Summary of Contents for ABB ACH580-01

  • Page 1 — 用于HVAC的ABB变频器 ACH580-01 变频器 外形尺寸 R1至 R5 快速安装和启动指导 3ABD00046115 中文A版本 基于: 3AXD50000044861 英文A版本 生效日期:2018-06-15...
  • Page 2 相关手册列表 代码 ( 英文 ) 代码 ( 中文 ) 变频器手册和指导 ACH580 HVAC 控制程序固件手册 3AXD50000027537 3ABD00045445 ACH580-01 (0.75 至 250 kW, 1 至 350 hp) 硬件手册 3AXD50000044839 ACH580-01 外形尺寸 至 快速安装和启动指导 3AXD50000044861 ACH580-01 外形尺寸 至 快速安装和启动指导 3AXD50000036602 ACH580 安装、运行和维护手册 (I, O & M) (仅US) 3AXD50000049127 助手控制盘用户手册...
  • Page 3: Table Of Contents

    目录 目录 相关手册 ZH – R1…R4 快速安装指南 遵循安全指导 ............. . 7 检查电容是否需要重整...
  • Page 4 目录 EN – R1…R4 Quick installation guide Obey the safety instructions ..........31 Check if capacitors need to be reformed .
  • Page 5 目录 II IEC, UN = 480 V ............57 III gC .
  • Page 6 Providing feedback on ABB Drives manuals ........
  • Page 7: Zh - R1

    ZH – R1…R4 快速安装指南 ZH – R1…R4 快速安装指南 本指南简要介绍如何安装变频器。如需了解有关安装的完整信息,请参阅 ACH580- 01 (0.75 to 250 kW) hardware manual (3AXD50000162420)。有关启动说明,请参阅 – 快速启动指南 第 页的 一章。 如需阅读手册,请访问 www.abb.com/drives/documents,搜索文件编号。 遵循安全指导 警告!请遵循这些指导。如果您忽略指导,可能会导致受伤、死亡或设备损 坏: • 如果您不是具有资格的电工,请勿进行电气安装工作。 • 当接上主电源时,切勿在变频器、电机电缆或电机上操作。如果变频器已经连 接到了输入电源,请在断开输入电源后等待5分钟。 • 当变频器或外部控制电路连接了电源时,切勿操作控制电缆。 • 在安装时,确保不让钻孔和研磨出的碎屑进入变频器。 • 确保变频器下方的地面和安装变频器的墙面是阻燃的。 检查电容是否需要重整...
  • Page 8: 保护变频器和输入电缆

    ZH – R1…R4 快速安装指南 ACH580-01 0.75 to 250 kW hardware manual (3AXD50000162420 [英文])中 的 Technical data(技术数据)一章。 保护变频器和输入电缆 III gC IV uR or aR 请参阅表 (第 页)和 (第 页);(UL:第 页的表 V UL )了解熔断器的信息。 如果使用gG熔断器,请确保熔断器的熔断时间少于0.5秒。遵循当地法规。 在墙上安装变频器 R1…R4 Figures A 请参阅第 页的图 。...
  • Page 9: 贴上警告贴纸

    ZH – R1…R4 快速安装指南 贴上警告贴纸。 请参阅第 页的图 。 7. 贴上本地语言的剩余电压警告贴纸。 检查与IT(浮地)和角接地的TN系统的兼容性  EMC 滤波器 内置EMC滤波器不适用于IT(浮地)系统或角接地的TN系统。在将变频器连接到 电网前断开EMC滤波器的连接。查看第 页的表。 警告!请勿将连接了内置EMC滤波器的变频器安装在IT系统(浮地电源系统 或高阻抗接地系统[超过30 ohm]的电源系统),否则系统将可能会通过变频 器的EMC滤波器电容连接到接地线。这可能会导致危险或损坏变频器。 请勿将连接了内置EMC滤波器的变频器安装在角接地的TN系统,否则可能会损坏变 频器。 注:不连接内置EMC滤波器,变频器的EMC兼容性会显著降低。  压敏电阻 压敏电阻不适用于IT(浮地)系统。在将变频器连接到电网前断开压敏电阻的连接。 查看第 页的表。 警告!安装变频器时请勿将压敏电阻连接到 IT 系统(未接地电源系统或高阻 抗接地系统[超过 30 ohm ]的电源系统),否则会损坏压敏电阻的电路。 如须断开EMC滤波器(EMC)或压敏电阻(VAR),请查看下表。具体操作说明请参 阅第 页。 外形尺寸 EMC 滤 对称接地...
  • Page 10 ZH – R1…R4 快速安装指南 外形尺寸 EMC 滤 对称接地 TN 系统 角接地 TN 系统 IT 系统(浮地或 压敏电阻 (TN-S 系统) 高阻抗接地系统 波器 (VAR) [>30 ohms]) (EMC) 外形尺寸 R4 不能 不断开 断开 用在角接地 TN 系 (2 个螺 统中。 钉) 不断开 断开 (1 个螺 钉)...
  • Page 11: 断开Emc滤波器或压敏电阻(必要时

