ABB ACQ80-04 Firmware Manual page 115

Drives for water, standard control program
Hide thumbs Also See for ACQ80-04:
Table of Contents

Advertisement

No.
Name/Value
Fault if running
32.07
Supervision 1
signal
Zero
Speed
Frequency
Current
Torque
DC voltage
Output power
AI1
AI2
Freq ref used
Inverter
temperature
Process PID output
Process PID
feedback
Process PID
setpoint
Process PID
deviation
Other
32.08
Supervision 1 filter
time
0.000 ... 30.000 s
32.09
Supervision 1 low
-21474836.00...
21474836.00
32.10
Supervision 1 high
-21474836.00...
21474836.00
32.11
Supervision 1
hysteresis
0.00...100000.00
32.15
Supervision 2
function
Disabled
Low
High
Abs low
Description
If running, the drive trips on fault
Selects the signal to be monitored by signal supervision
function 1.
None.
01.01 Motor speed used
01.06 Output frequency
01.07 Motor current
(page 67).
01.10 Motor torque
(page 67).
01.11 DC voltage
(page 67).
01.14 Output power
(page 68).
12.11 AI1 actual value
(page 84).
12.21 AI2 actual value
(page 86).
28.02 Frequency ref ramp output
05.11 Inverter temperature
40.01 Process PID output actual
40.02 Process PID feedback actual
40.03 Process PID setpoint actual
40.04 Process PID deviation actual
Source selection (see
Terms and abbreviations
Defines a filter time constant for the signal monitored by
signal supervision 1.
Signal filter time.
Defines the lower limit for signal supervision 1.
Low limit.
Defines the upper limit for signal supervision 1.
Upper limit.
Defines the hysteresis for the signal monitored by signal
supervision 1.
Hysteresis.
Selects the mode of signal supervision function 2. Determines
how the monitored signal (see parameter 32.17) is compared
to its lower and upper limits
The action to be taken when the condition is fulfilled is
selected by 32.16.
Signal supervision 2 not in use.
Action is taken whenever the signal falls below its lower limit.
Action is taken whenever the signal rises above its upper
limit.
Action is taken whenever the absolute value of the signal falls
below its (absolute) lower limit.
80B0 Signal supervision
(page 67).
(page 67).
(page 101).
(page 72).
(page 130).
(page 130).
(page 130).
(page 130).
on page 64).
(32.19
and
32.20
respectively).
Parameters 115
Def/FbEq16
1.
3
Frequency
0
1
3
4
6
7
8
9
10
22
23
24
25
26
27
-
0.000 s
1000 = 1 s
0.00
-
0.00
-
0.00
-
Disabled
0
1
2
3

Hide quick links: