9. Reinstall the shrouding removed earlier and close the cabinet door. Control panel For detailed information on the control panel, see ACx-AP-x assistant control panels user’s manual (3AUA0000085685...
Technical data 197 Technical data Contents of this chapter This chapter contains the technical specifications of the drive, for example, the ratings, sizes and technical requirements, provisions for fulfilling the requirements for CE and other markings. Ratings ■ IEC ratings The nominal ratings for the drives with 50 Hz and 60 Hz supply are given below.
198 Technical data IEC RATINGS ACQ580- Frame Input Output ratings 07… size rating Nominal ratings Light-duty use Heavy-duty I max I Ld P Ld I Hd P Hd 0430A-4 363** 0505A-4 0585A-4 0650A-4 0725A-4 1020 0820A-4 1020 0880A-4 1100 725*** ■...
Note 2: To achieve the rated motor power given in the table, the rated current of the drive must be higher than or equal to the rated motor current. The DriveSize dimensioning tool available from ABB is recommended for selecting the drive, motor and gear combination.
200 Technical data 1.00 0.90 0.80 +40 °C +50 °C +104 °F +122 °F For example: Temperature Derated current 40 ºC (104 ºF) I Ld I Hd 45 ºC (113 ºF) 0.95 · I Ld 0.95 · I d 50 ºC (122 ºF) 0.90 ·...
Technical data 201 Frame Coeffficient 1000 m 2000 m 3000 m 4000 m 3281 ft 6562 9842 ft 13123 ft 1.00 0.90 0.80 0.70 1.00 0.90 0.80 0.70 1.00 0.90 0.80 0.70 If ambient temperature is below +40 °C (+104 .°F), the derating can be reduced by 1.5% for every 1 °C reduction in temperature.
202 Technical data Frame 1.5 kHz 2 kHz 4kHz 8 kHz size 1.00 0.98 0.89 0.71 1.00 0.96 0.82 0.61 1.00* 0.95* 0.79* 0.58* 1.00 0.92 0.78 0.58 1.00 0.92 0.78 0.58 1.00 0.92 0.78 0.58 1.00 0.92 0.78 0.58 * current derating for -0414A-4 and -0430A-4 at 35 C Note: Changing the value of parameter 97.01 Switching frequency reference does not require derating.
Page 207
Technical data 203 ACQ580- Input Ultrarapid (aR) fuses (one fuse per phase) 07… current A 2 s Type Type Size (Buss- (Mersen) mann) 0880A-4 1400 2450000 170M6417 B1046961F Notes: Fuses with a higher current rating than specified must not be used. Fuses from other manufacturers can be used if they meet the ratings and the melting curve of the fuse does not exceed the melting curve of the fuse mentioned in the table.
204 Technical data Fuses (UL) The drive with option +C129 and option +F289 is equipped with standard fuses listed below for internal circuit protection. The fuses restrict drive damage and prevent damage to adjoining equipment in case of a short-circuit inside the drive. The drive also requires external fuses for branch circuit protection per NEC, see section Fuses for branch circuit protection (page...
Technical data 205 Fuses for branch circuit protection The drive is suitable for use on a circuit capable of delivering not more than 100,000 rms symmetrical amperes at 480 V maximum when the input cable is protected with UL class T or L fuses. The fuses for branch circuit protection per NEC must be selected according to the table below.
Technical data 207 R6, R7: 400 mm (15.75”) in) R8, R9: 500 mm (19.68 in) R10. R11: 800 mm (31.50 in) Maximum allowed plinth height for the extraction/installation ramp The maximum plinth height for the extraction/installation ramp delivered with the drive is 50 mm (1.97 in).
208 Technical data IEC 1) US 2) ACQ580- Frame size 07… Cu cable type Al cable type Cu cable type mm 2 mm 2 AWG/kcmil per phase 0880A-4 3×(3×240) 4×(3×240) 3×600 MCM or 4×400 U n = 480 V 0124A-4 3×95 3×120 0156A-4...
