212 Fault tracing
Fault / Aux. code
Code
code visible only on
(hex)
assistant control panel
and drive composer)
5089
SMT circuit
malfunction
5090
STO hardware failure
5091
Safe torque off
Programmable fault:
STO indication run/stop
5092
PU logic error
5093
Rating ID mismatch
5094
Measurement circuit
temperature
5095
Redundant
measurement
5096
Overtemperature hw
5098
I/O communication
loss
5681
PU communication
5682
Power unit lost
5690
PU communication
internal
5691
Measurement circuit
ADC
5692
PU board powerfail
5693
Measurement circuit
DFF
5695
Reduced run
(aux
Cause
Safe motor temperature fault is
generated and STO
event/fault/warning is not
generated.
0001 Auxiliary fan 1 broken.
0002 Auxiliary fan 2 broken.
STO hardware diagnostics has
detected hardware failure.
Safe torque off function is
active, ie. safety circuit
31.22
signal(s) connected to
connector STO is broken
during start or run.
Power unit memory has
cleared.
The hardware of the drive does
not match the information
stored in the memory. This
may occur eg. after a firmware
update.
Problem with internal
temperature measurement of
the drive.
Duplicated measurements are
beyond limits.
Excessive hardware
temperature.
Communication failure to
standard I/O.
Communication errors
detected between the drive
control unit and the power unit.
Connection between the drive
control unit and the power unit
is lost.
Internal communication error.
Measurement circuit fault.
Power unit power supply
failure.
Measurement circuit fault.
Configured power units not
found.
What to do
Check connection between the relay
output of the module and the STO
terminal.
Contact your local ABB representative for
hardware replacement.
Check safety circuit connections. For
more information, see chapter The Safe
torque off function in the Hardware
manual of the drive and description of
parameter
31.22 STO indication run/stop
(page 109).
Check the value of parameter
Control board
supply.
Contact your local ABB representative.
Cycle the power to the drive. You may
have to be repeat this.
Contact your local ABB representative.
Contact ABB.
Contact your local ABB representative.
Try resetting the fault or cycle the power
to the drive.
Check the connection between the drive
control unit and the power unit.
Check the value of parameter
Control board
supply.
Check the connection between the
control unit and the power unit.
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Configure the power units.
95.04