    ZH – R1…R4 快速安装指南  断开EMC滤波器或压敏电阻(必要时) 如果必要时要断开内置 EMC 滤波器或压敏电阻,请执行以下操作: 1. 关断变频器电源。 页的图 B1。 2. 打开前盖(如果尚未打开),请参阅第 3. R1…R3:断开内置 EMC 滤波器的连接,卸下该 EMC螺钉 (3a) 并放在储存位 置 (3b)。 R4:卸下两颗 EMC 螺钉,断开内置 EMC 滤波器。 4. R1…R3:断开地对相压敏电阻的连接,卸下压敏电阻螺钉 (4a) 并放在储存位置 (4b)。 R4:卸下压敏电阻螺钉,断开压敏电阻。...
  • Page 12: 连接电缆

    ZH – R1…R4 快速安装指南 连接电缆 ( 67 页)、C2、D、E1、E2、F、G1、G2 R1…R4 Figures 请参阅 第 和 (第 页)。 1. 从电缆入口拆下橡胶绝缘圈。 电机电缆请使用对称屏蔽线。如果屏蔽电缆为变频器或电机的唯一保护接地线,请确 保地线有足够的导电能力。 2. 在橡胶绝缘圈上切出足够大的孔。将绝缘圈套入电缆。 3. 如图 3a 和 3b 所示准备好电机电缆的两端(展示出了两种不同的电机电缆)。 注:将屏蔽线裸线做360度接地。将黄绿色双绞屏蔽线标记为保护接地线。 4. 将电缆从电缆入口孔中穿过,并将绝缘圈固定到孔上。 5. 连接电机电缆: • 将供电电缆夹的接地支架紧固到电缆的剥开部分,将屏蔽线做360度接地 (5a)。 • 将电缆绞合的屏蔽层连接到接地端子(5b)。 • 将电缆的相线连接到T1/U、T2/V和T3/W端子(5c)。按图中给出的力矩拧紧 螺钉。 6.
  • Page 13: 连接控制电缆

    ZH – R1…R4 快速安装指南 连接控制电缆 和 I2。图中所示为一根模拟信号电缆和一根数字信号电缆的 请参阅第 页的图 示例。请按所使用的默认配置进行连接。HVAC 默认配置的默认连接见第 默认 I/O 连接14 页的一节。 1. 卸下前盖(如果尚未卸下)。请参阅第 页的关闭电源并打开盖板一节。 模拟信号电缆连接示例: 2. 在橡胶绝缘圈上切一个足够大的孔,然后将绝缘圈套入电缆。将电缆从电缆入口 的孔中穿过并将绝缘圈固定到孔上。 3. 将电缆的外屏蔽层在接地夹下做360度接地。靠近控制电路板端子的电缆的剥开 部分要尽可能少。在SCR1端子处将成对电缆屏蔽和接地线也做接地。 4. 如图所示进行布线。 5. 将导线连接到控制板的对应端子上,并紧固到 0.5…0.6 N·m(0.4 lbf·ft)。 6. 将全部控制电缆都绑到提供的电缆捆绑架上。...
  • Page 14: 默认 I/O 连接