212 Technical data Connection drawings Note: With a combination of bottom and top entry and exit options, look the connection points from the bottom entry and exit and top entry and exit drawings. Frame R6: Input and motor cable terminal dimensions (bottom entry and exit, switch fuse OS250) DET A...
Page 217
Technical data 213 Frame R6: Input and motor cable terminal dimensions (bottom entry and exit, switch fuse OS400) DET A...
Page 218
214 Technical data Frame R6: Input and motor cable terminal dimensions (option +F289) DET A...
Page 219
Technical data 215 Frames R6 and R7: Input and motor cable terminal dimensions (bottom entry and exit, switch fuse OS250, du/dt filter [option +E205])
Page 220
216 Technical data Frames R6 and R7: Input and motor cable terminal dimensions (bottom entry and exit, switch fuse OS400, du/dt filter [option +E205])
Page 221
Technical data 217 Frames R6 and R7: Input and motor cable terminal dimensions (bottom entry and exit, options +F289 and +E205)
Page 222
218 Technical data Frame R7: Input and motor cable terminal dimensions (bottom entry and exit, switch fuse OS250) DET A...
Page 223
Technical data 219 Frame R7: Input and motor cable terminal dimensions (bottom entry and exit, switch fuse OS400) DET A...
Page 224
220 Technical data Frame R7: Input and motor cable terminal dimensions (bottom entry and exit, option +F289)
Page 225
Technical data 221 Frames R6 and R7: Input and motor cable terminal dimensions (top entry and exit, options +H351 and +H353)
Page 226
222 Technical data Frame R8: Input and motor cable terminal dimensions (bottom entry and exit, switch-disconnector OT400) DET A...
Page 227
Technical data 223 Frame R8: Input and motor cable terminal dimensions (bottom entry and exit, switch-disconnector OT400, du/dt filter [option +E205])
Page 228
224 Technical data Frame R8: Input and motor cable terminal dimensions (bottom entry and exit, option +F289)
Page 229
Technical data 225 Frame R9: Input and motor cable terminal dimensions (bottom entry and exit, switch-disconnector OT630) DET A...
Page 230
226 Technical data Frame R9: Input and motor cable terminal dimensions (bottom entry and exit, switch-disconnector OT630, du/dt filter [option +E205])
Page 231
Technical data 227 Frames R8 and R9: Input and motor cable terminal dimensions (top entry and exit, options +H351 and +H353)
Page 232
228 Technical data Frames R8 and R9: Input and motor cable terminal dimensions (bottom entry and exit, options +F289 and +E205)
Page 233
Technical data 229 Frame R9: Input and motor cable terminal dimensions (option +F289)
Page 234
230 Technical data Frame R10: Input and motor cable terminal dimensions (bottom entry and exit) C''-1 276 [ 10,86"] 190 [ 7,48"] 103 [ 4,05"] [ 13,54"] L 1, L2, L [ 0,51"] V2, W2 3LILI 0 1- 3 L1 L2 86 [3 ,38"] -tj- [ 7,16"]...
Page 235
Technical data 231 Frame R10: Input and motor cable terminal dimensions (bottom entry and exit, option +E205) [10,86"] [13,55"] [7,48"] [0,51"] _ 190 [4,05"] � � [4,25"] [1,65"] L1 L2 [1,65"] I I I s;;1- s;;1- [2,44"] [7,75"] [0,51"] U2, V2, W2 o [13,07"] s;;j...
Page 236
232 Technical data Frame R10: Input and motor cable terminal dimensions (top entry and exit) [6,50"] [1,65"] L 1, L2, L3 L2 L3 � [0,51"] ¢13 [4,68"] [8,07"] J._UJ__ [12,51"] [1,73"] [1,33"] , 4 4, [5,90"] [9,68"] [13,42"] [0,51"] [5,51"] [0,51"] [0,51"] ¢13...
