114 Parameters
No.
Name/Value
32

32 Supervision

32.01
Supervision status
Bit
Name
0
Supervision 1 active
1
Supervision 2 active
2
Supervision 3 active
3
Supervision 4 active
4
Supervision 5 active
5
Supervision 6 active
6...15
Reserved
0b0000...0b1111
32.05
Supervision 1
function
Disabled
Low
High
Abs low
Abs high
Both
Abs both
Hysteresis
32.06
Supervision 1
action
No action
Warning
Fault
Description
Configuration of signal supervision functions 1...6.
Six values can be chosen to be monitored; a warning or fault
is generated whenever predefined limits are exceeded.
See also section
Signal supervision
Signal supervision status word.
Indicates whether the values monitored by the signal
supervision functions are within or outside their respective
limits.
Note: This word is independent of the drive actions defined
by parameters 32.06, 32.16, 32.26, 32.36,
Description
1 = Signal selected by
1 = Signal selected by
1 = Signal selected by
1 = Signal selected by
1 = Signal selected by
1 = Signal selected by
Signal supervision status word.
Selects the mode of signal supervision function 1. Determines
how the monitored signal (see parameter 32.07) is compared
to its lower and upper limits
The action to be taken when the condition is fulfilled is
selected by 32.06.
Signal supervision 1 not in use.
Action is taken whenever the signal falls below its lower limit.
Action is taken whenever the signal rises above its upper
limit.
Action is taken whenever the absolute value of the signal falls
below its (absolute) lower limit.
Action is taken whenever the absolute value of the signal
rises above its (absolute) upper limit.
Action is taken whenever the signal falls below its low limit or
rises above its high limit.
Action is taken whenever the absolute value of the signal falls
below its (absolute) low limit or rises above its (absolute) high
limit.
Action is taken whenever the signal falls below its (hysteresis)
low limit or rises above its (hysteresis) high limit.
Selects whether the drive generates a fault, warning or
neither when the value monitored by signal supervision 1
exceeds its limits.
Note: This parameter does not affect the status indicated by
32.01 Supervision
status.
No warning or fault generated.
Warning
A8B0 Signal supervision 1
Drive trips on fault
80B0 Signal supervision
(page 49).
32.46
and 32.56.
32.07
is outside its limits.
32.17
is outside its limits.
32.27
is outside its limits.
32.37
is outside its limits.
32.47
is outside its limits.
32.27
is outside its limits.
(32.09
and
32.10
respectively).
is generated.
1.
Def/FbEq16
0b000
1 = 1
Disabled
0
1
2
3
4
5
6
7
No action
0
1
2