ABB ACQ80-04 Firmware Manual page 232

Drives for water, standard control program
Hide thumbs Also See for ACQ80-04:
Table of Contents

Advertisement

232 Fieldbus control through the embedded fieldbus interface (EFB)
Bit
Name
2
REVERSE
3
Reserved
4
RESET
5
EXT2
6
RUN_DISABLE
7
STOPMODE_RA
MP
8
STOPMODE_EM
ERGENCY_RAM
P
9
STOPMODE_CO
AST
10
RAMP_PAIR _2
11
RAMP_OUT_ZER
O
12
RAMP_HOLD
13
RAMP_IN_ZERO
14
REQ_LOCAL_LO
CK
Value
State/Description
1
Reverse direction of motor rotation. See in the table
below how this bit and sign of the reference effect the
direction of the motor direction.
Bit REVERSE = 0
Bit REVERSE = 1
0
(no op)
0=>1
Fault reset if an active fault exists.
0
(no op)
1
Select External control location EXT2. Effective if the
control location is parameterized to be selected from the
fieldbus.
0
Select External control location EXT1. Effective if the
control location is parameterized to be selected from the
fieldbus.
1
Run disable. If the drive is set to receive the run enable
signal from the fieldbus, this bit deactivates the signal.
0
Run enable. If the drive is set to receive the run enable
signal from the fieldbus, this bit activates the signal.
1
Normal ramp stop mode
0
(no op) Default to parameter stop mode if bits 7...9 are all
0.
1
Emergency ramp stop mode.
0
(no op) Default to parameter stop mode if bits 7...9 are all
0.
1
Coast stop mode.
0
(no op) Default to parameter stop mode if bits 7...9 are all
0.
1
Not applicable.
0
Not applicable.
1
Force Ramp Function Generator output to zero. Drive
ramps to stop (current and DC voltage limits in force).
0
Normal operation.
1
Halt ramping (Ramp Function Generator output held).
0
Normal operation.
1
Force Ramp Function Generator input to zero.
0
Normal operation.
1
Drive does not switch to local control mode
0
Drive can switch between local and remote control
modes.
Sign of the reference
Positive (+)
Negative (-)
Forward
Reverse
Reverse
Forward