Page 237
Technical data 233 Frame R10: Input and motor cable terminal dimensions (top entry and exit, option +F289) [10,86"] ,48"] [13,54"] [4,05"] � L2, L U2, V2, W2 � [0,51"] (b13 L1 L2 L3 � [3,38"] [7,16"] � [1,65"] [0,51"] sf� [10,86"] ""------¢13 [1,65"]...
238 Technical data Terminal and connection data for auxiliary control circuits Maximum acceptable voltage and current values and wire sizes in terminal blocks are given below. Terminal block Maximum acceptable voltage and current values and wire sizes X250 230V AC / 24V DC, 2A •...
Technical data 239 Electrical power network specification Voltage (U 1 ) ACQ580-07-xxxxx-4 drives: 380…480 VAC 3-phase ±10%. This is indic- ated in the type designation label as typical input voltage levels 3~400/480 V AC. Network type TN (grounded) and IT (ungrounded) systems...
240 Technical data Control unit connection data See chapter Control unit (page 139). Efficiency Approximately 98% at nominal power level Protection classes Degrees of protection IP21 (standard), IP42 (option +B054), IP54 (option +B055) (IEC/EN 60529) Enclosure types UL Type 1 (standard), UL Type 1 (option +B054), UL Type 12 (option (UL50) +B055).
Installation site alti- 0 to 2000 m (6561 ft) tude above sea level. For altitudes over 2000 m, contact ABB. Output derated above 1000 m (3281 ft). See section Output derating Air temperature -0 to +50 °C (32 to 122 -40 to +70 °C (-40 to...
242 Technical data Shock Not allowed With packing max. 100 With packing max. 100 IEC 60068-2-27:2008, m/s2 (330 ft./s2), 11 m/s2 (330 ft./s2), 11 EN 60068-2-27:2009 Environmental testing - Part 2-27: Tests - Test Ea and guidance: Shock Auxiliary circuit power consumption Cabinet heater (option 100 W +G300)
Technical data 243 Seaworthy package Timber, plywood, VCI sheet film (PE, thickness 0.10 mm), VCI stretch (option +P912) film (PE, thickness 0.04 mm), VCI emitter bags, PP tape, PET strap, sheet metal (steel). For sea transport with or without containerization. For long storage periods in environments where roofed and humidity- controlled storage cannot be arranged.
244 Technical data Frame Height Width Depth Stand- Material Container size ard/Option type R10, R11 2550 1150 1100 Standard Plastic and At least 40HC 4 wood R10, R11 2550 1430 1100 +P912, Plywood At least 40HC 5 +P929 Plywood over the nor- mal pack- aging.
Technical data 245 Frame Standard +P912, +P929 size Applicable standards The drive complies with the standards below. The compliance with the European Low Voltage Directive is verified according to standard EN 61800-5-1. EN 61800-5-1:2007 Adjustable speed electrical power drive systems. Part 5-1: Safety require- ments –...
246 Technical data Markings CE mark Product complies with the applicable European Union legislation. For fulfilling the EMC requirements, see the additional information concerning the drive EMC compliance (IEC/EN 61800-3). TÜV Safety Approved mark (functional safety) Product contains Safe Torque Off and possibly other (optional) safety functions which are certified by TÜV according to the relevant functional safety standards.
Technical data 247 ■ Compliance with the European EMC Directive The EMC Directive defines the requirements for immunity and emissions of electrical equipment used within the European Union. The EMC product standard (EN 61800-3:2004) covers requirements stated for drives. See section Compliance with the EN 61800-3:2004 below.
248 Technical data ■ Compliance with the EN 61800-3:2004 Definitions EMC stands for Electromagnetic Compatibility. It is the ability of electrical/electronic equipment to operate without problems within an electromagnetic environment. Likewise, the equipment must not disturb or interfere with any other product or system within its locality.
