86 Parameters
No.
Name/Value
12.18
AI1 max
0.000...11.000 V
12.19
AI1 scaled at AI1
min
-32768.000...
32767.000
12.20
AI1 scaled at AI1
max
-32768.000...
32767.000
12.21
AI2 actual value
0.000...22.000 mA
12.22
AI2 scaled value
-32768.000...
32767.000
12.23
AI2 forced value
0.000...22.000 mA
Description
Defines the maximum site value for analog input AI1.
Set the value actually sent to the drive when the analog signal
from plant is wound to its maximum setting.
See also parameter
12.19 AI1 scaled at AI1
Maximum value of AI1.
Defines the real internal value that corresponds to the
minimum analog input AI1 value defined by parameter
AI1
min. (Changing the polarity settings of
can effectively invert the analog input.)
AI
scaled
12.20
12.17
Real value corresponding to minimum AI1 value.
Defines the real internal value that corresponds to the
maximum analog input AI1 value defined by parameter
AI1
max. See the drawing at parameter
AI1
min.
Real value corresponding to maximum AI1 value.
Shows value of analog input AI2 in mA or V (depending on
whether the input is set to current or voltage by a hardware
setting).
This parameter is read-only.
Value of analog input AI2.
Shows value of analog input AI2 after scaling. See
parameters
12.29 AI2 scaled at AI2 min
percent
value.
This parameter is read-only.
Scaled value of analog input AI2.
Forced value that can be used instead of the true reading of
the input. See parameter
Forced value of analog input AI2.
min.
12.19
and
(12.12)
12.18
12.19
12.19 AI1 scaled at
and
12.101 AI1
12.02 AI force
selection.
Def/FbEq16
10.000
1000 = 1
0.000
12.17
12.20
AI
(12.11)
in
1 = 1
50.000
12.18
1 = 1
-
1000 = 1 unit
0.000
1 = 1
0.000
1000 = 1 unit