ABB ACQ80-04 Firmware Manual page 137

Drives for water, standard control program
Hide thumbs Also See for ACQ80-04:
Table of Contents

Advertisement

No.
Name/Value
40.47
Set 1 wake-up
deviation
-200000.00...2000
00.00
40.48
Set 1 wake-up
delay
0.00...60.00 s
40.49
Set 1 tracking mode
Not selected
Selected
DI1
DI2
DI3
DI4
DI5
DI6
Supervision 1
Supervision 2
Supervision 3
Other [bit]
40.50
Set 1 tracking ref
selection
Not selected
AI1 scaled
AI2 scaled
FB A ref1
FB A ref2
Other
40.58
Set 1 increase
prevention
No
Limiting
Other [bit]
Description
Defines the wake-up level as deviation between process
setpoint and feedback.
When the deviation exceeds the value of this parameter, and
remains there for the duration of the wake-up delay
Set 1 wake-up
delay), the drive wakes up.
See also parameter
40.31 Set 1 deviation
Wake-up level (as deviation between process setpoint and
feedback).
Defines a wake-up delay for the sleep function to prevent
nuisance wake-ups. See parameter
deviation.
The delay timer starts when the deviation exceeds the wake-
up level
(40.47 Set 1 wake-up
deviation falls below the wake-up level.
Wake-up delay.
Activates (or selects a source that activates) tracking mode.
In tracking mode, the value selected by parameter
1 tracking ref selection
is substituted for the PID controller
output. See also section
1 = Tracking mode enabled
0.
1.
Digital input DI1
(10.02 DI delayed
Digital input DI2
(10.02 DI delayed
Digital input DI3
(10.02 DI delayed
Digital input DI4
(10.02 DI delayed
Digital input DI5
(10.02 DI delayed
Digital input DI6
(10.02 DI delayed
Bit 0 of
32.01 Supervision status
Bit 1 of
32.01 Supervision status
Bit 2 of
32.01 Supervision status
Source selection (see
Terms and abbreviations
Selects the value source for tracking mode. See parameter
40.49 Set 1 tracking
mode.
None.
12.12 AI1 scaled value
(see page 85).
12.22 AI2 scaled value
(see page 86).
03.05 FB A reference 1
03.06 FB A reference 2
Source selection (see
Terms and abbreviations
Prevention of PID integration term increase for PID set 1.
Increase prevention not in use.
The PID integration term is not increased if the maximum
value for the PID output is reached. This parameter is valid
for the PID set 1.
Source selection (see
Terms and abbreviations
inversion.
40.47 Set 1 wake-up
deviation), and resets if the
Tracking
(page 40).
status, bit 0).
status, bit 1).
status, bit 2).
status, bit 3).
status, bit 4).
status, bit 5).
(see page 114).
(see page 114).
(see page 114).
(see page 70).
(see page 70).
Parameters 137
Def/FbEq16
0.00
(40.48
1 = 1
0.50
1 = 1
Not selected
40.50 Set
0
1
2
3
4
5
6
7
21
22
23
on page 64).
-
Not selected
0
1
2
3
4
on page 64).
-
No
0
1
on page 64).
-