    ZH – R1…R4 快速安装指南 默认 I/O 连接 HVAC默认配置的默认I/O连接如下所示。 参考电压与模拟输入和输出 信号线屏蔽 频率/速度给定值:0…10 V 1…10 kohm AGND 模拟输入的公共端 +10V 参考电压 10 VDC 实际反馈:0…10 V AGND 模拟输入的公共端 输出频率:0…10 V 最大 500 ohm 输出电流:0…20 mA AGND 模拟输出的公共端 辅助电压输出和可编程数字输入 X2 & X3 +24V 辅助电压输出 +24 VDC, 最大 250 mA DGND 辅助电压输出的公共端...
  • Page 15: 安装可选模块(如有

    ZH – R1…R4 快速安装指南 安装可选模块(如有) 请参阅 ACH580-01 0.75 to 250 kW hardware manual 3AXD50000162420 中 的 Electrical installation(电气安装)一章。 装回盖板 页的图 J。 请参阅第 1. 将盖板顶部内侧的搭扣放进外壳上的扣眼 (1a),然后在底部按下盖板 (1b)。 2. 用螺丝刀将紧固螺钉拧紧。 – 快速启动指南 有关启动说明,请参阅第 页的 一章。...
  • Page 16 ZH – R1…R4 快速安装指南...
  • Page 17: Zh - R5 快速安装指南

    ZH – R5 快速安装指南 ZH – R5 快速安装指南 本指南简要介绍如何安装变频器。如需了解有关安装的完整信息,请参阅 ACH580- 0.75 to 250 kW hardware manual (3AXD50000162420)。有关启动说明,请 – 快速启动指南 参阅第 页的 一章。 如需阅读手册,请访问 www.abb.com/drives/documents,搜索文件编号。 遵循安全指导 警告!请遵循这些指导。如果您忽略指导,可能会导致受伤、死亡或设备损 坏: • 如果您不是具有资格的电工,请勿进行电气安装工作。 • 当接上主电源时,切勿在变频器、电机电缆或电机上操作。如果变频器已经连 接到了输入电源,请在断开输入电源后等待5分钟。 • 当变频器或外部控制电路连接了电源时,切勿操作控制电缆。 • 在安装时,确保不让钻孔和研磨出的碎屑进入变频器。 • 确保变频器下方的地面和安装变频器的墙面是阻燃的。 检查电容是否需要重整 如果变频器已经有一年或更长时间未通电(存放或未用),则必须重整电容。...
  • Page 18: 保护变频器和输入电缆

    ZH – R5 快速安装指南 ACH580-01 (0.75 to 250 kW) hardware manual (3AXD50000162420)中的 Technical data (技术数据) 一章。 保护变频器和输入电缆 III gC IV uR or aR V UL 请参阅表 (第 页)和 (第 页);(UL:第 页的 表 62)了解熔断器的信息。 如果使用gG熔断器,请确保熔断器的熔断时间少于0.5秒。遵循当地法规。 在墙上安装变频器 R5 Figures A 请参阅第 页的图...
  • Page 19: 压敏电阻

    ZH – R5 快速安装指南 警告!请勿将连接了内置EMC滤波器的变频器安装在IT系统(浮地电源系统 或高阻抗接地系统[超过30 ohm]的电源系统),否则系统将可能会通过变频 器的EMC滤波器电容连接到接地线。这可能会导致危险或损坏变频器。 请勿将连接了内置EMC滤波器的变频器安装在角接地的TN系统,否则可能会损坏 变频器。 注:不连接内置EMC滤波器,变频器的EMC兼容性会显著降低。  压敏电阻 压敏电阻不适用于IT(浮地)系统。在将变频器连接到电网前断开压敏电阻的连接。 请查看第 页的表格。 警告!安装变频器时请勿将压敏电阻连接到IT系统(浮地电源系统或高阻抗 接地系统[超过30 ohm]的电源系统),否则会损坏压敏电阻的电路。 如须断开EMC滤波器(EMC)或压敏电阻(VAR),请查看下表。具体操作说明请参 阅第20页。 外形尺寸 EMC 滤 对称接地 TN 系统 角接地 TN 系统 IT 系统(浮地或 压敏电阻 (TN-S 系统) 高阻抗接地系统 波器 (VAR) [>30 ohms]) (EMC) 外形尺寸...
  • Page 20: 断开Emc滤波器或压敏电阻(必要时

