254 Fieldbus control through a fieldbus adapter
Bit
Name
5
Ramp hold
6
Ramp in zero
7
Reset
8
Inching 1
8
Reserved
9
Inching 2
9
Reserved
10
Remote cmd
11
Ext ctrl loc
12
User bit 0
13
User bit 1
14
User bit 2
15
User bit 3
Value STATE/Description
1
ramp function.
Proceed to RAMP FUNCTION GENERATOR: ACCELERATOR D.
0
Halt ramping (Ramp Function Generator output held).
1
Normal operation. Proceed to OPERATING.
Note: This bit is effective only if the fieldbus interface is set as the
source for this signal by drive parameters.
0
Force Ramp function generator input to zero.
0=>1
Fault reset if an active fault exists. Proceed to SWITCH-ON
INHIBITED.
Note: This bit is effective only if the fieldbus interface is set as the
source of the reset signal by drive parameters.
0
Continue normal operation.
1
Accelerate to inching (jogging) setpoint 1.
Notes:
• Bits 4...6 must be 0.
• See also section
and 97.02 Minimum switching frequency (page 162).
0
Inching (jogging) 1 disabled.
1
Accelerate to inching (jogging) setpoint 2.
See notes at bit 8.
0
Inching (jogging) 2 disabled.
1
Fieldbus control d.
0
Control word and reference not getting through to the drive, except
for bits 0...2.
1
Select External Control Location EXT2. Effective if control location is
parameterized to be selected from fieldbus.
0
Select External Control Location EXT1. Effective if control location is
parameterized to be selected from fieldbus.
1
User configurable
0
1
0
1
0
1
0
Parameter 97.01 Switching frequency reference
(page 44).