Technical data 249 WARNING! A drive of category C3 is not intended to be used on a low-voltage public network which supplies domestic premises. Radio frequency interference is expected if the drive is used on such a network. Category C4 The drive complies with the C4 category with these provisions: 1.
250 Technical data WARNING! A drive of category C4 is not intended to be used on a low-voltage public network which supplies domestic premises. Radio frequency interference is expected if the drive is used on such a network. UL marking The drive is cULus listed with option +C129.
Technical data 251 WARNING! The opening of the branch-circuit protective device may be an indication that a fault current has been interrupted. To reduce the risk of fire or electric shock, current-carrying parts and other components of the device should be examined and replaced if damaged.
ABB and its affiliates are not liable for damages and/or losses related to such security breaches, any unauthorized access, interference, intrusion, leakage and/or...
The Safe torque off function 273 The Safe torque off function Contents of this chapter This chapter describes the Safe torque off (STO) function of the drive and gives instructions for its use. Description The Safe torque off function can be used, for example, as the final actuator device of safety circuits that stop the drive in case of danger (such as an emergency stop circuit).
274 The Safe torque off function Standard Name IEC 61000-6-7:2014 Electromagnetic compatibility (EMC) – Part 6-7: Generic stand- ards – Immunity requirements for equipment intended to perform functions in a safety-related system (functional safety) in indus- trial locations IEC 61326-3-1:2017 Electrical equipment for measurement, control and laboratory use –...
The Safe torque off function 275 Wiring For the electrical specifications of the STO connection, see the technical data of the control unit. ■ Connection principle Single ACQ580-07 drive, internal power supply OUT1 + 24 V DC OUT2 + 24 V DC SGND...
276 The Safe torque off function Single ACQ580-07 drive, external power supply 24 V DC OUT1 + 24 V DC OUT2 + 24 V DC SGND UDC+ UDC- Drive Control unit Control logic To motor Activation switch ■ Wiring examples...
278 The Safe torque off function Multiple ACQ580-07 drives, internal power supply OUT1 + 24 V DC OUT2 + 24 V DC SGND OUT1 OUT2 SGND OUT1 OUT2 SGND Drive Control unit Activation switch...
The Safe torque off function 279 Multiple ACQ580-07 drives, external power supply 24 V DC – OUT1 + 24 V DC OUT2 + 24 V DC SGND OUT1 OUT2 SGND OUT1 OUT2 SGND Drive Control unit Activation switch...
280 The Safe torque off function ■ Activation switch In the wiring diagrams, the activation switch has the designation [K]. This represents a component such as a manually operated switch, an emergency stop push button switch, or the contacts of a safety relay or safety PLC. •...
The Safe torque off function 281 Operation principle 1. The Safe torque off activates (the activation switch is opened, or safety relay contacts open). 2. The STO inputs of the drive control unit de-energize. 3. The control unit cuts off the control voltage from the output IGBTs. 4.
282 The Safe torque off function Start-up including acceptance test To ensure the safe operation of a safety function, validation is required. The final assembler of the machine must validate the function by performing an acceptance test. The acceptance test must be performed •...
Page 287
The Safe torque off function 283 Action Test the operation of the STO function when the motor is stopped. • Give a stop command for the drive (if running) and wait until the motor shaft is at a standstill. Make sure that the drive operates as follows: •...
284 The Safe torque off function 1. Open the activation switch, or activate the safety functionality that is wired to the STO connection. 2. The STO inputs on the drive control unit de-energize, and the control unit cuts off the control voltage from the output IGBTs. 3.
Page 289
The Safe torque off function 285 or is not otherwise acceptable, stop the drive and machinery using the appropriate stop mode before activating the Safe torque off function. • The Safe torque off function overrides all other functions of the drive. •...
If any wiring or component change is needed after start up, or the parameters are restored, do the test given in section Acceptance test procedure (page 282). Use only spare parts approved by ABB. Record all maintenance and proof test activities in the machine logbook. ■ Competence...