    ZH – R5 快速安装指南  断开 滤波器或压敏电阻(必要时) 如果必要时要断开内置 EMC 滤波器或压敏电阻,请执行以下操作: 1. 关断变频器电源。 页的图 B。 2. 打开前盖(如果尚未打开),请参阅第 3. 卸下两颗 EMC 螺钉,断开内置 EMC 滤波器。 4. 卸下压敏电阻螺钉,断开压敏电阻。...
  • Page 21: 连接电缆

    ZH – R5 快速安装指南 连接电缆 和 E。 请参阅图 (第 页)、 1. 将本地语言的剩余电压警告贴纸贴在控制电路板旁。 2. 用螺丝刀松开搭扣,并将护罩拉出,卸下供电电缆端子上的护罩。 电机电缆请使用对称屏蔽线。如果屏蔽电缆为变频器或电机的唯一保护接地线,请确 保地线有足够的导电能力。 3. 在橡胶绝缘圈上切出足够大的孔。将绝缘圈套入电缆。 4. 如图 4a 和 4b 所示准备好电机电缆的两端(展示出了两种不同的电机电缆)。 注:将屏蔽线裸线做360度接地。将黄绿色双绞屏蔽线标记为保护接地线。 5. 将电缆从电缆入口孔中穿过,并将绝缘圈固定到孔上。 6. 连接电机电缆: 将供电电缆夹的接地支架紧固到电缆的剥开部分,将屏蔽线做 360 度接地 • (6a)。 • 将电缆绞合的屏蔽层连接到接地端子 (6b)。 将电缆的相线连接到 T1/U、T2/V 和 T3/W 端子 (6c)。按图中给出的力矩拧 •...
  • Page 22: 连接控制电缆

    ZH – R5 快速安装指南 连接控制电缆 页的图 G。图中所示为一根模拟信号电缆和一根数字信号电缆的示例。 请参阅第 默认 I/O 请按所使用的默认配置进行连接。HVAC 默认配置的默认连接见第 页的 连接 一节。 关闭电源并打开盖板 1. 卸下前盖(如果尚未卸下)。请参阅第 页的18一节。 模拟信号电缆连接示例: 2. 在橡胶绝缘圈上切一个足够大的孔,然后将绝缘圈套入电缆。将电缆从电缆入口 的孔中穿过并将绝缘圈固定到孔上。 3. 将电缆的外屏蔽层在接地夹下做360度接地。靠近控制电路板端子的电缆的剥开 部分要尽可能少。在SCR1端子处将成对电缆屏蔽和接地线也做接地。 3. 如图所示进行布线。 4. 将导线连接到控制板的对应端子上,并紧固到 0.5…0.6 N·m(0.4 lbf·ft)。 5. 将全部控制电缆都绑到提供的电缆捆绑架上。...
  • Page 23: 默认 I/O 连接

    ZH – R5 快速安装指南 默认 I/O 连接 HVAC默认配置的默认I/O连接如下所示。 参考电压与模拟输入和输出 信号线屏蔽 频率/速度给定值:0…10 V 1…10 kohm AGND 模拟输入的公共端 +10V 参考电压10 VDC 实际反馈:0…10 V AGND 模拟输入的公共端 输出频率:0…10 V 最大500 输出电流:0…20 mA AGND 模拟输出的公共端 X2 & X3 辅助电压输出和可编程数字输入 +24V 辅助电压输出 +24 VDC, 最大 250 mA DGND 辅助电压输出的公共端...
  • Page 24: 安装可选模块(如有

    ZH – R5 快速安装指南 安装可选模块(如有) 请参阅 ACH580-01 (0.75 to 250 kW) hardware manual (3AXD50000162420)中的 Electrical installation (电气安装)一章。 装回盖板 请参阅第 页的图 。 1. IP21,装回箱盖:向上滑动盖子 (1a),然后拧紧固定螺钉 (1b)。 2. IP21,装回模块盖:将盖板顶部内侧的搭扣放进外壳上的扣眼 (2a),在底部按下 盖板 (2b),然后拧紧固定螺钉 (2c)。 3. IP55,装回前盖:将盖板顶部内侧的搭扣放进外壳上的扣眼 (3a),在底部按下盖 板 (3a),然后拧紧固定螺钉 (3b)。 – 快速启动指南 有关启动说明,请参阅第...
  • Page 25: Zh - 快速启动指南

