204 Fault tracing
Warning / Aux. code
(aux code visible only
Code
on assistant control
(hex)
panel and drive
composer)
A6A5
No motor data
A6A6
Voltage category
unselected
A6A7
System time not set
A6B0
User lock is open
A6B1
User pass code not
confirmed
A6D1
FBA A parameter
conflict
A6E5
AI parametrization
A780
Motor stall
(Programmable
warning:
31.24 Stall
function)
Cause
1 Slip frequency is too small.
2 Synchronous and nominal
speeds differ too much.
3 Nominal speed is higher than
synchronous speed with 1 pole
pair.
4 Nominal current is outside
limits
5 Nominal voltage is outside
limits.
6 Nominal power is higher than
apparent power.
7 Nominal power not consistent
with nominal speed and
torque.
Parameters in group 99 have
not been set.
The voltage category has not
been defined.
System time is not set.
The user lock is open, ie. user
lock configuration parameters
96.100...96.102
are visible.
A new user pass code has
been entered in parameter
96.100
but not confirmed in
96.101.
The drive does not have a
functionality requested by a
PLC, or requested functionality
has not been activated.
The current/voltage hardware
setting of an analog input does
not correspond to parameter
settings.
Motor is operating in stall
region.
What to do
Check the settings of the motor
configuration parameters in groups 98
and 99.
Check that the drive is sized correctly for
the motor.
Check that all the required parameters in
group 99 have been set.
Note: It is normal for this warning to
appear during the start-up and continue
until the motor data is entered.
Set voltage category in parameter
Supply
voltage.
Close the user lock by entering an invalid
pass code in parameter
code. See section
User lock
Confirm the new pass code by entering
the same code in 96.101. To cancel,
close the user lock without confirming the
new code. See section
User lock
52).
Check PLC programming.
Check settings of parameter groups
Fieldbus adapter
(FBA).
Check the event log for an auxiliary code.
The code identifies the analog input
whose settings are in conflict.
Adjust either the hardware setting (on the
drive control unit) or parameter
12.15/12.25.
Note: Control board reboot (either by
cycling the power or through parameter
96.08 Control board
boot) is required to
validate any changes in the hardware
settings.
Check motor load, drive ratings and fault
function parameters.
95.01
96.02 Pass
(page 52).
(page
50