See the firmware manual of the drive control program for the indications generated by the drive, and for details on directing fault and warning indications to an output on the control unit for external diagnostics. Any failures of the Safe torque off function must be reported to ABB.
288 The Safe torque off function Safety data The safety data for the Safe torque off function is given below. Note: The safety data is calculated for redundant use, and does not apply if both STO channels are not used. PFD avg PFD avg Frame...
The Safe torque off function 289 • STO fault indication (parameter 31.22) delay: < 500 ms • STO warning indication (parameter 31.22) delay: < 1000 ms ■ Abbreviations Abbr. Reference Description Cat. EN ISO 13849-1 Classification of the safety-related parts of a control system in respect of their resistance to faults and their subsequent behavior in the fault condition, and which is achieved by the structural arrangement of the parts, fault detection and/or by...
After the mission time elapses, the safety device must be replaced. Note that any T M values given cannot be regarded as a guarantee or warranty. ■ TÜV certificate The TÜV certificate is available on the Internet at www.abb.com/drives/documents.
CHDI-01 115/230 V digital input extension module 293 CHDI-01 115/230 V digital input extension module Contents of this chapter This chapter describes the optional CHDI-01 115/230 V digital input extension module. Product overview The CHDI-01 115/230 V digital input extension module expands the inputs of the drive control unit.
294 CHDI-01 115/230 V digital input extension module Layout and connection examples 3-pin terminal blocks for 115/230 V in- Relay outputs puts RO4C 115/230 V AC HDI7 RO4A HDI8 24 V DC RO4B NEUTRAL HDI7 115/230 V input 1 RO4C Common, C HDI8 115/230 V input 2...
CHDI-01 115/230 V digital input extension module 295 Mechanical installation ■ Necessary tools • Screwdriver and a set of suitable bits. ■ Unpacking and examining the delivery 1. Open the option package. Make sure that the package contains: • the option module •...
296 CHDI-01 115/230 V digital input extension module • make sure that the value of both parameters 15.01 Extension module type and 15.02 Detected extension module is CHDI-01. If warning A7AB Extension I/O configuration failure is shown, • make sure that the value of parameter 15.02 is CHDI-01. •...
CHDI-01 115/230 V digital input extension module 297 CHDI-01 Plugged to drive SLOT2 Reinforced insulation (IEC 61800-5-1:2007) Functional insulation (IEC 61800-5-1:2007) Dimension drawing The dimensions are in millimeters and [inches].
CMOD-01 multifunction extension module (external 24 V AC/DC and digital I/O) 299 CMOD-01 multifunction extension module (external 24 V AC/DC and digital I/O) Contents of this chapter This chapter describes the optional CMOD-01 multifunction extension module (external 24 V AC/DC and digital I/O). Product overview The CMOD-01 multifunction extension module (external 24 V AC/DC and digital I/O) expands the outputs of the drive control unit.
300 CMOD-01 multifunction extension module (external 24 V AC/DC and digital I/O) Layout and example connections Grounding screw Diagnostic LED Hole for mounting screw 2-pin terminal block for external power sup- 3-pin terminal blocks for relay out- puts RO4C 24V AC/DC + in RO4A 24 V DC 24 V AC/DC...
CMOD-01 multifunction extension module (external 24 V AC/DC and digital I/O) 301 DO1 SGND Ground (earth) potential RO5B Normally open, NO 1) Digital output connection example 2) An externally supplied frequency indicator which provides, for example: • a 40 mA / 12 V DC power supply for the sensor circuit (CMOD frequency output) •...
302 CMOD-01 multifunction extension module (external 24 V AC/DC and digital I/O) WARNING! Do not connect the +24 V AC cable to the control unit ground when the control unit is powered using an external 24 V AC supply. Start-up ■...