    ZH – 快速启动指南 ZH – 快速启动指南 本指南介绍如何在 HVAC 控制盘上使用 “ 首次启动助手 ” 启动变频器。 如需了解有 关启动的完整信息,请参阅 ACH580 firmware manual (3AXD50000027537 [ 英语 ])。 启动之前 ZH – R1…R4 快速安装指南 一章 (外形尺寸 R1…R4)或第 确保按照第 页的 页 ZH – R5 快速安装指南 一章 (外形尺寸 R5)所述安装变频器。 的...
  • Page 26 ZH – 快速启动指南 下一步 选择调试 ACH580 并按 ( ) 。 电机的下列额定值设置请参考电机铭牌。完全按照电机铭牌所示输入值。 感应 (异步)电机铭牌示例: ABB Motors motor M2AA 200 MLA 4 IEC 200 M/L 55 Ins.cl. F IP 55 IA/IN t E/s r/min 690 Y 1475 32.5 0.83 400 D 1475 0.83...
  • Page 27 ZH – 快速启动指南 此步骤是可选的,要求转动电机。如果这可能会导 致任何风险或者机械设置不允许此动作,请勿执行 此操作。 要执行方向测试,选择转动电机并按 (下一步) 。 在控制盘上按手形键 ,启动变频器。 Hand 检查电机的转动方向。 如果是正向,选择是的,电机正在正向旋转并按 (下一步)继续。 如果不是正向,选择不,修改方向并按 (下一步)继续。 选择希望使用的单位并按 (下一步) 。 如有必要,修改面板上显示的单位。 进入 • 按 所选行的编辑视图。 滚动视图。 • 用 和 按 (下一步)进入下一个视图。...
  • Page 28 ZH – 快速启动指南 要在编辑视图上选择一个值: • 用 和 选择值。 按 (保存)接受新设置,或按 (取消) 来返回原先视图而不做任何修改。 设置日期和时间以及日期时间显示格式。 进入 • 按 所选行的编辑视图。 • 用 滚动视图。 和 按 (下一步)进入下一个视图。 。 要给变频器命名 (显示在顶部) ,按 如果您不想改变默认名称 (ACH580),按 (下一步)继续。 有关编辑文字的更多信息,请参阅 ACH580 firmware manual (3AXD50000027537 [ 英语 ])。 首次启动到此完成,变频器已经可以使用了。 按 (完成)进入主页视图。...
  • Page 29 ZH – 快速启动指南 2 – 手动 / 关闭 / 自动运行 变频器可以通过远程控制或本地控制, 在本地控制中,又有两种不同的模式。 远程控制:从 I/O 或现场总线控制变频器。 • 视图的顶行显示 Auto。 本地控制:从控制盘控制变频器。 • 视图顶行显示 Off,也就是说,变频器处于关闭 模式。变频器停止运行。 • 视图顶行显示 Hand,也就是说,变频器处于手 动模式。变频器运行中。 Hand 模式中的初始参 照值复制自变频器的参照值。 顶行的符号 表示您可以用 和 修改参 照值。 下列图表显示了当您按下 Hand、 Off 或 Auto 按钮时的状态变化。...
  • Page 30 ZH – 快速启动指南...
  • Page 31: Obey The Safety Instructions

    EN – R1…R4 Quick installation guide This guide briefly describes how to install the drive. For complete information on installation, see ACH580-01 (0.75 to 250 kW) hardware manual (3AXD50000044839 [English]). For start-up instructions, see chapter EN – Quick start-up guide page 51.
  • Page 32: Select The Power Cables

    -15 to +50 °C (+5 to +122 °F). No condensation or frost is allowed. For more information on the ambient temperature and derating, see chapter Technical data in ACH580-01 (0.75 to 250 kW) hardware manual (3AXD50000044839 [English]). Protect the drive and input power cable...
  • Page 33: Switch Off The Power And Open The Cover

    EN – R1…R4 Quick installation guide 33 Switch off the power and open the cover See figure on page 67. 2. Switch off the power from the drive. 3. Remove the front cover: Loosen the retaining screw, if any, with a screwdriver (3a) and lift the cover from the bottom outwards (3b) and then up (3c).
  • Page 34: Emc Filter

