No.
Name/Value
10.04
DI forced data
Bit
Value
0
Force the value of this bit to D1, if so defined in parameter
1
Force the value of this bit to D3, if so defined in parameter
2
Force the value of this bit to D3, if so defined in parameter
3
Force the value of this bit to D4, if so defined in parameter
4
Force the value of this bit to D5, if so defined in parameter
5
Force the value of this bit to D6, if so defined in parameter
6...15
Reserved
0b0000...0b1111
10.21
RO status
Bit
Value
0
1 = RO1 is energized.
1
1 = RO2 is energized.
2
1 = RO3 is energized.
3...15
Reserved
0b0000...0b1111
10.22
RO force selection
Bit
Value
0
1 = Force RO1 to value of bit 0 of parameter
1
1 = Force RO2 to value of bit 1 of parameter
2
1 = Force RO3 to value of bit 2 of parameter
3...15
Reserved
0b0000...0b1111
10.23
RO forced data
Bit
Value
0
Force the value of this bit to RO1, if so defined in parameter
1
Force the value of this bit to RO2, if so defined in parameter
2
Force the value of this bit to RO3, if so defined in parameter
3...15
Reserved
0b0000...0b1111
Description
Allows the data value of a forced digital input to be changed
from 0 to 1. It is only possible to force an input that has been
selected in parameter
10.03 DI force
Bit 0 is the forced value for DI1; bit 5 is the forced value for
the DI6.
Forced values of digital inputs.
Status of relay outputs RO1...RO3.
Status of relay outputs.
The signals connected to the relay outputs can be overridden
for eg. testing purposes. A bit in parameter
data
is provided for each relay output, and its value is applied
whenever the corresponding bit in this parameter is 1.
Note: Boot and power cycle reset the force selections
(parameters
10.22
and 10.23).
Override selection for relay outputs.
Contains the values of relay outputs that are used instead of
the connected signals if selected in parameter
force
selection. Bit 0 is the forced value for RO1.
Forced RO values.
selection.
10.03 DI force
10.03 DI force
10.03 DI force
10.03 DI force
10.03 DI force
10.03 DI force
10.23 RO forced
10.23 RO forced
data. (0 = Normal mode)
10.23 RO forced
data. (0 = Normal mode)
10.23 RO forced
data. (0 = Normal mode)
10.22 RO
10.22 RO force
10.22 RO force
10.22 RO force
Parameters 79
Def/FbEq16
0b0000
selection.
selection.
selection.
selection.
selection.
selection.
1 = 1
0b0000
1 = 1
0b0000
1 = 1
0b0000
selection.
selection.
selection.
1 = 1