CMOD-01 multifunction extension module (external 24 V AC/DC and digital I/O) 303 Parameter Setting 15.25 DO1 OFF delay Parameter setting example for frequency output This example shows how to make digital output DO1 of the extension module indicate the motor speed 0... 1500 rpm with a frequency range of 0...10000 Hz. Parameter Setting 15.22 DO1 configuration...
304 CMOD-01 multifunction extension module (external 24 V AC/DC and digital I/O) Transistor output (42…44) 1.5 mm 2 Maximum wire size Type Transistor output PNP Maximum load 4 kohm Maximum switching 30 V DC voltage Maximum switching 100 mA / 30 V DC, short-circuit protected current Frequency 10 Hz …...
Page 309
CMOD-01 multifunction extension module (external 24 V AC/DC and digital I/O) 305...
CMOD-02 multifunction extension module (external 24 V AC/DC and isolated PTC interface) 307 CMOD-02 multifunction extension module (external 24 V AC/DC and isolated PTC interface) Contents of this chapter This chapter describes the optional CMOD-02 multifunction extension module (external 24 V AC/DC and isolated PTC interface). Product overview The CMOD-02 multifunction extension module (external 24 V AC/DC and isolated PTC interface) has a motor thermistor connection for supervising the motor temperature and...
308 CMOD-02 multifunction extension module (external 24 V AC/DC and isolated PTC interface) There is reinforced insulation between the motor thermistor connection, the relay output and the drive control unit interface. Thus, you can connect a motor thermistor to the drive through the extension module.
CMOD-02 multifunction extension module (external 24 V AC/DC and isolated PTC interface) 309 Motor thermistor connection Grounding screw PTC IN PTC IN One to six PTC thermistors connected in series. PTC IN PTC connection Hole for mounting screw PTC IN Ground (earth) potential Diagnostic LED Mechanical installation...
310 CMOD-02 multifunction extension module (external 24 V AC/DC and isolated PTC interface) ■ Wiring Connect the external control cables to the applicable module terminals. Ground the outer shield of the cables 360 degrees under a grounding clamp on the grounding shelf of the control cables.
Disconnecting EMC filter and ground-to-phase varistor 313 Disconnecting EMC filter and ground-to-phase varistor When to disconnect the ground-to-phase varistor: TN-S, IT, corner-grounded delta and midpoint-grounded delta systems Frame Symmetrically grounded Corner-grounded (B1) and IT systems (ungrounded size TN systems (TN-S sys- midpoint-grounded delta or high-resistance groun- tems), ie.
Page 318
314 Disconnecting EMC filter and ground-to-phase varistor Frame Symmetrically grounded Corner-grounded (B1) and IT systems (ungrounded size TN systems (TN-S sys- midpoint-grounded delta or high-resistance groun- tems), ie. center-grounded (B2) systems ded [>30 ohms]) (C) wye (A) Drive Drive Drive Drive These are the EMC filter and varistor screws in different drive frame sizes.
R6...R9 Two EMC screws R10, Drive Note: • Because the varistor wire has been disconnected, ABB does not guarantee the EMC category. • ABB does not guarantee the functioning of the ground leakage detector built inside the drive. • In large systems the residual current device can trip without a real reason.
Page 320
316 Disconnecting EMC filter and ground-to-phase varistor voltages at the distribution board, and use the table to define the grounding system type. 1. input voltage line to line (U 2. input voltage line 1 to ground (U L1-G 3. input voltage line 2 to ground (U L2-G 4.
Disconnecting EMC filter and ground-to-phase varistor 317 Disconnecting the EMC filter and ground-to-phase varistor (frames R6…R9) To disconnect the internal EMC filter or ground-to-phase varistor, do as follows: 1. Switch off the power from the drive. 2. Open the cover, if not already opened. 3.
Product and service inquiries Address any inquiries about the product to your local ABB representative, quoting the type designation and serial number of the unit in question. A listing of ABB sales, support and service contacts can be found by navigating to www.abb.com/searchchannels.