    34 EN – R1…R4 Quick installation guide  Ground-to-phase varistor The ground-to-phase varistor is not suitable for use on an IT (ungrounded) system. Disconnect the ground-to-phase varistor before connecting the drive to the supply network. Check the table on page 34. WARNING! Do not install the drive with the ground-to-phase varistor connected on an IT system (an ungrounded power system or a high- resistance-grounded [over 30 ohms] power system), otherwise the varistor circuit can...
  • Page 35: Ground-To-Phase Varistor

    EN – R1…R4 Quick installation guide 35  Disconnect EMC filter or ground-to-phase varistor, if needed To disconnect the internal EMC filter or ground-to-phase varistor, if needed, do as follows: 1. Switch off the power from the drive. 2. Open the front cover, if not already opened, see figure on page 67.
  • Page 36 36 EN – R1…R4 Quick installation guide Connect the power cables See figures (page 67), C2, D, E1, E2, F, G1, R1…R4 Figures H (page 69). 1. Remove the rubber grommets from the cable entry. Use symmetrical shielded cable for motor cabling. If the cable shield is the sole PE conductor for drive or motor, make sure that is has sufficient conductivity for the PE.
  • Page 37: Connect The Power Cables

    EN – R1…R4 Quick installation guide 37 Connect the control cables See figures on page 69. It shows an example with one analog signal cable and one digital signal cable. Make the connections according to the default configuration in use. The default connections of the HVAC default configuration are shown in section Default I/O connections on page 38.
  • Page 38: Default I/O Connections

    OUT1 Safe torque off. Factory connection. Both circuits OUT2 must be closed for the drive to start. See chapter The Safe torque off function in ACH580-01 (0.75 SGND to 250 kW) hardware manual (3AXD50000044839 [English]). Total load capacity of the Auxiliary voltage output +24V (X2:10) is 6.0 W (250 mA / 24 V DC).
  • Page 39: Install Optional Modules, If Any

    EN – R1…R4 Quick installation guide 39 Install optional modules, if any See chapter Electrical installation in ACH580-01 (0.75 to 250 kW) hardware manual (3AXD50000044839 [English]). Reinstall cover See figure on page 70. 1. Put the tabs on the inside of the cover top in their counterparts on the housing (1a) and then press the cover at the bottom (1b).
  • Page 40 40 EN – R1…R4 Quick installation guide...
  • Page 41: En - R5 Quick Installation Guide

    EN – R5 Quick installation guide This guide briefly describes how to install the drive. For complete information on installation, see ACH580-01 (0.75 to 250 kW) hardware manual (3AXD50000044861 [English]). For start-up instructions, see chapter EN – Quick start-up guide page 51.
  • Page 42: Select The Power Cables

    -15 to +50 °C (+5 to +122 °F). No condensation or frost is allowed. For more information on the ambient temperature and derating, see chapter Technical data in ACH580-01 (0.75 to 250 kW) hardware manual (3AXD50000044861 [English]). Protect the drive and input power cable...
  • Page 43: Switch Off The Power And Open The Cover

    EN – R5 Quick installation guide 43 Switch off the power and open the cover See figure on page 71. 2. Switch off the power from the drive. 3. IP21, Remove the module cover: Loosen the retaining screws with a screwdriver (3a) and lift the cover from the bottom outwards (3b) and then up (3c).
  • Page 44 44 EN – R5 Quick installation guide Check from the table below if you have to disconnect the EMC filter (EMC) or ground- to-phase varistor (VAR). For instructions on how to do this, see page 45. Frame Ground- Symmetrically Corner grounded IT systems sizes filter...
  • Page 45: Disconnect Emc Filter Or Ground-To-Phase Varistor, If Needed

    EN – R5 Quick installation guide 45  Disconnect EMC filter or ground-to-phase varistor, if needed To disconnect the internal EMC filter or ground-to-phase varistor, if needed, do as follows: 1. Switch off the power from the drive. 2. Open the front cover, if not already opened, see figure on page 71.
  • Page 46: Connect The Power Cables

    46 EN – R5 Quick installation guide Connect the power cables See figures (page 72), and E. 1. Attach the residual voltage warning sticker in the local language next to the control board. 2. Remove the shroud on the power cable terminals by releasing the clips with a screwdriver and pulling the shroud out.
  • Page 47: Connect The Control Cables

