ABB ACQ80-04 Firmware Manual page 85

Drives for water, standard control program
Hide thumbs Also See for ACQ80-04:
Table of Contents

Advertisement

No.
Name/Value
12.12
AI1 scaled value
-32768.000...
32767.000
12.13
AI1 forced value
0.000...11.000 V
12.15
AI1 unit selection
V
mA
12.16
AI1 filter time
0.000...30.000 s
12.17
AI1 min
0.000...11.000 V
Description
Shows value of analog input AI1 after scaling. See
parameters
12.19 AI1 scaled at AI1 min
at AI1
max.
This parameter is read-only.
Scaled value of analog input AI1.
Forced value that can be used instead of the true reading of
the input. See parameter
Forced value of analog input AI1.
Selects the unit for readings and settings related to analog
input AI1.
Note: In firmware ASCL2 and ASCL4), this setting must
match the corresponding hardware setting on the drive
control unit. See chapter Electrical installation, section
Switches in the Hardware manual of the drive and the default
control connections for the macro in use in chapter
macros
(page 55). Control board reboot (either by cycling the
power or through parameter
required to validate any changes in the hardware settings.
Volts.
Milliamperes.
Defines the filter time constant for analog input AI1.
%
Unfiltered signal
100
63
Filtered signal
T
-t/T
O = I × (1 - e
I = filter input (step)
O = filter output
t = time
T = filter time constant
Note: The signal is also filtered due to the signal interface
hardware (approximately 0.25 ms time constant). This cannot
be changed by any parameter.
Filter time constant.
Defines the minimum site value for analog input AI1.
Set the value actually sent to the drive when the analog signal
from plant is wound to its minimum setting.
See also parameter
12.19 AI1 scaled at AI1
Minimum value of AI1.
and
12.20 AI1 scaled
12.02 AI force
selection.
96.08 Control board
t
)
min.
Parameters 85
Def/FbEq16
50.000
1 = 1
0
1000 = 1 unit
V
Control
boot) is
2
10
0.100 s
1000 = 1
0.000
1000 = 1