ABB ACQ80-04 Firmware Manual page 141

Drives for water, standard control program
Table of Contents

Advertisement

No.
Name/Value
46.06
Speed ref zero
scaling
0.00 ... 30000.00
rpm
46.07
Frequency ref zero
scaling
0.00 ... 1000.00 Hz
46.11
Filter time motor
speed
2...20000 ms
46.12
Filter time output
frequency
2...20000 ms
46.13
Filter time motor
torque
2...20000 ms
46.14
Filter time power
2...20000 ms
46.21
At speed hysteresis
0.00...30000.00
rpm
Description
Defines a speed corresponding to a zero reference received
from fieldbus (either the embedded fieldbus interface, or
interface FBA A). For example, with a setting of 500, the
fieldbus reference range of 0...20000 would correspond to a
speed of 500...[99.09] rpm.
Note: This parameter is effective only with the ABB Drives
communication profile.
Speed corresponding to minimum fieldbus reference.
Defines a frequency corresponding to a zero reference
received from fieldbus (either the embedded fieldbus
interface, or interface FBA A or FBA B). For example, with a
setting of 30, the fieldbus reference range of 0...20000 would
correspond to a speed of 30...[46.02] Hz.
Note: This parameter is effective only with the ABB Drives
communication profile.
Speed corresponding to minimum fieldbus reference.
Defines a filter time for signals
01.02 Motor speed
estimated.
Motor speed signal filter time.
Defines a filter time for signal
Output frequency signal filter time.
Defines a filter time for signal
Motor torque signal filter time.
Defines a filter time for signal
Output power signal filter time.
Defines the "at setpoint" limits for speed control of the drive.
When the difference between speed reference and the speed
feedback is smaller than
is considered to be "at setpoint". This is indicated by bit 8 of
06.11 Main status
word.
Drive at setpoint
(06.11
bit 8 = 1)
Limit for "at setpoint" indication in speed control.
01.01 Motor speed used
01.06 Output
frequency.
01.10 Motor
torque.
01.14 Output
power.
46.21 At speed
hysteresis, the drive
Speed feedback (rpm)
Speed reference +
Speed reference (rpm)
Speed reference -
0 rpm
Parameters 141
Def/FbEq16
0.00 rpm
1 = 1 rpm
0.00 Hz
10 = 1 Hz
and
500 ms
1 = 1 ms
500 ms
1 = 1 ms
100 ms
1 = 1 ms
100 ms
1 = 1 ms
50.00 rpm
46.21
(rpm)
46.21
(rpm)
1 = 1