    EN – R5 Quick installation guide 47 Connect the control cables See figure on page 73. It shows an example with one analog signal cable and one digital signal cable. Make the connections according to the default configuration in use. The default connections of the HVAC default configuration are shown in section Default I/O connections on page 48.
  • Page 48: Default I/O Connections

    OUT1 Safe torque off. Factory connection. Both circuits OUT2 must be closed for the drive to start. See chapter The Safe torque off function in ACH580-01 (0.75 SGND to 250 kW) hardware manual (3AXD50000044861 [English]). Total load capacity of the Auxiliary voltage output +24V (X2:10) is 6.0 W (250 mA / 24 V DC).
  • Page 49: Install Optional Modules, If Any

    EN – R5 Quick installation guide 49 Install optional modules, if any See chapter Electrical installation in ACH580-01 (0.75 to 250 kW) hardware manual (3AXD50000044861 [English]). Reinstall cover See figure on page 73. 1. IP21, Reinstall the box cover: Slide the cover upwards (1a) and tighten the retaining screws (1b).
  • Page 50 50 EN – R5 Quick installation guide...
  • Page 51: En - Quick Start-Up Guide

    EN – Quick start-up guide 51 EN – Quick start-up guide This guide describes how to start-up the drive using the First start assistant on the HVAC control panel. For complete information on start-up, see ACH580 firmware manual (3AXD50000027537 [English]). Before you start Ensure that the drive has been installed as described in chapter EN –...
  • Page 52 Refer to the motor nameplate for the following nominal value settings of the motor. Enter the values exactly as shown on the motor nameplate. Example of a nameplate of an induction (asynchronous) motor: ABB Motors motor M2AA 200 MLA 4 IEC 200 M/L 55 Ins.cl.
  • Page 53 EN – Quick start-up guide 53 To change a value in an edit view: • Use to move the cursor left and right. • Use to change the value. Press (Save) to accept the new setting, or press (Cancel) to go back to the previous view without making changes.
  • Page 54 54 EN – Quick start-up guide Change the units shown on the panel if needed. • Go to the edit view of a selected row by pressing • Scroll the view with Go to the next view by pressing (Next). To select a value in an edit view: •...
  • Page 55 EN – Quick start-up guide 55 The Home view monitoring the values of the selected signals is shown on the panel.
  • Page 56 56 EN – Quick start-up guide 2 – Hand/Off/Auto operation The drive can be in remote control or local control, and in local control there are additionally two different modes. Remote control: Drive is controlled from the I/O or the fieldbus. •...
  • Page 57: Iec, Un = 480 V

    Ratings and fuses I IEC, U = 400 V Type Input Max. Output ratings Heat Air flow Frame ACH580 rating current dissipation size Nominal use -01- 3-phase U = 400 V (380…415 V) 02A7-4 0.75 03A4-4 04A1-4 05A7-4 07A3-4 10.1 09A5-4 13.0 12A7-4...
  • Page 58: Iv Ur Or Ar

    III gC Type Min. Input gG (IEC 60269) North short- current American ACH580 Nominal Voltage ABB type circuit -01- type current rating 60269 current ACH580 size -01- 3-phase U = 400 or 480 V (380…415 V or 440…480 V) = 480 V...
  • Page 59 V UL UL/NEC Input IEC type current type ACH580 Bussmann UL class Maximum Voltage -01- ACH580 type current rating -01- 02A1-4 JJS-15 02A7-4 03A0-4 JJS-15 03A4-4 03A5-4 JJS-15 04A1-4 04A8-4 JJS-15 05A7-4 07A6-4 JJS-15 09A5-4 012A-4 12.0 JJS-15 12A7-4 014A-4 14.0 JJS-30 018A-4...
  • Page 61: Ratings And Fuses

    3AXD00000586715.xls III gC Type Min. Input gG (IEC 60269) North short- current American ACH580 Nominal Voltage ABB type circuit -01- type current rating 60269 current ACH580 size -01- 3-phase U = 400 or 480 V (380…415 V or 440…480 V)
  • Page 62 V UL UL/NEC Input IEC type current type ACH580 Bussmann UL class Maximum Voltage -01- ACH580 type current rating -01- 077A-4 JJS-100 096A-4 JJS-150 106A-4 3AXD00000586715.xls J...
  • Page 63: Compliance With The European Machinery Directive 2006/42/Ec

    Compliance with the European Machinery Directive 2006/42/EC Declaration of conformity...
  • Page 65: Compliance With The European Machinery Directive 2006/42/Ec

    Compliance with the European Machinery Directive 2006/42/EC Declaration of conformity...
  • Page 67 R1…R4 Figures A R3…R4 R1…R2: M5 × 4 ACH580-01 R1…R4 R3…R4: M6 UDC+ T1/U T2/V T3/W × 4 × 4 × 4 3 ~ M (PE) (PE) ONLY IT AND CORNER-GROUNDED TN SYSTEMS R1…R4 R1…R3 3a 3b U1-V1, U1-W1, V1-W1...
  • Page 68 R1…R2 R1…R2 INPUT BREAKERS MOTOR INPUT BREAKERS MOTOR T1/U T2/V T3/W T1/U T2/V T3/W UDC+ UDC+ INPUT BREAKERS MOTOR INPUT BREAKERS MOTOR T1/U T2/V T3/W UDC+ T1/U T2/V T3/W UDC+ Frame Frame R1…R2 size size N·m lbf·ft N·m lbf·ft N·m lbf·ft N·m lbf·ft...
  • Page 69 R1…R4 Figures H R1…R2 R1…R2 INPUT BREAKERS MOTOR T1/U T2/V T3/W UDC+ INPUT BREAKERS MOTOR T1/U T2/V T3/W UDC+ 0.5…0.6 N·m 0.5…0.6 N·m 0.5…0.6 N·m 0.5…0.6 N·m 0.5…0.6 N·m 0.5…0.6 N·m INPUT BREAKERS MOTOR T1/U T2/V T3/W UDC+...
  • Page 70 IP21 IP55 R1…R2 IP21 R4, IP55 R3 IP55 R4 × 2 × 2 × 2...
  • Page 71 R5 Figures A IP21 IP21 IP21 R5 IP21 R5 IP55 × 2 M5 × 3 1000 24.09 24.09 V DC, > 100 22.87 22.87 Mohm 6.30 6.30 d > U1-V1, U1-W1, V1-W1 U1-PE, V1-PE, W1-PE e > × 2 R5 IP21 R5 IP55 ×...
  • Page 72 4a 4b ACH580-01 R5 T1/U T2/V T3/W Frame size L1, L2, L3, N·m lbf·ft N·m lbf·ft N·m lbf·ft 3 ~ M Frame size T1/U, T2/V, T3/W N·m lbf·ft N·m lbf·ft N·m lbf·ft...
  • Page 73 R5 Figures F IP21 IP21 0.5…0.6 N·m 0.5…0.6 N·m IP55 × 8...
  • Page 75 近的客户提供服务,自助服务站为自己的客户提供服务。为了得到专业的 ABB 变频器维修 服务及购买到原厂备件,请您选择 ABB 变频器授权的服务站,我们将为您提供优质的服 务。 ABB 变频器授权服务站的联系方式可以在 ABB 官网找到 , 具体方法如下: http://new.abb.com/cn 进入 网页 , 直接搜索 “ 服务站 ”,即可进入 “ABB 变频器授权 服务站 ” 页面 http://new.abb.com/cn 网页 , 按照如下路径进入 ABB 变频器授权服务站页面: 或者进入 产品指南 >> 电气变频器,逆变器和变流器 >> 变频器服务 >>ABB 变频器授权服务站...
  • Page 76 联系我们 www.abb.com/drives www.abb.com/drivespartners 北京 ABB 电气传动系统有限公司 地址:北京市朝阳区酒仙桥北路甲 10 号 401 楼 100015 电话:+86 58217788 传真:+86 58217618 24 小时 ×365 天技术热线:+86 400 810 8885 网址:www.abb.com.cn/drives 全国各地区销售代表处联系方式 : 上海办事处 广州办事处 西安办事处 中国 上海市 200023 中国 广州市 519623 中国 陕西省西安市 710075 黄浦区蒙自路 763 号丰盛创建大厦 16 层...